background image

Xtreme Power Conversion Corporation

M90 User’s Manual

Page 65

Uninterruptible Power Supply

Table 4-15: 

Control execution

Item No. Description

Item No.

Description

1

Control! System Turn On

2

Control! System Turn Off

3

Control! Manual Battery Test

4

Control! Cancel Battery Test

5

Control! Turn To Bypass

6

Control! Shutdown Restore

7

Control! Cancel Shutdown

8

Control! Charger Turn On

9

Control! Charger Turn Off

10

5. Interface and Communication

As shown in figure 5-1, the Static Transfer Switch (STS) Module includes dry contact Ports (X1~X8), Extra Comm. 

Slot, SNMP Slot and communication port (RS232 Port, USB port) on the front panel.

Figure 5-1 Dry contact ports and communication ports

Dry Contact No.

Dry Contact No.

Function

X1

Remote EPO input port

X2

No use

X3

No use

X4

Maintenance Bypass Switch State Port 

X5

No use

X6

Battery Cabinet Temperature Detection Port

X7

No use

X8

No use

5.1 Dry Contact Port

5.1.1 X1-Remote EPO Input Port

The Emergency Power off (EPO) Function in UPS can be operated by an assigned remote contact. Users can set 

the logic (N.C or N.O) of this EPO Function through LCD panel.
X1 is the remote EPO input port. The port is shown in Figure 5-2 and described in Table 5-1.

Содержание M90-100k140

Страница 1: ...M90 80 140 Modular Online Three Phase UPS 15 140kVA Models User Installation Manual www xpcc com 2019 Xtreme Power Conversion Corporation All rights reserved Rev 9 23 19 ...

Страница 2: ...stallationEnvironment 5 2 3Unpacking 6 2 4MovingtheCabinet 8 2 5 Types of UPS Cabinet 9 2 6 Exterior 9 2 7 Internal Mechanisms 12 2 8 Control Panel 15 2 9IntroductionofModules 16 2 10 Power Cable 20 2 11 Wiring 22 2 12 Power Module Installation 23 2 12BatteryModuleInstallation 23 3 Operation Mode and UPS Operation 26 3 1 Block Diagram of UPS 26 3 2 Operation Mode 27 3 3UPSOperation 30 4 Control Pa...

Страница 3: ...tra Comm Slot 67 5 3 Local Communication Ports RS232 USB 67 5 4 SNMP Slot 67 6 Troubleshooting 68 7 Service 70 7 1ReplacementProceduresOfPowerModule 71 7 2 Replacement Procedures Of STS Module 71 7 3 Replacement Procedures Of Battery Module 71 7 4 Replacement Procedures Of Air Filter 71 8 Specifications 72 9 ObtainingService 74 10 Xtreme Power Conversion Limited Warranty 75 ...

Страница 4: ...s Voltage between all terminals including the protective earth Risk of Voltage Backfeed The isolation device must be able to carry the UPS input current 1 2 EMC WARNING This is a product for commercial and industrial application in the second environment installation restrictions or additional measures may be needed to prevent disturbances 1 3 Installation Information WARNING Installation must be ...

Страница 5: ...nd must be disposed properly For more information contact your local recycling reuse or hazardous waste center Do not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center 2 Installation 2 1 Initial Inspection 1 Visually examine if there is any damage inside and outside of packages in the process of the t...

Страница 6: ...of the UPS and the external battery cabinets for maintenance and ventilation 8 For safety concerns we suggest that you shall Equip with CO2 or dry powder fire extinguishers near the installation area Install the UPS in an area where the walls floors and ceilings were constructed by fireproof materials 9 Do not allow unauthorized personnel to enter the installation area Assign specific personnel to...

