background image

VESDA-E VES-A10-P Product Guide

40

www.xtralis.com

Relay #

Default

Assignment

Default to

Normally

Energized

Description for default configuration

Configurability

5

Action

No

Energizes when the Action alarm is
initiated.

Fully

configurable

6

Fire 1

No

Energizes when the Fire 1 alarm is initiated. Fire 1 cannot be

removed. Other

conditions can

be added.

7

Fire 2

No

Energizes when the Fire 2 alarm is initiated.

Fully

configurable

8

First Alarm

Sector 1

No

Energizes when sector 1 has been identified
as the first alarm sector.

Fully

configurable

9

First Alarm

Sector 2

No

Energizes when sector 2 has been identified
as the first alarm sector.

Fully

configurable

10

First Alarm

Sector 3

No

Energizes when sector 3 has been identified
as the first alarm sector.

Fully

configurable

11

First Alarm

Sector 4

No

Energizes when sector 4 has been identified
as the first alarm sector.

Fully

configurable

12

Scanning

No

Energizes when the detector is scanning the
inlet ports for smoke.

Fully

configurable

Table 4-2: Default Relay Assignments (continued...)

4.3.7

Unmonitored General Purpose Input (GPI)

The Unmonitored GPI is a programmable input which can be configured to initiate a number of different
actions, including, by default, a Remote Reset function. Refer to Section 5.5.11 on page 68 for further
information.

A voltage input of between 5V and 30V signals GPI ON. Less than 2V signals GPI OFF. The input is isolated
from the system by an opto-coupler device.

4.3.8

Monitored General Purpose Input (GPI) Wiring

The monitored GPI senses contact closure and is configurable to initiate the same actions as the unmonitored
GPI. "Remote Reset" is the default setting. A closed contact signals GPI ON and open contact signals GPI
OFF.

A 10K end of line resistor is used to allow the detector to monitor for open circuit faults in the wiring from the
detector to the contact. Refer to Section 4.3.11 for information on correct wiring of the End of Line resistor.

Содержание VESDA-E VES-A10-P

Страница 1: ...VESDA E VES A10 P Product Guide VES A10 P 4 Pipes August 2019 Document 33794_02 Part Number 30915 ...

Страница 2: ......

Страница 3: ...amage Xtralis is not responsible and cannot be held accountable for any liability that may arise due to improper use of the equipment and or failure to take proper precautions Only persons trained through an Xtralis accredited training course can install test and maintain the system Liability You agree to install configure and use the products strictly in accordance with the User Manual and produc...

Страница 4: ...ocument Convention Description Bold Used to denote emphasis Used for names of menus menu options toolbar buttons Italics Used to denote references to other parts of this document or other documents Used for the result of an action The following icons are used in this document Convention Description Caution This icon is used to indicate that there is a danger to equipment The danger could be loss o...

Страница 5: ... following measures re orientate or relocate the receiving antenna increase the separation between the equipment and receiver connect the equipment to a power outlet which is on a different power circuit to the receiver or consult the dealer or an experienced radio television technician for help FDA This Xtralis product incorporates a laser device and is classified as a Class 1 laser product that ...

Страница 6: ...reshold setting that initiates an evacuation signal must be set such that the sensitivity of each sampling hole is more sensitive than 10 m 3 2 ft as determined by the ASPIRE software Product Listings Regional approvals listings and regulatory compliance vary between product models Refer to www xtralis com for the latest product approvals matrix Document 33794_02 Part Number 30915 ...

Страница 7: ...em Check 45 5 Configuration 47 5 1 Communication between Xtralis VSC and the detector 47 5 2 Connecting to the Detector 51 5 3 Authentication 54 5 4 Commands 55 5 5 Configuration Options 58 5 6 Factory Default Settings 73 6 Commissioning 77 6 1 AutoLearn Smoke 78 6 2 AutoLearn Flow 79 6 3 Commissioning Smoke Test 79 7 Maintenance 81 7 1 Standby 81 7 2 Open the Door 82 7 3 Replacing the Filter 83 7...

Страница 8: ...10 P Product Guide 2 www xtralis com A Commissioning Forms 109 A 1 VES A10 P Detector Commissioning Configuration 113 A 2 ASPIRE Data 113 A 3 Smoke Test 113 A 4 Air Sampling Test Results 113 B Glossary 115 Index 117 ...

Страница 9: ...cs protection l More robust contamination resistance l Four configurable alarm levels per sector and a wide sensitivity range l Flow fault thresholds configurable per port l Long life easy to replace air sample filter l 3 5 colour touch screen for status review l Quiet operation l Advanced remote diagnostics l Area coverage up to 2 000 m 21 520 ft VES A10 P l Up to four inlet pipes l Total maximum...

Страница 10: ...VESDA E VES A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...

Страница 11: ... of the air is then drawn into the smoke detection chamber via the sampling module after first passing through the replaceable filter A further filter provides filtered clean air to protect the optical surfaces inside the detection chamber from contamination The detection chamber uses a short wavelength laser light source in conjunction with photodiodes and advanced imaging technology to achieve o...

