u
n6: Motor Line-to-Line Resistance Online Tuning
The drive can tune the motor line-to-line resistance during run in order to prevent torque loss due to a rise in motor temperature
increase, especially at low speeds.
n
n6-01: Motor Line-to-Line Resistance Online Tuning Selection
No.
Name
Setting Range
Default
n6-01
Motor Line-to-Line Resistance Online Tuning
0 or 1
1
Setting 0: Disabled
Setting 1: Enabled
u
n8: PM Motor Control
These parameters are available when using the special Open Loop Vector Control for permanent magnet motors and can be
used to adjust the control performance.
n
n8-45: Speed Feedback Detection Control Gain (for PM OLV)
Sets the gain for internal speed feedback detection control. Although this setting rarely needs to be changed, adjustment may
be necessary under the following conditions:
• Increase this setting if motor oscillation or hunting occurs.
• Decrease this setting in increments of 0.05 to decrease the drive responsiveness.
No.
Name
Setting Range
Default
n8-45
Speed Feedback Detection Control Gain
0.00 to 10.00
0.80
n
n8-47: Pull-In Current Compensation Time Constant (for PM OLV)
Sets the time constant for making the actual current and the pull-in current agree.
Although this setting rarely needs to be changed, adjustment may be necessary under the following conditions:
• Increase this setting when it takes too long for the reference value for the pull-in current to match the target value.
• Decrease this setting if motor oscillation occurs.
No.
Name
Setting Range
Default
n8-47
Pull-In Current Compensation Time Constant
0.0 to 100.0 s
5.0 s
n
n8-48: Pull-In Current (for PM OLV)
Tells the drive the amount of d-axis current to be provided to the motor during no-load operation at a constant speed. Set as a
percentage of the motor rated current.
• Increase this setting when hunting occurs or the motor speed is unstable while running at a constant speed.
• If there is too much current when driving a light load at a constant speed, then reduce this level slightly.
No.
Name
Setting Range
Default
n8-48
Pull-In Current
<1>
Determined by
E5-01
<1> Setting range varies depending on drive software version. Software versions PRG: 1018 and later disable pull-in current when n8-48 = 0, and allow
the pull-in current to be changed during Run.
PRG: 1018 and later: 0% or 20 to 200%
PRG: 1017 and earlier: 20 to 200%
n
n8-49: d Axis Current for High Efficiency Control (for PM OLV)
Sets the amount of d axis current when using Energy Saving control as a percentage of the motor rated current.
Although this setting seldom needs to be changed, please note the following:
• If motor operation is unstable when driving heavy loads, try increasing this setting (towards 0).
• If motor parameters (E5) have been changed, this value will be reset to 0 and has to be readjusted.
5.9 n: Special Adjustments
YASKAWA ELECTRIC SIEP C710606 18F YASKAWA AC Drive – V1000 Technical Manual
243
5
Parameter Details