Страница 7: ...small wood into groove Then remove two side panels Refer to Figure 2 3 Figure 2 3 4 Remove 4 fixing cabinet plates and loosen leveling feet by rotating them counterclockwise Then move the cabinet from the pallet Refer to Figure 2 4 5 To fix the cabinet in position simply rotate leveling feet clockwise Refer to Figure 2 5 Figure 2 4 Figure 2 5 ...

Страница 8: ...st three people move the UPS to the installation area One person holds a lateral side of the UPS with hands another holds the other lateral side of the UPS with hands and the other person pushes the UPS either from the front side or from the back side to the installation area and avoid tipping the UPS 3 The casters are designed to move on level ground Do not move the UPS on an uneven surface This ...

Страница 9: ... N A 2 6 Exterior In the front of the UPS there are control interface LCD Panel and door lock The side panels are lockable The casters at the bottom of the UPS cabinet can be used to move over short dis tances There are four leveling feet to fix and stabilize the UPS cabinet on the ground Refer to Figure 2 7 Inside the cabinet there are Breakers STS Module Power Module slots and Battery module slo...

Страница 10: ...me Power Conversion Corporation M90 User s Manual Page 10 Uninterruptible Power Supply Figure 2 7 Exterior Mechanical Data Dimensions UPS cabinet Width Depth Height 42U 23 6 43 3 79 1 Figure 2 8 Dimensions ...

Страница 11: ...ew Unlock and open the front door and you will see the Main Breaker Q1 Maintenance Breaker Q2 Output Break er Q3 STS Module Power Module slots and Battery Module slots Battery Module Slots is only for M90 80 M90 80 M90 140 1 Battery Breaker 2 STS Module 3 Power Module 4 Battery Module Figure 2 9 Front View ...

Страница 12: ...r for internal bat tery modules in the M90 80 but there aren t any in the M90 140 M90 80 M90 140 Figure 2 10 Rear View 2 7 Internal Mechanisms 2 7 1 Breakers After opening the front door there are three breakers Main Breaker Q1 Maintenance Breaker Q2 and Output Breaker Q3 For the M90 80 there is a battery breaker for internal battery modules You can see it when you open the rear door Battery Break...

Страница 13: ...Xtreme Power Conversion Corporation M90 User s Manual Page 13 Uninterruptible Power Supply M90 80 M90 140 Figure 2 11 Front Breakers M90 80 Figure 2 12 Rear Breaker Battery Breaker ...

Страница 14: ...ption 1 Output Block Connects the critical loads Includes R S T and Neutral terminals 2 Bypass Input Block Connects bypass AC source Includes R S T and Neutral terminals 3 Main Input Block Connects main AC source Includes R S T and Neutral terminals 4 For UPS Grounding For UPS grounding Includes one grounding terminal 5 Battery Input Block Connects an external battery cabinet Includes Positive Neg...

Страница 15: ...locks 2 8 Control Panel 2 8 1 LCD Display Through the graphic LCD display the user can easily understand the operation mode of UPS In addition the mea surement parameters versions of firmware and warnings can be browsed in the friendly interface For detailed information please refer to Charter 4 Figure 2 16 Control Panel ...

Страница 16: ... Load on Battery FAULT ALARM Red Flashing Low battery Off Battery converter is normal and battery is charging On UPS fault 2 8 3 Control Key Turn on or turn off the UPS 2 9 Introduction of Modules The design of STS Module Power Module and Battery Module make maintenance and replacement quick and easy The modular and hot swappable design of Power Module makes it a highly cost effective solution to ...

Страница 17: ...Item Description 1 Extra Comm Slot This slot can insert an optional card Extra Comm card which can enhance the communication capability of UPS system It can provide another SNMP slot and some dry contact ports 2 LCD Port This port connects to Control Panel with a factory installed cable 3 RS232 port Local communication interface 4 USB port Local communication interface 5 SNMP Slot This slot can wo...