Страница 12: ...re 1 Fire 2 Disabled Fault and Power l Controls Reset and Disable button Touch screen featuring a limited set of additional controls and lookup tools 2 3 1 Status LEDS The VESDA E VES A10 P detector features a range of LED Indicators which illuminate when their respective activation conditions are met LED Symbol Description Fire 2 The Fire 2 LED is lit when the Fire 2 Alarm threshold is reached Th...

Страница 13: ...ox for the Disable condition on the Relay configuration screen section 5 5 12 is ticked l To disable the detector once all alarms and faults have been acknowledged press and hold the button for approximately 4 seconds until the DISABLED LED illuminates continuously l To re enable the unit once all alarms and faults have been acknowledged press and hold the button for approximately 4 seconds until ...

Страница 14: ...een shows l Sector Smoke Level l Sector Alarm Level The sector status screen will be shown automatically when the smoke level exceeds the Adaptive Scan Threshold and scanning starts Display element Description Sector Alarm Level Sector Smoke Level bargraph including alarm threshold indicators Sector 1 name User configured Sector Name Airflow Screen The Airflow screen displays the flow level for ea...

Страница 15: ...Learn Smoke and AutoLearn Flow functions 0 Figure 2 8 Status Screen Navigation Press Left or Right arrows at the bottom of the screen to cycle through the available screens 2 4 Internal Buttons AutoConfig l To normalize the detector press and hold the button until the AutoConfig LED illuminates continuously approximately 2 seconds then release the button l To initiate AutoLearn Smoke and Flow pres...

Страница 16: ... connection between the VES A10 P detector and a PC or laptop running the Xtralis VSC software Note The USB port must not be used for permanent field connection Ethernet The Ethernet port is used for configuration and or monitoring purposes It enables direct or routed network connection between the detector and a PC or laptop installed with Xtralis VSC WIFI The WiFi module provides wireless connec...

Страница 17: ...gn Guides Application Notes for sampled air pre conditioning Storage Conditions Non operational l Humidity Dry 95 l Temperature 0 to 85 C l Must not be exposed to sunlight or other radiation sources Sampling Pipe Network l Maximum length per pipe when using four straight pipes l Four pipe VES A10 P 70 m 230 ft l Maximum total pipe length with branches l Four pipe VES A10 P 560 m 1 837 ft l Pipe Mo...

Страница 18: ...5 6 on page 73 for the default settings Referencing Reference smoke level source Table 2 2 VES A10 P Detector Specifications continued Table 2 3 Key Software Features Event Log Up to 20 000 events stored on FIFO basis AutoLearn l Minimum 15 minutes l Maximum 15 days 23 hrs 59 minutes l Recommended 14 days Thresholds are automatically changed from the previously set values to the updated values aft...

Страница 19: ...0 5 28 E 34 0 1 34 F 34 0 1 34 G 34 0 1 34 H 34 0 1 34 I 26 5 1 04 J 350 05 13 78 K 224 0 8 82 L 230 2 9 06 M 135 48 5 3 N 132 28 5 21 O 28 5 1 12 P 35 0 1 38 Q 45 0 1 77 R 127 0 5 0 S 143 0 5 63 T 26 0 1 02 Figure 2 10 Front top bottom and side dimensions VESDA E VES A10 P Product Guide www xtralis com 13 ...

Страница 20: ...VESDA E VES A10 P Product Guide A B C D E F mm inch A 17 5 0 69 B 315 0 12 4 C 17 5 0 69 D 144 99 5 71 E 77 2 3 04 F 3 5 0 1 Figure 2 11 Rear dimensions with Mounting Bracket 14 www xtralis com ...

Страница 21: ...ch A 224 0 8 82 B 112 0 4 41 C 40 9 1 61 D 268 39 10 57 E 40 71 1 6 F 20 25 0 8 G 183 5 7 22 H 20 25 0 8 Figure 2 12 Rear Dimensions with hole locations for direct mounting VESDA E VES A10 P Product Guide www xtralis com 15 ...

Страница 22: ...VESDA E VES A10 P Product Guide 16 www xtralis com This page is intentionally left blank ...

Страница 23: ...rds l Evenly arrange the sampling pipe network over return air grilles l The sampling pipe fits firmly into the tapered detector port DO NOT glue this connection l Allow sufficient movement at the detector to permit pipe removal for maintenance l Keep the exhaust pipe as short as possible to minimize airflow resistance in the pipe l Pipe ends must be made smooth for bonding l Sampling holes must b...

Страница 24: ...g Smoke Detection on page iii 3 4 Managing the Exhaust Air Air is expelled from the detector via the exhaust port at the bottom of the unit enclosure The air exhaust port is tapered to accommodate standard pipes of OD 25 mm ID 21 mm and to provide an airtight seal IPS inch pipes 1 05 inch OD require an adaptor VSP 961 as shown in Figure 3 2 If required connect an outlet pipe to the exhaust manifol...

