Xylem Bell & Gossett B Series Скачать руководство пользователя страница 1

SAFETY

INSTRUCTIONS

This safety alert symbol will be used in this manual to draw attention to
safety related instructions. When used, the safety alert symbol means

ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED!

FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN A

SAFETY HAZARD.

DESCRIPTION

Precharged Expansion Tanks contain either a bladder or a diaphragm
to separate the air charge from the system water. Tanks are designed
to absorb the expansion forces of heating/cooling system water while
maintaining proper system pressurization under varying operating
conditions. 

NOT FOR USE IN DOMESTIC

(POTABLE) WATER SYSTEMS

DANGER:

Series “B”, “D”, & “B-LA” are for use in closed loop 

systems only. Domestic, potable or fresh water can cause serious 
corrosion in a tank. This can result in leakage and a potential 
explosion. Do not use for domestic, potable or fresh water. Failure 
to follow this instruction will result in serious personal injury or 
death and property damage.

OPERATIONAL LIMITS

Maximum Operating Pressure: 125 psi (or as stamped on nameplate)
Maximum Operating Temperature: 240ºF
Minimum Operating Temperature:  35°F (non-glycol application)

18°F (glycol application)

Pressurized Expansion Tanks (ASME)

INSTALLER:

PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

WARNING: Explosion Hazard

Failure to follow instructions in the accompanying product

manual can cause rupture or explosion, possibly causing serious or
fatal injury, leaking or flooding and/or property damage.

WARNING: 

Carefully read the Instruction Manual to avoid 

serious personal injury and property hazards and to ensure

safe use and proper care of this product.

INSTRUCTION MANUAL 

A01500

J