Страница 18: ...when the Power Module is well installed Then the Power Module can start to work 3 DIP Switches There are three DIP switches for Power Module address setting In the same cabi net each Power Module ID MUST be exclusive 4 Battery Start Button When AC input is not existing use this button to start battery power for UPS 5 FAULT LED ON The Power Module is in fault condition or the Ready Switch is unlock...

Страница 19: ... located at the back of UPS cabinet Refer to Figure 2 20 Figure 2 20 Parallel Board The SW1 and SW2 position have been well installed before leaving factory It s not necessary to change it for single UPS system application Module ID Assignment SW1 SW2 Module Address Module ID SW1 SW2 Module Address Module ID SW1 SW2 0 0 SW1 SW2 0 9 1 1 1 10 2 2 2 11 3 3 3 12 4 4 4 13 5 5 5 14 6 6 6 15 7 7 7 16 SW1...

Страница 20: ...cs of 12V 580W batteries Figure 2 21 M90 80 Battery Module Figure 2 22 M90 80 Battery Module 2 10 Power Cable Please follow the local wiring regulations Follow environmental conditions and refer to IEC60950 1 2 10 1 AC input and output maximum current and power cable configuration For M90 80 models Model 15KVA 20KVA 30KVA 40KVA 45KVA 60KVA 75KVA 80KVA Current A 45 60 1 90 120 2 135 180 3 225 240 4...

Страница 21: ...50 150 240 240 Fixation torque force lb in 100 100 100 100 100 100 100 100 Warning 1 When Load is less than 20KVA at least one layers of battery modules 4 modules have to be installed 2 When Load is between 20KVA and 40KVA at least two layers of battery modules 8 modules have to be in stalled 3 When Load is between 40KVA and 60KVA at least three four of battery modules 12 modules have to be instal...

Страница 22: ...d Power Cables BAT N To External BATTERY Power Cables Figure 2 23 UPS Cabinet Wiring 2 11 2 AC source connection For Single input application connect Input1 to the AC power source and use 3 short wires to connect Input1 and Input2 For Dual input application connect input1 to the Main AC power source and connect input2 to the Bypass power source The sequence of three phase R S and T must be connect...

Страница 23: ...tery setting is different from actual installation the UPS will keep warning Please refer to section 4 2 6 3 and Table 4 9 for the details 2 12 Power Module Installation The weight of Power Module is over 30 kg so at least two persons are required for handling 2 12 1 Insert the Power Module 1 Adjust the DIP switch positions to set the different Module Address Refer to Table 2 1 2 Place the ready s...

Страница 24: ...Corporation M90 User s Manual Page 24 Uninterruptible Power Supply 4 Secure the Power Module to the cabinet by fixing the screws at the front panel of the Power Module 5 Move the ready switch to the position i e in ready state ...

Страница 25: ...and disconnected from UPS system 3 Use a screwdriver to remove the four screws from fixing holes 4 Two people pull out together and remove the Power Module from its slot 2 13 Battery Module Installation The weight of Battery Module is heavy so at least two persons are required for handling Before performing the Battery Module installation replacement make sure the Battery Breaker is in the OFF pos...

Страница 26: ...rding the maximum load of power modules please refer to section 2 10 2 to install the required Battery Modules 4 Secure the Battery Module to the cabinet by fixing the screws of the Battery Module 3 Operation Mode and UPS Operation 3 1 Block Diagram of UPS Figure 3 1 Wiring diagram for dual inputs ...

Страница 27: ...nsfer UPS that permits operation in the following modes Standby Mode Line Mode Battery Mode Bypass Mode ECO Mode Shutdown Mode Maintenance Bypass Mode manual bypass Standby Mode Upon connecting to utility input power the UPS is in Standby mode before UPS is turned on if BYPASS enable set ting is Disabled and charger function will be active when the battery is present The load is not powered under ...

