Version 001 (25.8.2020)
Page
1
of
2
D-502-0172
The Quick Manual will guide you through a quick installation of the product, but in no case could it replace the full operating manual. A
complete operating manual is available on our website
www.xvent.cz
or can be downloaded using a QR code.
Xvent s.r.o.
Poděbradská 289
53009 Pardubice-
Trnová
-
The air curtain
is designed for indoor covered and dry areas with an ambient temperature from +5 ° C to +40 ° C
.
-
The air curtain can also be used for environments with higher non-condensing humidity corresponding to the degree of protection IP54
and IP44, according to EN 60529 depending on the type of air curtain. However, a maximum of 80%. The air curtain can also be used in a
corrosive environment C2, according to EN ISO 9223. The air curtain must not be operated in an environment with a risk of explosion and
increased dust.
-
Neither the manufacturer nor the supplier is liable for damage caused by incorrect use of the air curtain. The risk is borne by the user.
-
The air curtain must not be operated during finishing construction activities, especially during activities in which excessive dust is
generated, eg: grinding of concrete, plasterboard, etc ...
Use of the Wind air curtain
Technical parameters
Vertical installation
-
The air curtain must stand on a flat, cohesive and firm surface.
-
The correct height of the air curtain must be at least 100 mm longer than the
height of the opening. If the height of the opening is higher or equal to the air
curtain height, you must attach another air curtain.
-
Use the "WIND-HOLDER" base (accessory) to fasten the air curtain to the floor.
QUICK MANUAL FOR USE AND INSTALLATION
Use a smart device (mobile phone, tablet, etc.) equipped with this technology to read the QR code.
Installation and connection of the air curtain may only be
carried out by a trained person with the appropriate
authorization for the connection of electrical equipment,
who has the appropriate tools at his disposal. During
installation, all instructions and recommendations given in
the Operation and Installation Manual for the WIND must be
observed.
Before starting any installation or maintenance work, it is
necessary to turn off the power and secure the switch
before turning it on again. When handling the air curtain,
take its weight into account and observe safety.
Anchoring the base
(anchors, dowel screws
must be diameter 10
mm. A washer must be
placed under the head
of the anchoring screw,
nuts, for better weight
distribution of the air
curtain. The air curtain
can be rotated ± 20 ° in
the base.
-
The Wind air curtain is designed to separate the indoor and outdoor environment with a
stream of air. This function prevents the escape of indoor air from the indoor environment to
the outdoor environment with open doors, gates, etc.… Another function of t
he air curtain
with closed doors, gates is the possibility to heat the interior by hot air heating. When
purchasing additional accessories - filter, the air curtain is also used to filter the air of the
indoor environment.
-
The air curtain is intended primarily for entrances to industrial halls, warehouses, sports
facilities, workshops, smaller establishments, and also to the entrances of commercial
premises.
Installation
–
general information
The air curtain must be positioned in the way, that the edge of exhaust of air curtain will be in direction
to the wall aligned towards the door frame of the screened opening. The minimum distance between
the side of the air curtain and the wall, the ceiling is 0.1 m and between the fan intake and the wall, the
ceiling is 0.3 m (from flammable substances 0.5 m). The air curtain - the exhaust must always be turned
at lea
st 10 ° outwards from the opening. Otherwise, proper operation
of the air curtain cannot be
guaranteed. Local installation conditions must be taken into account.