Страница 25: ...xtralis com l A 24 VDC Power Supply and backup battery compliant with local fire protection codes and standards l Screws and inserts for the mounting bracket that are appropriate for the installation location l Type A to Type B USB Interface Lead required for initial configuration of the detector Figure 4 1 l Wrist strap for ESD prevention Figure 4 1 Type A to Type B USB Interface Lead 4 1 Prepare...

Страница 26: ...r Figure 4 4 noting the location of air sampling pipes and cable entry points Due to the rigid nature of the plastic pipe installation must provide for sufficient movement in all pipework air inlet air exhaust and cable pipes to allow pipe ends to be easily fitted and removed A B Legend A Min 50 mm 2 in below ceiling level B Mounting Bracket The detector can be mounted directly against a wall or o...

Страница 27: ...e user interface has the correct orientation The door must be moved to the other side of the fascia to allow access to the electrical sockets and filter This is done as follows 1 Place the detector on a flat surface with the back plate facing down 2 Open the front door and remove the fascia Refer to Sections 7 2 on page 82 and 7 4 on page 86 for further information Figure 4 5 Detector with fascia ...

Страница 28: ...ure 4 6 Tabs used to remove top and bottom cover Legend A Top cover retaining tabs B Bottom cover retaining tabs 4 Detach the tethers Figure 4 7 and Figure 4 8 You can leave the cables from the detector to the fascia connected Figure 4 7 Detaching the tethers ...

Страница 29: ...A10 P Product Guide www xtralis com 23 Figure 4 8 Detector with tethers detached 5 Detach the front door from the fascia by removing pin A from the hinge Figure 4 9 Figure 4 10 Leave pin B in place do not remove it ...

Страница 30: ...VESDA E VES A10 P Product Guide 24 www xtralis com B A Figure 4 9 Removing door hinge pin A Figure 4 10 Detaching door ...

Страница 31: ...by doing the following a Leave the fascia upright b Rotate the detector 180 degrees c Rotate the door 180 degrees and place it next to the right side of the fascia 7 Replace the door hinge pin Figure 4 12 Figure 4 13 A 180 o B Figure 4 11 Rotate detector and door and move door to right side of fascia ...

Страница 32: ...VESDA E VES A10 P Product Guide 26 www xtralis com Figure 4 12 Replacing the door hinge pin showing correct positioning of door and pin ...

Страница 33: ...he door hinge pin Figure 4 14 Correct positioning of door hinge pin when fully in place 8 Re attach the tethers Attach at the slots circled in Figure 4 15 Position the tethers in the slots and pull up as shown in Figure 4 16 Figure 4 15 Re attach tethers at circled positions ...

Страница 34: ...overs 10 Re attach the fascia Re attach to the front of the detector by tightening the two retaining screws as shown in Figure 7 8 11 The detector is now inverted The display should be upright while the exhaust vent is at the top and sampling pipe inlets at the bottom The electrical connections and filter should be accessible by opening the door ...

Страница 35: ...with the bottom depth line F E F B D A C D Legend A Mounting bracket B Sampling Pipes C Electrical Conduit D Pipe alignment marks E 3 4 inch IPS pipe 1 05 inch OD depth F 25 mm pipe depth Figure 4 17 Position Mounting Bracket in line with pipes 2 Mark the mounting surface through two keyholes B on the mounting surface Figure 4 18 A B B Legend A Mounting bracket B Keyholes Figure 4 18 Mark keyholes...

Страница 36: ... slots on the mounting bracket and slide the detector down until the top of the detector is flush with the top of the mounting bracket Figure 4 21 A A A Legend A Mounting buttons Figure 4 21 Mounting the detector 7 Open the door on the front of the detector Figure 4 22 Refer to Section 7 2 on page 82 for further information on how to open the door 8 Insert and tighten the locking screw A This secu...

Страница 37: ...nting template 3 Insert two M4 button head screws at positions A and B such that the screw head is protruding 7 mm from the wall Figure 4 24 Drill a pilot hole at position C for later insertion of a screw at Step 12 7mm Upright Detector Inverted Detector 25mm 3 4 IPS 25mm 3 4 IPS Edge of Detector 25m m 3 4 IPS 25m m 3 4 IPS Edge of Dete ctor B A A B C C Figure 4 24 Insert mounting screws 4 Positio...

Страница 38: ...ed retract the inlet and exhaust pipes and electrical conduit 10 Mount the detector onto the screws using the keyholes using the following steps Upright Detector Inverted Detector Figure 4 26 Mount the detector l Position the right keyhole on the rear of the detector over the head of the right screw A Figure 4 27 A A Upright Detector Inverted Detector Figure 4 27 Position detector over screw l Sli...

Страница 39: ...head of screw B Push the detector to the wall Figure 4 29 B B Upright Detector Inverted Detector Figure 4 29 Position detector on the second screw l Rotate the detector anticlockwise or clockwise for an inverted detector to lock the detector on to the screw Figure 4 30 Upright Detector Inverted Detector Figure 4 30 Rotate the detector 12 Insert an M4 screw at the small end of the detector s bottom...