Страница 28: ...ier derives power from the battery and supplies DC power to the inverter The inverter filters the DC power and converts it into pure and stable AC power to the load Figure 3 5 Battery Mode Diagram 3 2 4 Bypass Mode Upon connecting to utility input power the UPS is in Bypass mode before UPS is turned on if BYPASS enable set ting is Enabled and charger function will be active when battery is present...

Страница 29: ...sfer the power source of load from bypass to inverter In order to shorten the transfer time the rectifier and inverter are working when the UPS is in ECO mode Figure 3 7 ECO Mode Diagram 3 2 6 Shutdown Mode When the UPS is in the off state and the utility power source is absent the UPS will enter into shutdown mode Or when the UPS has discharged the battery to the cut off level the UPS will enter ...

Страница 30: ...e bypass power source is normal Figure 3 9 Maintenance Bypass Mode Diagram 3 3 UPS Operation Do not start the UPS until the installation is completed Make sure the wiring is correct and the power cables are properly connected Make sure the Power Modules addresses have been configured Refer to the Power Module ID Assistance section Make sure the ready switch on the Power Module has been moved to th...

Страница 31: ...les and the bat tery required for the UPS system Step 2 Switch ON the battery breaker Step 3 Switch ON the external power switch in distribution panel to power the UPS The STS module starts running and the LCD panel is displayed Step 4 Switch ON the input breaker Q1 The UPS will enter into Standby Mode if the setting of Bypass mode is disabled Or the UPS will enter into Bypass Mode if the setting ...

Страница 32: ...no warning or fault event happening If there is please refer to Chapter 6 Troubleshoot ing to solve it Step 6 Press Power ON OFF button for two seconds to enter into Line Mode as shown below After turned on UPS will do self test and start Inveter up UPS will be transferred to Line mode when all power modules are ready ...

Страница 33: ... complete 3 3 2 Cold Start Startup Step 1 Switch ON the battery Breaker Step 2 Press the Battery Start button on any one of Power Modules to start up the control power of all Power modules and STS as shown below Battery Start Button Step 3 After pressing the Battery Start button UPS will enter into Standby mode Refer to the diagram below for LCD display ...

Страница 34: ...hen UPS will enter Battery Mode as shown in the diagram below Step 6 Switch ON the output breaker Q3 Cold start startup procedure is complete 3 3 3 Maintenance Bypass Operation Follow the instruction to transfer to Maintenance Bypass and UPS protection as below 3 3 3 1 Transfer to maintenance bypass Step 1 Remove the mechanical lock plate of Maintenance Bypass Breaker Step 2 Make sure the UPS oper...

Страница 35: ...odule Power Module and Battery Module 3 3 3 2 Transfer to UPS Protection Step 1 Make sure the maintenance is complete The Power Modules and STS module have been installed well Step 2 Switch ON the Main Breaker Q1 as shown below Step 3 Please enter LCD SETUP MENU and choose SYSTEM to ensure that the Bypass mode is enabled If the Bypass mode is disabled you have to set it enabled Then exit the SETUP...

Страница 36: ...tenance Bypass Breaker as shown below Step 5 Lock back the mechanical lock plate as shown below 3 3 4 Turn off Operation 3 3 4 1 Bypass Mode Standby Mode Turn Off Operation When the UPS neither is turned on nor turned off the UPS operates in the Standby Mode or Bypass Mode It de pends on the Bypass Mode Setting ...

Страница 37: ...agrams are shown below Bypass Mode Setting is Disabled Bypass Mode Setting is Enabled Step 1 Switch OFF the Main Breaker The LCD diagrams are shown below Bypass Mode Setting is Disabled UPS enters Shutdown Mode It is normal the Un Connection is shown when Power Modules have shut off their control power ...

Страница 38: ...rnal power switch to disconnect the AC power to the UPS Wait until the LCD is OFF Step 3 Switch OFF the battery breaker if the UPS will disconnect the AC power for a long time 3 3 4 2 Line Mode Turn Off Operation The LCD diagrams are shown below when the UPS operates in the Line Mode Press Power On Off button for 2 seconds to turn off the UPS Or use the Menu Control System Turn Off to turn off the...

