Residential Water

CentriPro

HOW CAN THE AQUAVAR SOLO² BE USED TO DEVELOP A WELL SYSTEM?
Set the low pressure cutoff function to off to avoid tripping on low pressure. Use this function for open discharge 
situations or whenever the system pressure will be 20 PSI or more below the system set point pressure. The low 
pressure cutoff function must be returned to the on position after system set up is complete.

CAN THE AQUAVAR SOLO² BE USED FOR SURFACE MOUNT BOOSTER APPLICATIONS? WHAT ARE THE MOTOR 
ELECTRICAL REQUIREMENTS?
Yes, however we do supply the Aquavar ABII or S-Drive for this application. The surface mount motor does not typically 
require the filter that is used with submersible motors. That is why the Aquavar ABII and S Drive are more appropriate 
for surface mount applications than the Aquavar SOLO².

CAN I RUN A 50 HZ MOTOR WITH THE AQUAVAR SOLO² OR USE THE AQUAVAR SOLO² IN A 50 HZ APPLICATION?
The Aquavar SOLO can be used in a 50 Hz application, 50 Hz input in combination with lower input voltage than 230V 
will likely reduce hydraulic performance in order to compensate for higher running current load. This is similar to 
system response in “dirty voltage” conditions.

CAN I USE A 208V INPUT ON THE AQUAVAR SOLO²?
Yes, the input power used must be a grounded power system. The voltage measured from L1 and L2 must be in the 
range of 196VAC to 265VAC. The voltage measured from L1 to GND and L2 to GND must be equal and within a range 
of 120VAC ±10%. Reduced input voltage will reduce system performance.

WHY WOULD I USE DUAL SET POINTS AND HOW DO I SET IT UP?
Dual set points are used in an application where a different set point value is required for a portion of the day such as 
night set back or irrigation system. Please reference IM229 for set up.

HOW DO I PROGRAM OUTPUT RELAYS?
To configure the output relay parameter first press and hold the mode button for 10 seconds, this will allow you to 
scroll through the menu structure. Press the down button 5 times until you reach “rCon”. Press the mode button for 2 
seconds to enter the parameter list. Use the down button to select the parameter, choose from RUN, Fault and Not 
Fault. Once parameter is selected, press MODE button and wait for parameter to blink to confirm it was saved. Please 
reference IM229 for additional set up.

HOW DO I RESET FAULT HISTORY?
To reset the fault history first press and hold the mode button for 10 seconds, this will allow you to scroll through the 
menu structure. Press the down button 3 times until you reach “FrSt” (Fault code history reset). Press and hold the 
mode button for 2 seconds to reset. Display will read done when reset is complete.

CAN THE AQUAVAR SOLO² RUN A CHLORINATOR OR ANOTHER EXTERNAL METERING PUMP?
Yes, however the external pump requires its own power source. The Aquavar SOLO² can provide an output signal to 
control the metering pump. Please reference IM229 for additional set up.