Страница 40: ...VESDA E VES A10 P Product Guide 34 www xtralis com Upright Detector Inverted Detector Figure 4 31 Locking screw 13 Tighten the top and bottom screws 14 Insert the pipes and electrical conduit ...

Страница 41: ... is not UL tested Caution Electrostatic discharge ESD precautions need to be taken prior to removing the fascia from the detector in order to prevent damage to sensitive electronic components within the VES A10 P Attention Les precausions contre le decharge electrostatique dois etre respecter avant d ouvrir le panneau du detecteur afin de prevenir au dommage des composants electroniques a l interi...

Страница 42: ...Alert I 5 Action J 7 Fire 2 K 8 First Alarm Sector 1 L 9 First Alarm Sector 2 M 10 First Alarm Sector 3 N 11 First Alarm Sector 4 O 12 Scanning P 6 Fire 1 Comms R Ethernet S USB GPI T Monitored GPI U Unmonitored GPI Ground V Jumper for ground fault monitoring Q Chassis Ground Terminal Figure 4 33 Socket Locations 4 3 3 Power Source There are two sets of power terminals on the main board Figure 4 3...

Страница 43: ...efer to Codes and Standards Information for Air Sampling Smoke Detection on page iii 4 3 4 Communication Ports The front door must be opened in order to access the communication ports Refer to Section 7 2 for information on opening the front door and Figure 4 33 for the physical location of the ports Note For all connection methods the detector also provides a gateway to all the other devices on t...

Страница 44: ... detector to be able to detect ground faults on the VESDAnet wiring the Ground Reference Terminal Figure 4 33 must be connected to the local ground A A B Shield Module 1 Module 2 Module 3 Module 5 Module 4 Shield B A A B Shield Shield B A A B Shield Shield B A A B Shield Shield B A A B Shield Shield B Figure 4 35 Example closed loop VESDAnet network The VESDA E VES A10 P detector is shipped with t...

Страница 45: ...lay Operation URGENT FAULT Relay Fire 1 Relay No Fault Energized Fault or unpowered state No Fire De energized Fire Relay Assignments and Behaviour l Relays 1 2 4 5 7 8 9 10 11 12 are fully configurable l Relays 3 and 6 are fixed to Urgent Fault and Fire 1 respectively These relays may be assigned additional conditions l Relays 3 and 6 are changeover relays SPDT 1 Form C All the other relays are s...

Страница 46: ...ector Fully configurable 12 Scanning No Energizes when the detector is scanning the inlet ports for smoke Fully configurable Table 4 2 Default Relay Assignments continued 4 3 7 Unmonitored General Purpose Input GPI The Unmonitored GPI is a programmable input which can be configured to initiate a number of different actions including by default a Remote Reset function Refer to Section 5 5 11 on pag...

Страница 47: ...third party Input Output Loop module 3 inputs 1 output Note These are example drawings Refer to the appropriate product manual for the exact wiring details of the third party equipment Normally Closed NC Normally Open NO Normally Open NO Normally Closed NC Normally Open NO Fire Input EOL Normal Short Fire Open Wiring Fault EOL Normal Short Fire Fault Input EOL Normal EOL EOL EOL NC NO Monitored GP...

Страница 48: ...d standards The size of the battery is determined by l local codes and standards l the total power required by the system l back up time required l allowance for reduction in capacity with age l expected temperature variations Note It is recommended that batteries be inspected and changed as per manufacturer s specifications or as per local codes and standards To facilitate the calculation of the ...

Страница 49: ...inals and that the polarity is correct On power up l The Power LED illuminates and the detector runs a series of self diagnostic tests l If there is a fault the Fault LED illuminates To identify the fault check the Active Event List for the detector using Xtralis VSC l The aspirator starts up and air may be felt flowing out of the exhaust port It is normal for the detector to display airflow fault...

Страница 50: ...urther information The sampling air pipes are firmly connected to the air inlet ports Ensure that the pipes are NOT glued The power supply wiring has been connected to the detector If required the end of line resistor for the monitored GPI has been connected Refer to Section 4 3 11 on page 42 for further information The alarm and fault relay output terminals of the detector have been connected to ...

Страница 51: ...lling the VES A10 P detector before it is commissioned for use To perform the preliminary system check l Power up the detector by connecting the power supply to the Power In terminal l Check that the display is functioning l Check that the aspirator is functioning by determining whether air is being expelled from the exhaust port ...

Страница 52: ...VESDA E VES A10 P Product Guide 46 www xtralis com This page is intentionally left blank ...

Страница 53: ...n l configure the respective parameters in the detector including the authentication password l create a connection profile for Ethernet or WiFi as required l connect to the detector USB is used for initial configuration however it must not be used for permanent connection Permanent connection for secondary monitoring must only be done with Ethernet or WiFi For example the installer would connect ...