Страница 39: ...he Bypass Mode Standby Mode Turn Off Operation procedure 3 3 4 3 Battery Mode Turn Off Operation The LCD diagram is shown below when the UPS operates in the Battery Mode Press Power On Off button for 2 seconds to turn off the UPS Or use the Menu Control System Turn Off to turn off the UPS After turning off the UPS will tranfer to Standby Mode Next follow the Bypass Mode Standby Mode Turn Off Opera...

Страница 40: ... functional areas 1 LCD display 2 LED indications 3 Control key 4 Audio Alarm as shown in Figure 4 1 Figure 4 1 Control Panel 1 LCD display Graphic display and all measured parameters 2 LED indications Refer to Table 4 1 3 Control key Refer to Table 4 2 4 Audible Alarm Refer to table 4 3 Table 4 1 LED indications LED Color Status Definition INPUT Green On Input source is normal Flashing Input sour...

Страница 41: ... Buzzer sounds two seconds Battery mode Buzzer sounds every 2 seconds Low battery Buzzer sounds every half seconds UPS alarm Buzzer sounds every 1 second UPS fault Buzzer continuously sounds 4 2 Screen Description 4 2 1 Start Screen Upon starting the UPS executes self test The initial screen displays and remains still in approximately 5 seconds as shown in Figure 4 2 Figure 4 2 Initial screen 4 2 ...

Страница 42: ...rement screen The meanings of each icon are listed as below Module icon Explanation STS icon with ID no Power module icon with ID no No power module Power module output on Power module output off Power module charger on Power module charger off Power module fault Power module is operated normally 3 Main Menu Touch icon to enter sub screen 4 UPS Flow Chart Current flow chart and measurement data 5 ...

Страница 43: ...sion Corporation M90 User s Manual Page 43 Uninterruptible Power Supply 4 2 3 Control Screen Touch icon to enter into the sub menu as shown in Figure 4 5 and 4 6 Figure 4 5 Control menu tree Figure 4 6 Control screen page ...

Страница 44: ...gure 4 7 4 2 5 Measurement Screen Touch icon to enter into the sub menu There are two sub menus system measurement and module measure ment Touch icon to monitor system measurement value or icon to monitor module measurement value You may choose Input Output Bypass Load or Battery to monitor detailed status under System or Module direc tory Please refer all screens in Figure 4 8 and 4 9 All detaile...

Страница 45: ...Xtreme Power Conversion Corporation M90 User s Manual Page 45 Uninterruptible Power Supply Figure 4 9 System Measurement Screens Touch icon to monitor module measurement value ...

Страница 46: ... Voltage V Bypass phase voltage L1 L2 L3 Units 0 1V Frequency Hz Bypass Frequency L1 L2 L3 Units 0 1Hz Power Factor Bypass Power Factor L1 L2 L3 Load Sout KVA Apparent power Units 0 1KVA Pout KW Active power Units 0 1KW Load Level The percentage of the UPS rating load Units 1 Battery Positive Voltage V Battery Positive Voltage Units 0 1V Negative Voltage V Battery Negative Voltage Units 0 1V Posit...

Страница 47: ...r password and maintainer password The default password for user is 0000 It could be change by user The manitainer password is owned by service personnel Entering different level of password can access to differnet settings The setting can be changed in different opera tion mode The Table 4 5 lists the relevant information Table 4 5 All setting items in Setup Menu Setting item Standby Mode Bypass ...

Страница 48: ...Low Shutdown Setting Y Y Y Y Y Y Y Periodic Battery Test Y Y Y Y Y Y Y Y Y Battery Test Interval Y Y Y Y Y Y Y Y Y Stop by Time Y Y Y Y Y Y Y Y Stop by Battery Voltage Y Y Y Y Y Y Y Y Stop by Battery Capacity Y Y Y Y Y Y Y Y Battery Age Alert Y Y Y Y Y Y Y Y Y Temperature Compensation Y Y Y Y Y Y Y Y Y Pre Alarm Y Y Y Y Y Y Y Y Y Y means that this setting item can be set in this operation mode Set...

