• When the internal event configuration 1 operation type is set at [0: No event], the
internal event main setting, sub-setting, and hysteresis are not displayed.
• For details about internal event operation with main setting, sub-setting, and
hysteresis, refer to;
List of internal event operations (on pages 5-57 to 5-62)
■
ON delay and OFF delay
ON delay is a function that delays the timing, at which the internal event status is
changed from OFF to ON.
OFF delay is a function that delays the timing, at which the internal event status is
changed from ON to OFF.
However, when the operation type is set at [20: Loop diagnosis 1], [21: Loop
diagnosis 2], [22: Loop diagnosis 3], or [32: Timer], the ON delay and OFF delay
are operated as another function.
For details, refer to;
List of internal event operations (on pages 5-57 to 5-62)
ON delay and OFF delay can be set.
(Continue on next page.)
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Item (Bank)
Display
Contents
Initial value
User level
Internal Event 1 ON delay
(Event bank)
0.0 to 999.9s (Delay time unit is “0.1s”.)
0 to 9999s (Delay time unit is “1s”.)
0 to 9999min (Delay time unit is “1min”.)
0.0s
or 0s
or 0min
High function
Internal Event 1 OFF delay
(Event bank)
Same as internal event 1 ON delay.
0.0s or 0s or 0min
Internal Event 2 ON delay
(Event bank)
Same as internal event 1 ON delay.
0.0s or 0s or 0min
Internal Event 2 OFF delay
(Event bank)
Same as internal event 1 ON delay.
0.0s or 0s or 0min
Internal Event 3 ON delay
(Event bank)
Same as internal event 1 ON delay.
0.0s or 0s or 0min
Internal Event 3 OFF delay
(Event bank)
Same as internal event 1 ON delay.
0.0s or 0s or 0min
Internal Event 4 ON delay
(Event bank)
Same as internal event 1 ON delay.
0.0s or 0s or 0min
Internal Event 4 OFF delay
(Event bank)
Same as internal event 1 ON delay.
0.0s or 0s or 0min
Item (Bank)
Display
Contents
Initial value
User level
Basic,
Standard,
High function
Internal Event 8 Main setting
(Event bank)
Same as Internal Event 1 Main setting.
0
Internal Event 8 Sub-setting
(Event bank)
Same as Internal Event 1 Sub setting.
0
Internal Event 8 Hysteresis
(Event bank)
Same as Internal Event 1 Hysteresis.
5
Содержание SDC35
Страница 16: ......
Страница 17: ......
Страница 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Страница 32: ......
Страница 46: ......
Страница 58: ......
Страница 71: ......
Страница 78: ...5 20 Chapter 5 DETAILED DESCRIPTION OF EACH FUNCTION Item Bank Display Contents Initial value User level ...
Страница 84: ......
Страница 95: ......
Страница 172: ......
Страница 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Страница 211: ......
Страница 230: ......
Страница 240: ......
Страница 248: ......
Страница 260: ......
Страница 268: ......
Страница 270: ......
Страница 279: ......