Just-FiTTER
This Just-FiTTER function provides the effect of the overshoot suppression and
the following items can be set:
• When the control method is other than the ON/OFF control (CtrL
≠
0), the
display and setting can be configured.
• Function of Just-FiTTER overshoot limit/restraint/control coefficient (JF.ov)
When the Just-FiTTER overshoot limit/restraint/control coefficient (JF.ov) is set
to “0”, the Just-FiTTER function becomes invalid.
When this coefficient is “1” or more, the effect of the overshoot
limit/restraint/control becomes larger as the coefficient becomes larger.
• Function of Just-FiTTER settling band (JF.bd)
When the % value of the width of the absolute value deviation to the PV range is
larger than the set value, the Just-FiTTER function is started. When this value is
smaller than the set value, this is judged as that the PV is settled by the Just-
FiTTER function.
■
RationaLOOP
This RationaLOOP function suppresses the unstable trend if the immediate
response to external disturbance is increased by the high precision control logic.
The following items can be set:
• When the control method is other than the ON/OFF control (CtrL
≠
0), the
display and setting can be made.
■
SP lag
This SP lag function suppresses changes in MV when the SP is changed. The
following items can be set:
• When the control method is other than the ON/OFF control (CtrL
≠
0), the
display and setting can be made.
• Function of SP lag constant (SP.Lg)
When the SP lag constant is set at "0.0", the SP lag function becomes invalid.
When this value is "0.1" or more, changes in MV when the SP is changed
become smaller and the effect of the overshoot suppression becomes larger as the
value becomes larger.
5-28
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Item (Bank)
Display
Contents
Initial value
User level
Just-FiTTER overshoot
limit/restraint/control
coefficient
(Extended tuning bank)
0 to 100
(“0”: JF function disabled)
0
Standard,
High function
Just-FiTTER settling band
(Extended tuning bank)
0.00 to 10.00%
0.30%
High function
Item (Bank)
Display
Contents
Initial value
User level
Control algorithm
(Extended tuning bank)
0: PID (Conventional PID)
1: RationaLOOP (High-performance PID)
0
Standard,
High function
Item (Bank)
Display
Contents
Initial value
User level
SP lag constant
(Extended tuning bank)
0.0 to 999.9
(No effect when set at “0.0”.)
0.0
High function
Содержание SDC35
Страница 16: ......
Страница 17: ......
Страница 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Страница 32: ......
Страница 46: ......
Страница 58: ......
Страница 71: ......
Страница 78: ...5 20 Chapter 5 DETAILED DESCRIPTION OF EACH FUNCTION Item Bank Display Contents Initial value User level ...
Страница 84: ......
Страница 95: ......
Страница 172: ......
Страница 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Страница 211: ......
Страница 230: ......
Страница 240: ......
Страница 248: ......
Страница 260: ......
Страница 268: ......
Страница 270: ......
Страница 279: ......