Страница 49: ...ese Simplified Chinese TIME Adjust Time Set current date and time yyyy mm dd hour min sec MUST be set after UPS installation System Installed Date Set system installed date yyyy mm dd 2015 1 1 Default MUST be set after UPS installation System Last Maintain Date Set system latest maintenance date yyyy mm dd MUST be set after UPS installation Battery Installed Date Set battery installed date yyyy mm...

Страница 50: ... Table 4 7 EEPROM Reset Category list Setting Item Factory Reset EEPROM Reset General Model Name Language Y Y Adjust Time System Installed Date Y System Last Maintain Date Y Battery Installed Date Y Battery Last Maintain Date Y Change Password Y Baud Rate Y Audible Alarm Y Y Factory Reset EEPROM Reset EPO Function Y Save Setting System Output Voltage Y Bypass Voltage Range Y Y Bypass Frequency Ran...

Страница 51: ...Y Stop by Battery Voltage Y Y Stop by Battery Capacity Y Y Battery Age Alert Y Y Temperature Compensation Y Y Pre Alarm Y 4 2 6 2 Setup System Screen The Setup System screen and setting list as shown in Figure 4 15 and table 4 7 System setting can be set only when UPS is operated in certain mode Please check setting item availability table 4 5 for the details If it s not set up under specific mode...

Страница 52: ...ult 127Vac MUST be reviewed after UPS installation BYPASS SETTING Bypass Set bypass voltage range Upper limit 10 15 Default 20 Lower limit 10 20 Default 30 Voltage Set bypass Frequency range Upper Lower limit 1Hz 2Hz 4Hz Default Converter Mode Set converter mode Disable Default Enable ECO Mode Set ECO mode Disable Default Enable Bypass Mode Set bypass mode Disable Default Enable MUST be reviewed a...

Страница 53: ...certain seconds System Shutdown Time Set system shutdown time 0 2 99min 0 2 min Default This delay time will start counting when the CONTROL Shutdown Restore command is executed System Restore Time Set system restore time 0 9999min 1 min Default This delay time will start counting after shutdown time is elapsed when the CONTROL Shutdown Restore command is executed Redundancy Set total power and re...

Страница 54: ... Default MUST be set after UPS installation Battery Capacity in Ah Set battery capacity 0 999 9Ah Default MUST be set after UPS installation or Battery capacity is changed Maximum Charging Current Set battery maximum charging current 1 128A 2A Default MUST be set after UPS installation or Battery capacity is changed Battery Low Shutdown SETTING Battery Low Voltage Set battery low voltage 10 5 11 5...

Страница 55: ...et battery capacity to stop battery testing 20 50 20 Default Battery Age Alert Battery Age Alert Months Set battery age for replacement Disable 12 60Months Disable Default If this feature is enabled and the battery has been installed over this period there is a warn ing Battery Age Alert to indicate it Temperature Compensation Set battery temperature compensation 0 5 mV C cl 0 mV C cl Default 4 2 ...

Страница 56: ...imit 1Hz 2Hz 3Hz 4Hz Default Load Set UPS Overload percentage 40 100 100 Default Set UPS load unbalance percentage 20 100 100 Default 4 2 7 Information Screen Touch icon to enter into the sub menu In this Information screen you can check the UPS configuration of the unit There are three sub menus Identification System and Battery Figure 4 19 Information menu 4 2 7 1 INFORMATION Identification Scre...

Страница 57: ...ntification screen page 4 2 7 2 INFORMATION System Screen When System submenu tab is touched the system power nominal voltage nominal frequency etc informa tion will be displayed as shown in Figure 4 21 and 4 22 Touch UP and DOWN arrows to switch different pages Figure 4 21 INFORMATION System screen page 1 ...

