Xtreme Power Conversion Corporation
Web/SNMP Cards
Page 24
UPS Management
High-efficiency operation is enabled until the following Stop Time is reached (the Stop Time of the same
day if this is later than the Start Time, the Stop Time of the following day otherwise).
• Stop Time:
The hour of the day before which the high-efficiency operation is enabled.
High-efficiency operation is enabled starting from the preceding Start Time (the Start Time of the same
day if this is earlier than the Stop Time, the Start Time of the previous day otherwise).
Both Start Time and Stop Time are specified in 24-hour format. In order to check the correct operation of the in-
verter feed path on all modules, at least 1 minute of normal operation must be programmed during the week. The
system will reject/disable the configuration if this condition is not satisfied. Please refer to the UPS User Manual
for additional details and examples of configuration.
NOTE:
the configuration of the activation schedule can only be updated when high-efficiency operation is disabled.
Once the configuration has been updated, it can be downloaded to the UPS system. This operation will also en-
able high-efficiency operation. In case of Parallel System, the configuration will be propagated to all modules in
the system.
System Section
Network page
Network configuration of the card – refer to the NETWORK CONFIGURATION chapter within this manual. Note that
the settings on this page will only take effect after a reboot of the card.
Date & Time page
Through this page it is possible to configure the adapter date and time settings. The SNMP/Web adapter features
an internal real-time-clock, and provides different ways to synchronize its clock with the actual time:
• NTP server: the card will periodically re-synch its internal date and time with the NTP server
• Manual: the card date and time are set by the user
• Browser: the card date and time will synch with the browser time
Regardless of the chosen configuration, make sure the correct timezone is selected. The timezone setting also af-
fects auto correction for the daylight saving time.
RCCMD page
This page shows the current configuration for the Network Shutdown (RCCMD) functionality. The various RCCMD
clients are listed, with three action buttons:
• Edit: edit the RCCMD Client configuration
• Test: send an RCCMD Test Message to the Client
• Del: delete the RCCMD Client
New RCCMD Clients can be added with the Add button.
The page to Add/Edit RCCMD clients requires to specify the following information:
• Client: RCCMD Client IP Address or hostname
• Port: RCCMD Port on the Client, default is 6003
• Condition: three different shutdown conditions can be chosen:
o
After X minutes on battery
o
At X minutes remaining of battery autonomy
o
When the UPS signals a Low Battery condition
NOTE
: Although the web interface accepts hostnames to identify RCCMD Clients, it is strongly recommended to
identify the clients with their IP address. Using symbolic hostnames may cause the network shutdown to fail in
case the DNS server is not available, unreachable or mis-configured.