Страница 54: ...e 5 1 Connection Manager 2 Select Add The Add Connection dialog is displayed Figure 5 2 Figure 5 2 Add Connection 3 Select the VESDAnet connection option then select Next Adding a USB Connection 1 Select USB then select Next Figure 5 3 Figure 5 3 Select USB ...

Страница 55: ...k the checkbox next to Remember Password and then enter the password that has been configured in the detector configuration General Options for Ethernet and WiFi connection See section 5 5 1 Figure 5 6 Warning If the Remember Password option is selected the user will not be required to enter the password when a connection is requested Users should be aware that saving the password in this manner m...

Страница 56: ...VES A10 P Product Guide 50 www xtralis com Figure 5 6 Enter IP Address 3 Enter a unique name for the Connection or accept the pre generated name then select Finish Figure 5 7 Figure 5 7 Enter a Connection Name ...

Страница 57: ...tor and the PC installed with Xtralis VSC can be made using a router or switch Figure 5 9 or directly between the two devices Complex networks are beyond the scope of this document For a successful connection Ethernet connectivity must be enabled within the detector the detector must have an IP address and an authentication password must be set Configuration procedures for these requirements are d...

Страница 58: ... this document Figure 5 10 Connecting to a detector via WiFi using a router Enabling WiFi Connection The WiFi connection method only needs be configured once and then edited if there is a change to any of the relevant building network connection parameters 1 Connect to the detector using USB following the procedure described in Section 5 2 1 2 In the WiFi tab for the detector l For dynamic IP addr...

Страница 59: ... detectors on the VESDAnet with WiFi disabled Figure 5 11 Connection to a detector via another detector on VESDAnet using a WiFi connection Alternatively it is possible to connect using a High Level Interface HLI connected between the PC or Laptop with Xtralis VSC and the VESDAnet Socket in one of the devices on the VESDAnet Notes l The VES A10 P detector acts as a gateway on VESDAnet and allows a...

Страница 60: ... VES A10 P detector via Xtralis VSC user functionality is initially limited For additional privileges the user must log in to the detector using an 4 digit numeric PIN code In Xtralis VSC select Logon from the Connection menu and enter the PIN User Level Access Level Functional Authorization USR Low This is the USER or the OPERATOR level The user can view the event log and change the date and time...

Страница 61: ...y mode End Standby The End Standby command is available when the detector is in Standby mode The End Standby command causes the detector to exit Standby mode Reset The Reset command unlatches all latched alarms and faults and returns relays to their normal state Clears the Xtralis VSC active event list Start Normalize Air Flow Starts the air flow normalization process for the selected detector The...

Страница 62: ...low To cancel AutoLearn Smoke and Flow functions using the internal AutoConfig button press and hold the button for 5 seconds The LED will turn off Start AutoLearn Smoke Starts the AutoLearn Smoke process for the detector The detector monitors the environment and determines appropriate smoke thresholds The user is prompted to enter the monitoring period When the AutoLearn has finished the smoke th...

Страница 63: ...detector will behave as if real smoke has been detected Alarm relays will energize unless the detector is disabled Start Air Flow Fault Test Tests the air flow sensing system by shutting down the aspirator Start Relay Test Tests the available relays by activating and deactivating as required Start LED Test Tests each LED by cycling through all LEDs on the detector display panel Return to Factory D...

Страница 64: ...ame of the VESDAnet network The user can leave this blank if desired l Location A description of the physical location of the detector This name will appear on Xtralis VSC and on the LCD display of the A10 model detector l Serial Number The serial number of the device This is factory set and cannot be changed l VESDA Zone The unique zone number used to link this detector and remote display relay d...

Страница 65: ...k data from this device The non preferred port is used if for some reason transmissions on the preferred port fail For best performance in large networks this setting should be randomly distributed between connected devices l Loop Open Ended on This Device This should be checked if the network has been wired so either VESDAnet port A or VESDAnet B is not connected on this detector Xtralis recommen...

Страница 66: ... IP address Subnet Mask and Default Gateway fields are disabled Once the IP address has been successfully obtained by the detector it is displayed on the detector detail status screen Static IP Address Configuration l IP Address IPV4 static address This address must be used when creating a connection profile for the detector in Xtralis VSC l The default IP address is 192 168 0 200 This allows dire...

Страница 67: ...isting WiFi network l WiFi Enabled Controls whether detector attempts to use WiFi and connect to an access point l Access Point SSID Set by installer to suit building access point l Security mode WPA2 mode only l WPA Key Use button to enter WPA2 key required to join building access point WiFi IP Configuration Parameters The following parameters allow setting of a dynamic or static IP address for t...

Страница 68: ...imeouts Figure 5 16 Security Options l Maximum number of WiFi Ethernet connections The number of connections which can be running at any time WiFi and considered Ethernet together l USB Connection Idle Timeout minutes The USB connection will be dropped after no activity from the user on Xtralis VSC for this period of time l Ethernet WiFi connection idle timeout hours Ethernet and WiFi connections ...