Страница 58: ...tab is touched the Battery nominal voltage capacity charging current etc information will be displayed as shown in Figure 4 23 Figure 4 23 INFORMATION Battery screen page 4 2 8 Events Screen When event occurs you will see flashing icon in the Main Screen as shown in Figure 4 24 You also can touch icon to check the latest event lists history events and reset all events as shown in Figure 4 25 ...

Страница 59: ...rging current etc information will be displayed Use UP and DOWN buttons to switch between different pages Figure 4 25 Events menu 4 2 8 1 Current Events When event occurs it will display Module ID and alarm code in Current Events screen It can save up to 50 events in current list Only 10 events can be listed in one page Therefore if it exceeds more than 10 you have to press icon to read other even...

Страница 60: ...to Table 4 13 Important setting changed UPS opera tion mode changes refer to Table 4 14 UPS mode change and control action executes refer to Table 4 15 Control execution will be saved in History Events Refer to Figure 4 27 for display screen Figure 4 27 History Events screen 4 2 8 3 Reset All Events The detailed event information is saved in history events It can save up to 500 events in history e...

Страница 61: ...be saved in History Events Refer to Figure 4 27 for display screen Figure 4 27 History Events screen 4 2 8 4 Reset All Events The Maintainer password is required to enter Reset All Events screen as shown in Figure 4 28 After entering cor rect password it will pop up reconfirmed screen Then touch icon to reset all events or touch icon to cancel this action as shown in Figure 4 29 Figure 4 28 Reset ...

Страница 62: ...er Inverter Voltage is over Peak Value Fault Inverter Voltage High Inverter Voltage is too high Fault Inverter Voltage Low Inverter Voltage is too Low Fault R Inverter Voltage Short R phase inverter Output is short circuited Fault S Inverter Voltage Short S phase inverter Output is short circuited Fault T Inverter Voltage Short T phase inverter Output is short circuited Fault RS Inverter Voltage S...

Страница 63: ...vices are demanding more power than the UPS can supply Warning Battery Open Battery not connected Warning Battery voltage High Battery voltage is too High Warning Module Un Lock As stated Warning Turn On Abnormal As stated Warning Charge Fail As stated Warning EEPROM Fail EEPROM operation error Warning Fan Lock As stated Warning Line Phase Error As stated Warning Bypass Phase Error As stated Warni...

Страница 64: ... Setup Change Password 16 Setup ECO Mode 17 Setup Baud Rate 18 Setup Bypass Mode 19 Setup Audible Alarm 20 Setup Auto Restart 21 Setup Factory Reset 22 Setup Cold Start 23 Setup EEPROM Reset 24 Setup Battery Mode Delay Time 25 Setup EPO Function 26 Setup Shutdown Restore Time 27 Setup Save Setting 28 Setup Redundancy 29 Setup Power Rating Setting 30 Setup Charger Test 31 Setup Nominal Battery Volt...

Страница 65: ...S Module includes dry contact Ports X1 X8 Extra Comm Slot SNMP Slot and communication port RS232 Port USB port on the front panel Figure 5 1 Dry contact ports and communication ports Dry Contact No Dry Contact No Function X1 Remote EPO input port X2 No use X3 No use X4 Maintenance Bypass Switch State Port X5 No use X6 Battery Cabinet Temperature Detection Port X7 No use X8 No use 5 1 Dry Contact P...

Страница 66: ...n pins 1 and 2 of X1 are closed Note 1 EPO function activates shutdown of the rectifiers inverters and static transfer switch But it does not internally disconnect the input power supply 2 The default setting of the EPO function logic is Normal Opened N O 5 1 2 X4 Maintenance Bypass Switch State Port X4 is the maintenance bypass switch port The port is shown in Figure 5 3 and described in Table 5 ...

