![Yamatake SDC35 Скачать руководство пользователя страница 219](http://html.mh-extra.com/html/yamatake/sdc35/sdc35_user-manual_905228219.webp)
Chapter 8. MODBUS COMMUNICATION FUNCTION
8 - 1 Outline of Communication
8-1
If the optional model is provided with the RS-485 communications function, communication with a PC, PLC or
other host devices are available using a user-configured program.
The communication protocol can be selected from the Controller Peripheral Link (CPL) communication
(Yamatake's host communication protocol) and the MODBUS communication. This chapter describes the
MODBUS communications.
■
Features
The features of the
C35/36
's communication function are as follows:
• Up to 31 units can be connected to a single master station as a host device.
• When the communication specifications of the host device conform to the RS-
232C interface, the communication converter
CMC10L
(sold separately) is
required. The
CMC10L
allows the conversion between RS-232C and RS-485.
• Almost all of the device parameters can be communicated.
For details on communication parameters, refer to;
Chapter 9, LIST OF COMMUNICATION DATA
■
Setup
The following setups are required for performing the MODBUS communication:
• If the optional model number is provided with the RS-485 communications
function, display and setup are available.
• If the communications type is set to MODBUS RTU format, data format (data
length) cannot be displayed nor set up, and the action is fixed to 8-bit data.
Handling Precautions
• Setups can be performed through key operation on the console or the
SLP-C35 Smart Loader Package. However, they cannot be
performed via RS-485 communications.
• If you use the Yamatake CMC10L as an RS-232C/RS-485 converter,
set the response time-out (C70) to 3ms or longer.
Item
Display
Contents
Initial User
(Setting display/bank)
value
level
CPL/MODBUS
0: CPL
0
Basic,
(Setup setting/Setup bank)
1: MODBUS ASCII format
Standard,
2: MODBUS RTU format
High
Station address
0: Does not communicate
0
function
(Same as above)
1 to 127
Transmission speed
0: 4800bps
2
(Same as above)
1: 9600bps
2: 19200bps
3: 38400bps
Data format (Data length)
0: 7 bits
1
(Same as above)
1: 8 bits
Data format (Parity)
0: Even parity
0
(Same as above)
1: Odd parity
2: No parity
Data format (Stop bit)
0: 1 stop bit
0
(Same as above)
1: 2 stop bits
Response time-out
1 to 250ms
3
High
function
Содержание SDC35
Страница 16: ......
Страница 17: ......
Страница 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Страница 32: ......
Страница 46: ......
Страница 58: ......
Страница 71: ......
Страница 78: ...5 20 Chapter 5 DETAILED DESCRIPTION OF EACH FUNCTION Item Bank Display Contents Initial value User level ...
Страница 84: ......
Страница 95: ......
Страница 172: ......
Страница 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Страница 211: ......
Страница 230: ......
Страница 240: ......
Страница 248: ......
Страница 260: ......
Страница 268: ......
Страница 270: ......
Страница 279: ......