Страница 69: ...hrough 4 The settings for day time alarm thresholds for each sector 1 through 4 l Alarm Level Night Sector 1 through 4 The settings for night time alarm thresholds for each sector 1 through 4 l Set all to Sector 1 Press this button to set all thresholds to the thresholds set for Sector 1 l Scanning Sector Scan Time The duration for which the detector examines the air for each sector when scanning ...

Страница 70: ...If the installation site flow conditions vary significantly it is recommended that the Major High and Major Low parameters are set closer to their limits l Major High The level of air flow considered to be so far above normal as to require urgent attention l Minor High The level of air flow considered to be above normal but not urgent l Minor Low The level of air flow considered to be below normal...

Страница 71: ...option page allows you to define the time period after which a filter fault will be generated Figure 5 19 Filter Options Service Interval days The time period after a new filter is installed at which non urgent fault Filter smoke dust limit nearly exceeded Fault 767 will be generated ...

Страница 72: ...Sector Names page allows the user to set the names of the sectors being monitored Figure 5 20 Filter Options Sector Name Sector Number 1 through 4 A description of the sector being monitored This name will appear on Xtralis VSC and on the LCD display of the A10 model detector ...

Страница 73: ... of the VES A10 P detector monitoring the protected area is limited to 50 of the Fire 1 alarm threshold of the VES A10 P A single reference detector can be used by multiple VESDA detectors within the protected area The percentage of reference smoke level subtracted can be set differently for each detector monitoring the protected area This is set using the dilution factor parameter There may be a ...

Страница 74: ...se Input Options The configuration options are as follows l GPI function Unmonitored and GPI function Monitored Refer to Table 5 3 below for a description of the individual selections l Button Lockout If the checkbox is ticked the Reset Disable and Acknowledge functions can t be executed using the front panel button Function State Change External Reset Unmonitored GPI The detector resets on a 0 VD...

Страница 75: ...nitored GPI l The detector is held in Standby mode see Section 7 1 while 5 VDC l The detector exits Standby mode at a 5 VDC to 0 VDC falling edge Monitored GPI l The detector is held Standby mode see Section 7 1 while contact is closed l The detector exits Standby mode when the contact opens Note No alarms can be generated while the detector is in standby mode 0V 5V Standby Open Closed Enabled Sta...

Страница 76: ...closure or opening of the contact and l The detector is held disabled while contact is closed l The detector is enabled when the contact opens 0V 5V Reset and enabled Disabled Reset Open Closed Disabled Reset Reset and enabled Inverted Reset Unmonitored GPI l The detector resets on a 5 VDC to 0 VDC falling edge Monitored GPI l The detector resets on the opening of the contact 0V 5V Reset Open Clos...

Страница 77: ... In addition each relay can be configured Normally Energized or Normally De Energized Figure 5 23 Relay Options Relay Assignments Select the conditions you want to assign to each relay by checking the checkbox es under the relay The following checkboxes cannot be changed l Relay 6 always reports Fire 1 l Relay 3 always reports Urgent Fault and is always Normally Energised You can assign more than ...

Страница 78: ...ve is removed from the relay coil when the condition occurs The default mode of the relays is listed in Table 4 2 Latching If the cause of a condition is removed for example smoke decreases below the threshold and latching is enabled the detector remembers the condition and holds the corresponding relays and displays in the active state as though the cause of the condition were still active Latchi...

Страница 79: ... No Automatically Obtain IP Address Unchecked Unchecked Checked No IP Address 3 192 168 0 200 n a n a No Subnet mask 3 255 255 255 0 n a n a No Default Gateway Blank n a n a No WiFi WiFi Enabled Unchecked Unchecked Checked No WiFi Configuration No l Access Point SSID Blank n a n a No l Security Mode WPA2 WPA2 WPA2 No l Security Key 4 None n a n a No IP Address Configuration l Automatically Obtain ...

Страница 80: ...e Change Logging 0 005 obs m 0 0016 obs ft 0 0001 obs m 0 000031 obs ft 0 2 obs m 0 0063 ofs ft Yes Significant Smoke Change VESDAnet 0 005 obs m 0 0016 obs ft 0 0001 obs m 0 000031 obs ft 0 2 obs m 0 0063 ofs ft Yes Scanning Sector Scan Time 8 seconds 8 seconds 15 seconds Yes Scanning Scan Delay 3 0 10 Yes Work Days Monday through Friday n a n a Yes Day Night Changeover Time l Enabled Unchecked U...

Страница 81: ...tion Factor 100 1 100 Yes General Purpose Inputs GPI Function Unmonitored Reset n a n a Yes GPI Function Monitored Mains OK n a n a Yes Button Lockout Unchecked Unchecked Checked Yes Relays Assignment of Relays to conditions See Table 4 2 n a n a Yes Normally Energized See Table 4 2 n a n a Yes Latching Checked Unchecked Checked Yes Beep Unchecked Unchecked Checked Yes AutoLearn Smoke and Flow Com...

Страница 82: ...VESDA E VES A10 P Product Guide 76 www xtralis com This page is intentionally left blank ...