Страница 67: ...escribed in Table 5 3 Figure 5 4 Battery Cabinet Temperature Detection Port Table 5 3 Description of Battery Cabinet Temperature Detection Port Name Position Description SCL X6 1 I C communication SCL Signal SDA X6 2 I C communication SDA Signal 3 0V X6 3 3V Power GND X6 4 GND 5 2 Extra Comm Slot There is an optional card Extra Comm Card which can be inserted into this slot This option can enhance...

Страница 68: ... personnel Fault S Inverter Voltage Short S phase inverter Output is shorted Contact service personnel Fault T Inverter Voltage Short T phase inverter Output is shorted Contact service personnel Fault RS Inverter Voltage Short R S inverter Output is shorted Contact service personnel Fault ST Inverter Voltage Short S T inverter Output is shorted Contact service personnel Fault TR Inverter Voltage S...

Страница 69: ...t Load Capacity and specification Warning Battery Open Battery not connected 1 Check battery breaker 2 Check if the battery connection is well connected 3 Check the setting of Nominal Battery voltage 4 Contact service personnel if necessary Warning Battery voltage High Battery voltage is too High Check the setting of Nominal Battery voltage and contact service personnel Warning Module Un Lock As s...

Страница 70: ...d the replacement of air filter Warning 1 Only the customer service engineers can service the power modules bypass module and battery modules 2 Remove the power modules bypass module and battery modules from top to bottom so as to prevent cabinet from toppling due to high center of gravity 3 The static transfer switch module is NOT hot pluggable It should be replaced only when the UPS is in mainte...

Страница 71: ...to Bypass operation 5 Press menu control system turn on YES to turn UPS on 7 3 Replacement Procedures Of Battery Module Warning Confirm the types of battery are the same 1 Remove the fixing screws on both sides of the front panel of the module and pull out the battery module 2 Push the new battery module into cabinet and fix it with screws on both sides of the front panel 7 4 Replacement Procedure...

Страница 72: ... for 200ms BATTERY SYSTEM Nominal voltage 120V Charge Current programable 8A 16A 24A 32A DIMENSIONS Enclosure 23 6 W x 43 3 D x 79 1 H 657 lbs WEIGHT Power module 19 0 W x 28 0 D x 5 1 H 74 lbs Battery module 4 1 W x 28 3 D x 6 0 H 70 lbs ENVIRONMENT Temperature 0 40 C 32 104 F Altitude 5 200 ft above sea level Audible noise 65dBA at 1m APPROVALS UL 1778 TUV cUL FCC A RoHS Energy Star all pending ...

Страница 73: ...150 for 200ms BATTERY Nominal voltage 120V SYSTEM Charge Current programable 8A 16A 24A 32A 40A 48A 56A DIMENSIONS UPS Enclosure 23 6 W x 43 3 D x 79 1 H 657 lbs WEIGHT Battery Enclosure 23 6 W x 43 3 D x 79 1 H TBD lbs Power module 19 0 W x 28 0 D x 5 1 H 74 lbs Battery module 4 1 W x 28 3 D x 6 0 H 68 lbs ENVIRON MENT Temperature 0 40 C 32 104 F Altitude 5 200 ft above sea level Audible noise 65...

Страница 74: ...ask you for the above information and if possible help solve your problem over the phone In the event that the unit requires factory service the technician will issue you a Return Mate rial Authorization number RMA If you are returning the UPS to Xtreme Power for service please follow these procedures 1 Pack the UPS in its original packaging If the original packaging is no longer available ask the...

Страница 75: ...tion approved third party b the equipment is damaged by the customer is improperly used or stored is subjected to an adverse operating environment or is operated outside the limits of its electrical specifi cations or c the equipment has been used or stored in a manner contrary to the equipment s operating manual intended use or other written instructions Any technical advice furnished by XPC Corp...

Отзывы: