P91/P91g Li UPS
1.5K/2K/3K
Uninterruptible Power Supply System
Version: 1.0
Страница 1: ...P91 P91g Li UPS 1 5K 2K 3K Uninterruptible Power Supply System Version 1 0 ...
Страница 2: ...w 4 2 2 Operating principle 6 2 3 Install the UPS Only for RT Models 6 2 4 Setup the UPS 7 2 5 Battery Replacement 9 3 Operations 11 3 1 Button operation 11 3 2 LCD Panel 11 3 3 Audible Alarm 13 3 4 LCD display wordings index 13 3 5 UPS Setting 14 3 6 Operating Mode Description 17 3 7 Faults Reference Code 18 3 8 Warning indicator 18 4 Troubleshooting 20 5 Storage and Maintenance 21 6 Specificatio...
Страница 3: ...ct domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system Please use only VDE tested CE marked or UL marked for 100 110 115 120 125 VAC models mains cable e g the mains cable of your computer to connect...
Страница 4: ...rrent is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS capacitors To avoid electrical shock turn off the unit and unplug it form the AC power source before servicing the battery Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must ...
Страница 5: ...ent has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructi...
Страница 6: ...e original package in a safe place for future use 2 1 Rear panel view IEC Type 1 5K 2K 3K NEMA Type 1 5K 2K 3K 1 Programmable outlets connect to non critical loads 2 Output receptacles connect to mission critical loads 3 AC input 4 Network Fax Modem surge protection 5 USB communication port 6 RS 232 communication port 7 SNMP intelligent slot ...
Страница 7: ...5 8 Emergency power off function connector EPO 9 External battery connection ...
Страница 8: ...utput Dynamic Bypass 2 3 Install the UPS For safety consideration the UPS is shipped out from factory without connecting battery wires Before install the UPS please follow below steps to re connect battery wires first Step 1 Step 2 Step 3 Remove front panel Connect the AC input and re connect battery wires Put the front panel back to the unit This UPS can be either displayed on the desk or mounted...
Страница 9: ... the UPS for heat dissipation and easy maintenance Step 1 UPS input connection Plug the UPS into a two pole three wire grounded receptacle only Avoid using extension cords For 200 208 220 230 240VAC models The power cord is supplied in the UPS package For 100 110 115 120 125 127VAC models The power cord is attached to the UPS The input plug is a NEMA 5 15P for 1 5K models NEMA 5 20P for 2K model a...
Страница 10: ...d When installing either SNMP or AS400 card in the UPS it will provide advanced communication and monitoring options Step 4 Network connection Network Fax Phone surge port Connect a single modem phone fax line into surge protected IN outlet on the back panel of the UPS unit Connect from OUT outlet to the equipment with another modem fax phone line cable Step 5 Disable and enable EPO function This ...
Страница 11: ...con located in the system tray near the clock 2 5 Battery Replacement When the icons of and are flashing in LCD display and alarm is sounding every 2 seconds it s time to replace batteries Contact your service representative to replace batteries Batteries can be replaced easily without turning the UPS off or disconnecting the load If you prefer to remove input power to change the batteries press t...
Страница 12: ...10 front panel Step 4 Step 5 Step 6 After replacing the batteries put the battery box back to original location and screw it tightly Re connect the battery wires Put the front panel back to the unit ...
Страница 13: ...key Press this button to confirm selection in UPS setting mode Select Button Switch LCD message Press this button to change the LCD message for input voltage input frequency input current battery voltage battery current battery capacity ambient temperature output voltage output frequency load current and load percent Setting mode Press and hold this button for 3 seconds to enter UPS setting mode w...
Страница 14: ...requency load current and load percent k kilo W watt V voltage A ampere percent centigrade degree Hz frequency Load information Indicates the load level by 0 24 25 49 50 74 and 75 100 Indicates overload Programmable outlets information Indicates that programmable management outlets are working Mode operation information Indicates the UPS connects to the mains Indicates the battery is working Indic...
Страница 15: ...n Display content Meaning ENA Enable DIS Disable ESC Escape HLS High loss LLS Low loss AO Active open AC Active close EAT Estimated autonomy time RAT Running autonomy time SD Shutdown OK OK ON ON BL Battery Low OL Over Load OI Over input current NC Battery No Connect OC Over Charge SF Site wiring fault EP EPO TP Temperature CH Charger BF Battery Fault BV Bypass Out Range FU Bypass frequency unstab...
