4 - 55
Setting the Low Flow Cut
Introduction
When the fluid flow inside the detector is narrow, the fluid is regarded as
stationary and the analog output can be latched to zero. The value at which to
cut the flow in this situation is referred to as the "low flow latch."
Default setting
OFF
Setting range
OFF or ON 0% - ON 10%
Open the low flow cut setup
screen by following the steps to
enter the Engineering Mode.
Touch the key.
By touching the key, the
"OFF" message will change to
"ON". Now you can enter the
low flow cut in a numerical
value.
Touch the key, and the
cursor will moves to the nu-
merical figures.
Use the and keys to select
the desired numbers.
Touch the key to move the
cursor to the "#".
1
Screen
Procedure
Step
2
3
5
6
4
# LOW-FLOW CUT
OFF
# LOW-FLOW CUT
OFF
# LOW-FLOW CUT
ON 0 0 %
# LOW-FLOW CUT
ON 0 0 %
# LOW-FLOW CUT
ON 0 5 %
# LOW-FLOW CUT
ON 0 5 %
Содержание MagneW3000 PLUS
Страница 1: ...CM2 MGG210 2001 MagneW3000 PLUS Smart Electromagnetic Flowmeter Model MGG14C User s Manual ...
Страница 13: ...xi MEMO ...
Страница 25: ...1 12 ...
Страница 41: ...2 16 MEMO ...
Страница 53: ...3 12 MEMO ...
Страница 114: ...4 61 MEMO ...
Страница 129: ...6 1 Parts List Continued MGG10C MGG14C ...