![Xtreme X90-5S Скачать руководство пользователя страница 81](http://html1.mh-extra.com/html/xtreme/x90-5s/x90-5s_user-and-installation-manual_3879512081.webp)
79
8. Specifications
The chapter states the specifications of UPS.
8.1
Conformity And Standards
The UPS has been designed to conform to the United State and international standards listed in
Table 8-1
.
Table 8-1
: international standards
Item
Normative reference
Uninterruptible power systems (UPS)
–
Part 1:
General and safety requirements for UPS
UL 1778: 2014 R8.15
CSA C22.2 No. 107.3-14
Electromagnetic compatibility (EMC) requirements
for UPS
47 CFR FCC Rules and Regulations Part
15 Subpart B,Class A digital Device
Notes:
8.2 Environmental Characteristics
Table 8-2:
Environmental characteristics
Item
Unit
Specifications
Noise within 1 m
dB
Max. 75
Altitude
m
≤1000, derate power by 1% per 100m
Relative humidity
% RH
0 ~ 95, non-condensing
Operating temperature
°C
0 ~ 40°C
Storage and transport
temperature for UPS
°C
-15 ~ 60
8.3 Mechanical Characteristics
Table 8-3
: Mechanical characteristics
42U
Model
Unit
X90-SMB350 / X90-ENC5S
Rated power
kVA/kW
70
140
210
280
350
Dimensions, W x D x H
mm
300/800
x
1065
x
2000
Weight
kg
580
624
668
712
756
Color
N/A
Black
Protection degree, IEC (60529)
N/A
IP20 (front door and back door is open or closed)
Model
Unit
X90-SMB700 / X90-ENC10S
Rated power
kVA/kW
420
490
560
630
700
Dimensions, W x D x H
mm
450/900
x
1065
x
2000
Weight
kg
769
813
857
901
945
Color
N/A
Black
Protection degree, IEC (60529)
N/A
IP20 (front door and back door is open or closed)