MV1/MV2 process
The time proportional cycle and time proportional cycle mode of MV1/MV2 can
be set.
• MV1 is the general term for the ON/OFF control output, time proportional
output, and time proportional output for heat side of the Heat/Cool control.
MV2 is the time proportional output for cool side of the Heat/Cool control.
• When MV1 is connected only to the voltage pulse output in the DO Assignment,
the display and setting of the time proportional unit 1 (CyU) can be performed.
• When MV1 is connected to any of the relay control output, voltage pulse control
output, and event output in the DO Assignment, the display and setting of the
time proportional cycle 1 (Cy) can be made. However, when the time
proportional unit 1 (CyU) is other than “0”, the display and setting of the time
proportional cycle 1 (Cy) cannot be performed.
• When the Heat/Cool control is used and MV2 is connected only to the voltage
pulse output in the DO Assignment, the display and setting of the time
proportional unit 2 (CyU2) can be performed.
• When the Heat/Cool control is used and MV2 is connected to any of the relay
control output, voltage pulse control output, and event output in the DO
Assignment, the display and setting of the time proportional cycle 2 (Cy2) can be
made. However, when the time proportional unit 2 (CyU2) is other than “0”, the
display and setting of the time proportional cycle 2 (Cy2) cannot be performed.
• The initial value of the time proportional cycle 1 (Cy) is “10” when the control
output 1 is the relay output and it is “2” in other cases.
• The initial value of the time proportional cycle 2 (Cy2) is “10” when a model
with one control output point is used and it is “2” when other models are used.
5-70
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Item (Bank)
Display
Contents
Initial value
User level
Time proportional unit 1 (for
MV1)
(Parameter bank)
0: 1s unit
1: Cycle fixed at 0.5s.
2: Cycle fixed at 0.25s.
3: Cycle fixed at 0.1s
If the set value is other than “0”, the time
proportional cycle 1 (Cy) cannot be set.
0
Basic,
Standard,
High function
Time proportional cycle 1
(for MV1)
(Parameter bank)
10 or 2s
Time proportional cycle
mode
(Parameter bank)
0: Controllability aiming type
1: Operation service life aiming type (ON/OFF
operation is performed only once within the
time proportional cycle.
0 or 1
High function
5 to 120s (Output destination of MV1 includes
the relay output.)
1 to 120s (Output destination of MV1 does not
include the relay output.)
If the time proportional unit 1 (CyU)
≠
0, this
setting becomes invalid and the setting
becomes impossible.
Time proportional unit 2 (for
MV2)
(Parameter bank)
0: 1s unit
1: Cycle fixed at 0.5s.
2: Cycle fixed at 0.25s.
3: Cycle fixed at 0.1s
If the set value is other than “0”, the time
proportional cycle 2 (Cy2) cannot be set.
0
Basic,
Standard,
High function
Time proportional cycle 2
(for MV2)
(Parameter bank)
10 or 2s
High function
5 to 120s (Output destination of MV2 includes
the relay output.)
1 to 120s (Output destination of MV2 does not
include the relay output.)
If the time proportional unit 2 (CyU2)
≠
0, this
setting becomes invalid and the setting
becomes impossible.
High function
Содержание SDC35
Страница 16: ......
Страница 17: ......
Страница 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Страница 32: ......
Страница 46: ......
Страница 58: ......
Страница 71: ......
Страница 78: ...5 20 Chapter 5 DETAILED DESCRIPTION OF EACH FUNCTION Item Bank Display Contents Initial value User level ...
Страница 84: ......
Страница 95: ......
Страница 172: ......
Страница 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Страница 211: ......
Страница 230: ......
Страница 240: ......
Страница 248: ......
Страница 260: ......
Страница 268: ......
Страница 270: ......
Страница 279: ......