ST3000 Smart Transmitter Series 900 Electronic Differential Pressure/Pressure Transmitter
5-2 : Setting Tag No. and Checking Specifications
5-2-1 :Starting Communications
WARNING
In some cases, communications between the transmitter and the SFC in the automatic
mode cause a sudden change in the output. Although this change is only temporary, it
may result in a hazardous situation. Switch the process control loop to manual before
starting communications between the transmitter and the SFC.
Procedure
This procedure starts communications between this transmitter and the SFC:
Step
Description
SFC screen
1
Place in manual mode, the pro-
cess
No display
2
Refer to Figure 5-1 and connect
the SFC to the transmitter.
3
Turn ON the SFC power switch.
Press the key
4
Press the key
The default tag number is xxxxxxxx
LOOP IN MANUAL?
PRESS ID
DSTJ TAG NO.
LIN DP XXXXXXXX