ST3000 Smart Transmitter Series 900 Electronic Differential Pressure/Pressure Transmitter
Set range calculation Ex. STC Type
Calculate the set range using these procedures:
The following symbols are used to express density and distance.
It is assumed that the density is fixed, during liquid level measurement.
: Specific gravity of liquid in tank
l
: Distance between 100% liquid level and 0% liquid level (measurement range)
h
: Distance between 0% liquid level and high-pressure outlet port
d
: Distance between high-pressure outlet port and transmitter
Figure 5-9 Open Tank
Figure 5-10 Closed Tank
Differential pressure at 0% liquid level (Pressure on high-pressure side - Pressure on
low-pressure side) =
h
= LRV
Differential pressure at 100% liquid level (Pressure on high-pressure side - Pressure
on low-pressure side) =
l + h = (l+h)
= URV
Therefore, set the range as follows:
Low limit (LRV):
h
; High limit (URV): (l+h) r
Example of calculation:
l = 1500 mm, h = 250 mm
= 0.9,
= 1.0
If the above conditions are assumed, the following results are obtained:
Differential pressure at 0% liquid level = (250 x 0.9) = 725 mmH
2
O = 7.110 kPa
Differential pressure at 100% liquid level = {(1500 + 250) x 0.9) = 2075 mmH
2
O =
20.35 kPa
Therefore, set the range as follows:
Low limit (LRV): 7.110 kPa{725 mmH
2
O}, High limit (URV): 20.35 kPa{2075
mmH
2
O}