Xylem Bell & Gossett ecocirc XL Скачать руководство пользователя страница 1

    

ecocirc XL

P0002557

rev2     

March 2019

QUICK STARTUP GUIDE 

______________________________________________________________________ 

WARNING

This guide does not replace the instruction and operating manual (IOM) 
Read the manual carefully before installing and using the product. Improper use of the product can cause personal     
injury and damage to property and may void the warranty

.  

______________________________________________________________________ 

Startup checklist 

Operation

Pump Display

  Mount pump in the system according to flow direction indicated on the pump housing and 

with motor housing in one of the allowed orientations shown in figure 1. 

Make sure the pump is properly aligned with the system piping. Do not attempt to spring 
the suction or discharge line in position.

 

On 3-phase pumps, install two (2) Absolute Pressure Sensors provided with the pump. 

Make sure that power supply matches nameplate electrical ratings of the pump. 

Figure 3 shows wiring terminals for single phase and figure 3a shows for 3-phase pumps. 

Please note that 3-phase pumps will rotate only in one direction set at the factory. Wire 
swapping is not an option with these units. 

Connect auxiliary input/output signal wires to the pump as indicated. 

Power and control wiring must be run in separate channels.

 

Fill the system with water.

 

Open all valves in the system to facilitate proper air venting of system piping. 

Power the pump ON and see that all LEDs are lit and successive submenus start rolling. 
(refer to the “Electronic Drive Manual” in case of errors or alarm codes on display)

The display and the LEDs switch-on for 1 second 
and then a sequence of submenus for advanced 
functions begin to appear.

At each power-on, the automatic air venting procedure is executed. 

In case of residual air inside the system creating noise or excessive vibration: 

o

Vent the system again.

o

  Recall the automatic air venting procedure by pressing the up and down arrows

 simultaneously.

o

  If problem is not resolved, refer to instruction manual and/or the electronic drive 

manual. 

The user interface displays “deg” (degassing) 
and a count-down begins until completion of the 
procedure: 
4DEG - 3DEG - 2DEG – 1DEG 

At the end of the air venting procedure, the pump 
starts to run with default settings.

  Set control mode of the pump, by short pressing button 

 (see figure 2 or 2a). 

At the user interface, the chosen mode LED will 
light up. 

Constant pressure mode 

Proportional pressure mode 

Fixed speed mode   

Night mode   

Short press button 

 to display the actual set points (see figure 2 or 2a). 

On display the actual setpoint starts blinking

Change values as desired with arrow buttons 

 (see fig. 2 or 2a)

 

The setpoint stops blinking on display and the 
new parameters will be displayed

10 

To change the displayed  units of measurement, press the button 

 (see fig.2 or 2a)

 

m

3

/h gpm 

  m  ft  

      rpm

11 

To change the unit of measurement of head or flow, press the button 

 for more than

1sec. (see fig. 2)

 

• Flow: m

3

/h 

 gpm (US) 

. Head: 

  m 

 ft

12 

The user interface can be locked/ unlocked by pressing and holding down the two arrow 
setting buttons 

 and the parameter button 

 simultaneously for two seconds

.

The user interface will be automatically locked after ten minutes of pressing the last button.

 

By pressing any button when the user interface 
is locked, the display shows 

Unlocked user interface displays: