Chapter 4.
WIRING
4 - 1
Wiring
4-1
WARNING
Before wiring, or removing/mounting the SDC35/36, be sure to turn the power
OFF.
Failure to do so might cause electric shock.
Do not touch electrically charged parts such as the power terminals.
Doing so might cause electric shock.
CAUTION
Wire the SDC35/36 properly according to predetermined standards.
Also wire the SDC35/36 using specified power leads according to recognized
installation methods.
Failure to do so might cause electric shock, fire or faulty operation.
Do not allow lead clippings, chips or water to enter the controller case.
Doing so might cause fire or faulty operation.
Firmly tighten the terminal screws with the specified torque as listed in the
specifications.
Insufficient tightening of terminal screws might cause electric shock or fire.
Do not use unused/spare terminals on the SDC35/36 as relay terminals.
Doing so might cause electric shock, fire, or faulty operation.
We recommend attaching the terminal cover (sold separately) after wiring the
SDC35/36.
Failure to do so might cause electric shock, fire, or faulty operation.
Use the relays within the recommended life.
Failure to do so might cause fire or faulty operation.
Use Yamatake Corporation's "SURGENON" if there is the risk of power
surges caused by lightning.
Lightning power surges might cause fire or faulty operation.
Do not make incorrect connections. If the cables are connected incorrectly,
this might cause the unit to malfunction.
The controller requires 6 seconds to stabilize after power ON. Great care
should be taken when the relay output from the controller is used as interlock
signals.
The part between the control output 1 and control output 2 is not isolated.
When necessary, use an appropriate isolator.
Do not connect multiple loader cables to multiple units from one personal
computer. The current coming from other circuits might cause the PV value
indication error to occur.
Do not connect any terminating resistor in the communication path when
performing the RS-485 wiring. Doing so might cause the communication to
fail.
Always mount a switch for shut-down of the main power of this unit in an area
easily accessible to the operator when performing electric wiring of this unit.
Additionally, connect a slow-action type (T) fuse having a rated current of
0.5A and rated voltage of 250V to the wiring for the instrument power supply
of the AC power supply model. (IEC127)
Содержание SDC35
Страница 16: ......
Страница 17: ......
Страница 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Страница 32: ......
Страница 46: ......
Страница 58: ......
Страница 71: ......
Страница 78: ...5 20 Chapter 5 DETAILED DESCRIPTION OF EACH FUNCTION Item Bank Display Contents Initial value User level ...
Страница 84: ......
Страница 95: ......
Страница 172: ......
Страница 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Страница 211: ......
Страница 230: ......
Страница 240: ......
Страница 248: ......
Страница 260: ......
Страница 268: ......
Страница 270: ......
Страница 279: ......