Installation
4.1
General precautions
Before starting, make sure that the safety instructions shown in
on
page 5 have been fully read and understood.
WARNING: Risk of explosion
Comply with the local explosion protection regulations.
WARNING: Risk of explosion
The improper installation of the unit in potentially explosive atmospheres can cause explosion.
WARNING:
All the hydraulic and electrical connections must be completed by a technician possessing the
technical-professional requirements outlined in the current regulations.
WARNING:
Always wear personal protective equipment.
WARNING:
Always use suitable working tools.
4.2
Mechanical installation
4.2.1
Precautions
WARNING: Risk of injury due to improper floor installation
Install the unit on a concrete or metal foundation base sufficiently strong to ensure permanent
and rigid support, suitable for the size and weight of the unit and as flat and even as possible.
4.2.2
Installation area
1.
on page 45.
2.
Place the unit in a raised position in relation to the floor.
3.
Check that the air clearance between the wall and the motor fan grid is:
•
≥ 100 mm (4 in), to ensure suitable ventilation
•
≥ 300 mm (12 in), to allow inspection and removal of the motor.
4.
Make sure that any leaks will not cause flooding to the installation area or submerge the
unit.
5.
Make sure that the unit is protected from sudden temperature changes
Permitted positions
WARNING: Risk of explosion
Only install the unit in the horizontal position, to allow self-venting.