Страница 83: ...faults during this time 3 Set the Pipes in Use value in the Airflow configuration options 4 Set the aspirator setting to the value used when designing the system in ASPIRE to achieve the required transport time 5 Normalize the airflow This takes approximately 3 minutes after which the pipe flow rates should be close to 100 6 Reset the detector after normalization It should now be running without f...

Страница 84: ...normal environmental background variations During the learning cycle if an alarm condition occurs AutoLearn will not complete its cycle In this situation the user must restart the AutoLearn process If AutoLearn is halted the alarm thresholds will be left at the previous settings Conditions experienced during learning are assumed to be representative of normal operating conditions The AutoLearn Smo...

Страница 85: ...e flow thresholds will be left at the previous settings Conditions experienced during learning are assumed to be representative of normal operating conditions The AutoLearn Flow learning times can be set between 15 minutes and 16 days with the default being set to 14 days 6 3 Commissioning Smoke Test It is recommended that a smoke test be carried out to verify the integrity of the pipe network to ...

Страница 86: ...VESDA E VES A10 P Product Guide 80 www xtralis com This page is intentionally left blank ...

Страница 87: ...ing authority l Ensure that any ancillary devices dependent on the detector are isolated before work commences Attention Pendant que le detecteur ou la zone est desactivee aucun feu d indication va etre emis par le detecteur Avant tout entretien ou tester l Informer les autorité de supervision appropriée l S assurer que tout les appareils auxiliaires dépendants sur le détecteur sont isolés avant d...

Страница 88: ...uide 82 www xtralis com 7 2 Open the Door Several maintenance functions require that front door be opened Open the Front Door 1 Open the door by inserting a thin screwdriver into hole B and pushing firmly Figure 7 1 Open the door ...

Страница 89: ... high levels of contamination Remove the Filter Note that it is not necessary to turn off the 24V DC power to the detector when removing and replacing the filter The detector will turn off the aspirator when it detects that the filter has been removed and a fault will be signaled 1 Open the front door Ensure that the area around the filter is free of lint and dust before removing the filter Refer ...

Страница 90: ...hich allow it to be tilted on the chamber manifold Figure 7 3 Tilt Filter towards the left hand side of the detector 4 Lift the filter out of the detector case Figure 7 4 Figure 7 4 Remove Filter Reinstall the Filter Note Ensure that the new filter is free of lint and dust 1 Tilt the filter towards the left and position its hinge pins in their recess Figure 7 5 ...

Страница 91: ...ww xtralis com 85 Figure 7 5 Engage hinge pins 3 Tilt the filter to the right 4 Firmly press as shown in Figure 7 6 until the filter makes a distinct clicking sound and no additional movement is possible Figure 7 6 Reinstall the Filter ...

Страница 92: ...moving the fascia from the detector A wrist strap must be connected to the case of the detector Figure 7 7 Attention Les precausions contre le decharge electrostatique dois etre respecter avant d ouvrir le panneau du detecteur Un bracelet doit être raccordé au panneau du détecteur Figure 7 7 Figure 7 7 Wrist Strap application Remove the Fascia 1 Turn off the 24V DC power to the detector 2 Remove t...

Страница 93: ...VESDA E VES A10 P Product Guide www xtralis com 87 Figure 7 8 Fascia removal remove screws 3 Remove the fascia and allow it to hang by the two tether straps Figure 7 9 Fascia hanging on two tethers ...

Страница 94: ... clear of dirt and debris prior to replacement Care must be taken during aspirator replacement The aspirator must be correctly seated it is essential to ensure that the gaskets are not damaged or dislodged from the underside of the aspirator Remove the Aspirator 1 Turn off the 24V DC power to the detector 2 Open the front door and remove the front fascia Refer to Sections 7 2 and 7 4 for further i...

Страница 95: ...VESDA E VES A10 P Product Guide www xtralis com 89 Figure 7 12 Remove aspirator from the detector Reinstall the replacement Aspirator To replace the aspirator follow the removal procedure in reverse ...

Страница 96: ...7 7 To replace the Smoke Detection Chamber perform the following steps 1 Open the front door and remove the front fascia Refer to Sections 7 2 and 7 4 for further information 2 Remove the Sampling Module as described in Section 7 7 on page 95 3 Remove Smoke Detection Chamber as described below 4 Install the new Smoke Detection Chamber as described below 5 Reinstall the Sampling Module as described...

Страница 97: ...VESDA E VES A10 P Product Guide www xtralis com 91 Figure 7 13 Undo Chamber retaining screws 4 Disconnect the chamber loom from the connector labeled J3 Figure 7 14 ...

Страница 98: ...VESDA E VES A10 P Product Guide 92 www xtralis com Figure 7 14 Disconnect Chamber Loom 5 Remove the chamber from the detector base Figure 7 15 Figure 7 15 Remove the Chamber from the detector base ...