Страница 16: ...tput voltage 100 presents output voltage is 100Vac 110 presents output voltage is 110Vac 115 presents output voltage is 115Vac 120 presents output voltage is 120Vac Default 125 presents output voltage is 125Vac 02 Frequency Converter enable disable Interface Setting Parameter 2 Enable or disable converter mode You may choose the following two options CF ENA converter mode enable CF DIS converter m...
Страница 17: ...V to 24V of the nominal voltage Default 12V For 120 Models the setting voltage in parameter 3 is from 3V to 12V of the nominal voltage Default 6V 06 Bypass enable disable when UPS is off Interface Setting Parameter 2 Enable or disable Bypass function You may choose the following two options ENA Bypass enable DIS Bypass disable Default 07 Bypass voltage range setting Interface Setting Parameter 2 S...
Страница 18: ...els 55 59Hz setting the frequency low loss point from 55Hz to 59Hz Default 57 0Hz 09 Programmable outlets enable disable Interface Setting Parameter 2 Enable or disable programmable outlets ENA Programmable outlets enable DIS Programmable outlets disable Default 10 Programmable outlets setting Interface Setting Parameter 2 Set up backup time limits for programmable outlets 0 999 setting the backup...
Страница 19: ... AC is selected as EPO logic it will activate EPO function with Pin 1 and Pin 2 in close status 17 Site fault detection enable disable Interface Setting Parameter 2 Enable or disable site fault detection You may choose the following two options ENA Site fault detection enable Default for 120 models DIS Site fault detection disable Default for 230 models 18 Display setting for autonomy time Interfa...
Страница 20: ...cceptable range but UPS is overload UPS will enter bypass mode or bypass mode can be set by front panel Alarm is sounding every 10 seconds Standby mode UPS is powered off and no output supply power but still can charge batteries Fault mode When a fault has occurred the ERROR icon and the fault code will be displayed 3 7 Faults Reference Code Fault event Fault code Icon Fault event Fault code Icon ...
Страница 21: ...ttery fault Sounding every 2 seconds At this time UPS is off to remind users something wrong with battery Out of bypass voltage range Sounding every 2 seconds Bypass frequency unstable Sounding every 2 seconds Battery replacement Sounding every 2 seconds EEPROM error Sounding every 2 seconds NOTE Site Wiring Fault function can be enabled disabled via software Please check software manual for the d...
Страница 22: ...ries are connected well Fault code is shown as 27 on LCD display and alarm is continuously sounding Battery voltage is too high or the charger is fault Contact your dealer Fault code is shown as 28 on LCD display and alarm is continuously sounding Battery voltage is too low or the charger is fault Contact your dealer The icons and and the warning code flash on LCD display Alarm is sounding every s...
Страница 23: ...eplace the battery Fault code is shown as 2A on LCD display and alarm is continuously sounding The short circuit occurs on the charger output Check if battery wiring of connected external pack is in short circuit status Fault code is shown as 45 on LCD display At the same time alarm is continuously sounding The charger does not have output and battery voltage is less than 10V PC Contact your deale...
Страница 24: ...near load 55 150VAC 50 60Hz auto sensing Up to 98 110 130 for 5 min 130 140 for 30 sec 140 for 1 5 sec 32 104 F 0 40 C 11 500 ft above sea level 5 years electronics 5 years battery warranty USA and Canada RS 232 USB EPO intelligent slot for optional cards Web SNMP Relay dry contact Modbus ViewPower software horizontal brackets tower pedestals user manual COMMUNICATION INTERFACE INCLUDED IN BOX AVA...
Страница 25: ...e is adjusted to 200VAC 208VAC Rack depth is front bracket to unit panel Add 1 for depth including front bezel 110 300 VAC 50 60Hz auto sensing 2 THD linear load 4 THD non linear load 110 130 for 5 min 130 140 for 30 sec 140 for 1 5 sec Up to 98 32 104 F 0 40 C 11 500 ft above sea level CE RoHS battery packs comply to UL1973 WARRANTY COMMUNICATION INTERFACE INCLUDED IN BOX ENVIRONMENT Temperature ...
Страница 26: ...10Vac input 1350VA 1040W 13 5A 100Vac input P91 2kLi 100 125Vac 50 60Hz 16A 1Ø 100 110 115 120 125Vac 50 60Hz 1Ø 2000VA 1800W 16A 125Vac input 2000VA 1800W 16 7A 120Vac input 2000VA 1740W 17 4A 115Vac input 2000VA 1640W 18 2A 110Vac input 1800VA 1500W 18A 100Vac input P91 3kLi 100 125Vac 50 60Hz 24A 1Ø 100 110 115 120 125Vac 50 60Hz 1Ø 3000VA 2700W 24A 125Vac input 3000VA 2700W 25A 120Vac input 30...