background image

Содержание ControlByWeb X-16s

Страница 1: ......

Страница 2: ...X 16s Users Manual X 16s User Manual Revisions Revision Description 1 0 Initial release 1 1 Added further information about entering slope and offset settings Page 2 Xytronix Research Design Inc...

Страница 3: ...ng functions similar to that of a Programmable Logic Controller PLC However unlike a PLC the X 600M is designed for web based applications from the ground up No add on software or hardware is required...

Страница 4: ...ngle ended analog signals four differential analog signals or a combination both Reference Output Two 5 0V reference terminals can be used to power resistance sensing sensors such as potentiometers an...

Страница 5: ...enever the module is powered To identify the module during installation the X 600M can send a blink command which will cause the power LED to blink for three seconds 1 3 Part Numbers and Accessories A...

Страница 6: ...r property damage 2 2 Mounting X 16s can be mounted to a standard 35mm by 7 55mm DIN Rail Normally expansion modules are mounted to the left side embossed logo side of the enclosure of the X 600M cont...

Страница 7: ...ly power It is recommended that any load device to be controlled not be connected to the expansion modules until after the X 600M has been configured and tested By doing this wiring and configuration...

Страница 8: ...1 Ain2 Analog Input 2 0 5V or Differential Ain1 Agnd Analog Ground Ain3 Analog Input 3 0 5V or Differential Ain3 Ain4 Analog Input 4 0 5V or Differential Ain3 Agnd Analog Ground Ain5 Analog Input 5 0...

Страница 9: ...down the output The following diagram shows a voltage divider circuit for a 0 10V sensor In the example resister values for R1 and R2 are chosen so that Vout will have a 0 to 5 volt range Generally y...

Страница 10: ...0Vin 5Vout 0Vout 2V V Once the slope is determined calculate the offset using the Y mX b linear equation where b is the offset 0Vout 2V V 0Vin Offset Offset 0V 2V V 0V 0 To configure the X 600 with t...

Страница 11: ...he voltage sense connections made with a 4 wire Kelvin connection This technique uses separate pairs of current carrying and voltage sensing wires to make accurate measurements The goal is to prevent...

Страница 12: ...The outputs are connected to Ain1 and Ain2 The X 16s must be programmed for differential mode on Ain1 The analog measurement will be made by the voltage difference between the two inputs Ain1 Ain2 For...

Страница 13: ...example of using the X 16s with a potentiometer position sensor Potentiometers are in essence a variable resistor with three connections Typically the 5Vref reference from the X 16s is used to apply p...

Страница 14: ...d for the calculations For example if the range of a laser rangefinder is 1Meters to 100Meters the transducer will output 4mA at 1M and 20mA at 100M By default the X 16s makes measurements in units of...

Страница 15: ...sensor that will measure current up to 20 Amps AC The sensor produces a linear 0 5VDC output that it can be connected directly to one input of the X 16s analog module The slope is calculated and enter...

Страница 16: ...a WebRelay module This example is similar to the potentiometer example above except that the X 600M is configured to control a remote device Each analog input can be configured to send messages to a...

Страница 17: ...t is a bare switch with no power source In this example a voltage source for the switch is provided by the 5Vref output A pull down resistor must be provided to drive the input to a known state 0V whe...

Страница 18: ...nd populates it with all of the resources components supported by the Ethernet devices and expansion modules This makes it easy to start experimenting with the web page s user interface and to try out...

Страница 19: ...nts you would like to configure and select the Create Device Widget checkbox This will display the status of the I O on the Dashboard Click Add Checked I O to submit these changes 4 Click Commit Chang...

Страница 20: ...ta for all eight analog inputs should be shown Use this page to test and debug the dashboards panels widgets and components in real time A pull down menu allows access to other dashboards Within minut...

Страница 21: ...urrent 350nA Conversion Rate 7 Hz Reference Output Voltage 5 00V Current 50mA max Accuracy 0 04 Temperature Coefficient 3ppm C Max Connector Type 14 position removable 3 81 mm pitch Connection wire Us...

Страница 22: ...95 non condensing Mechanical Size 1 41 x 3 88 x 3 1 in 35 7 x 98 5 x 78 mm not including connector Weight 4 8 oz 136 g Electromagnetic Compliance IEC CISPR 22 CISPR 24 FCC 47CFR15 Class B EN55024 ITE...

Страница 23: ...ning for any purpose other than the personal use by the purchaser of this product Xytronix Research Design Inc assumes no responsibility for any errors that may appear in this document Whereas reasona...

Страница 24: ...n The foregoing warranty shall not apply to defects or damage resulting from improper use or misuse unauthorized repair tampering modification improper connection or operation outside the electrical e...

Страница 25: ...he instructions may cause interference to radio communications There is no guarantee however that interference will not occur in a particular installation If this equipment does cause harmful interfer...

Страница 26: ...Appendix E Mechanical Dimensions X 16s Users Manual Appendix E Mechanical Dimensions Page 26 Xytronix Research Design Inc...

Отзывы: