STEP loop
Whether or not the loop exists at the end of the step operation and the operation
end status can be set.
• When this setting is set at “0”, the operation is stopped (READY mode) if the
operation of the SOAK portion of the final step is completed.
• When this setting is set at “1”, the operation is returned to the RAMP portion of
step 1 if the operation of the SOAK portion of the final step is completed. At this
time, the RAMP operation is performed from SP to SP-1 of the final step
regardless of the setting of [C34: STEP PV start]. Since the number of loop
cycles is not limited, the loop operation is continued until the READY mode is
selected.
• When this setting is set at “2”, the operation is continued with SP of the final step
kept remained until the READY mode is selected if the SOAK portion of the
final step is completed.
Chapter 5. DETAILED DESCRIPTION OF EACH FUNCTION
Item (Bank)
Display
Contents
Initial value
User level
STEP loop
(Setup bank)
0: Stop (No loop)
1: Loop
2: Final step continued. (No loop)
0
High function
Содержание SDC35
Страница 16: ......
Страница 17: ......
Страница 19: ... display key para key or V key key enter key 2 second press hold of para key V ...
Страница 32: ......
Страница 46: ......
Страница 58: ......
Страница 71: ......
Страница 78: ...5 20 Chapter 5 DETAILED DESCRIPTION OF EACH FUNCTION Item Bank Display Contents Initial value User level ...
Страница 84: ......
Страница 95: ......
Страница 172: ......
Страница 174: ...6 2 Chapter 6 LIST OF DISPLAYS AND SETTING DATA ...
Страница 211: ......
Страница 230: ......
Страница 240: ......
Страница 248: ......
Страница 260: ......
Страница 268: ......
Страница 270: ......
Страница 279: ......