Страница 99: ... 16 Position the indicated loom sections beside the air flow sensing module not on top of it This will ensure that when installing the chamber the looms are not caught between the chamber and the air flow sensing module Figure 7 16 Position the gray loom 2 Position the chamber looms A and B as shown in Figure 7 17 A B Figure 7 17 Position the Chamber looms ...

Страница 100: ...n the position shown so that the looms are not caught between the chamber and other parts of the detector Figure 7 18 Install the Chamber 4 Secure the four screws which hold the chamber to the detector base Figure 7 13 5 Reconnect the loom to J3 Figure 7 14 6 Reinstall the Filter Refer to Section 7 3 on page 83 for further information ...

Страница 101: ...rea around the Sampling Module is clear of dirt and debris prior to replacement Care must be taken during Sampling Module replacement The Sampling Module must be correctly seated in order for a correct seal to be established between the Sampling Module and the rest of the detector It is essential to ensure that the rubber seal on the underside of the Sampling Module is correctly in place Removing ...

Страница 102: ... P Product Guide 96 www xtralis com 4 Press on the lever on the connector to release the catch Figure 7 20 Figure 7 20 Release the Sampling Module cable 5 Undo the three screws holding the Sampling Module Figure 7 21 ...

Страница 103: ...VESDA E VES A10 P Product Guide www xtralis com 97 Figure 7 21 Undo Sampling Module screws ...

Страница 104: ...Sampling Module Figure 7 22 Figure 7 22 Remove Sampling Module Installing a replacement Sampling Module 1 Firmly press the Sampling Module into the detector in the direction of the arrow shown so that the rubber seal on the Sampling Module is seated on the pipes in the detector Figure 7 23 You will feel the module slide onto the pipes ...

Страница 105: ...VESDA E VES A10 P Product Guide www xtralis com 99 Figure 7 23 Reinstall Sampling Module 2 Tighten the three screws and re connect the Sampling Module cable Figure 7 19 ...

Страница 106: ...ke Detection Chamber as described in Section 7 6 on page 90 6 Remove Ultrasonics Flow Sensing and Scanning Module as described below 7 Install the new Ultrasonics Flow Sensing and Scanning Module as described below 8 Reinstall the Smoke Detection Chamber as described in Section 7 6 on page 90 9 Reinstall the Sampling Module as described in Section 7 7 on page 95 10 Reinstall the Aspirator as descr...

Страница 107: ...emove the Ultrasonics Flow Sensing and Scanning Module Installing the replacement Ultrasonics Flow Sensing and Scanning Module 1 Re install the Ultrasonics Flow Sensing and Scanning Module into the detector base ensuring that the looms are not trapped under the module 2 Secure the three screws that hold the Ultrasonics Flow Sensing and Scanning Module to the detector base 3 Reconnect the main boar...

Страница 108: ...VESDA E VES A10 P Product Guide 102 www xtralis com ...

Страница 109: ...ble 7 2 Spare Parts Part No Description VSP 955 VESDA E VES A10 P Scanner Manifold VSP 960 VESDA E Mounting Bracket VSP 961 VESDA E Exhaust Adaptor US VSP 962 VESDA E Filter VSP 962 20 VESDA E Filter 20 Pieces VSP 963 VESDA E Aspirator VSP 964 03 VESDA E Smoke Detection Chamber VSP 965 VESDA E Sampling Module VSP 968 VESDA E VES A00 P Front Cover Plastic LEDs VSP 969 S VESDA E VES A10 P Front Cove...

Страница 110: ...VESDA E VES A10 P Product Guide 104 www xtralis com This page is intentionally left blank ...

Страница 111: ...software to further investigate the fault 8 2 Troubleshooting with the Front Panel Display The main screen of the VESDA E VES A10 P touchscreen display features a range of fault indicators When a fault is generated the respective indicator will illuminate Use Xtralis VSC to further investigate the fault by reviewing the event log Fault Indicator Description General detector fault for example an el...

Страница 112: ... The Xtralis VSC software also displays any current faults in the active event list The list displays the date and time of the fault the serial number of the device on which the fault has occurred the zone number fault number and a description of the fault For detailed information about a fault select the fault in the active event list or the event log then press F1 Xtralis VSC will display the ca...

Страница 113: ...w l WPA 2 encryption must be used whenever Wi Fi is enabled l Restrict access to HLI devices to authorized personnel only l Passwords must be chosen in line with the guidelines in the detector user guide and provided to trusted users only l Default PIN codes must be changed as part of the initial configuration System Maintenance Requirements l Do NOT use the USB port for long term monitoring or al...

Страница 114: ...VESDA E VES A10 P Product Guide 108 www xtralis com This page is intentionally left blank ...

Страница 115: ...ire panel using the Xtralis VSC Relay Test command Turn each relay on off individually See below Relay 1 Tested Default assignment Disable Relay 2 Tested Default assignment Minor Fault Relay 3 Tested Default assignment Urgent Fault Relay 4 Tested Default assignment Alert Relay 5 Tested Default assignment Action Relay 6 Tested Default assignment Fire 1 Relay 7 Tested Default assignment Fire 2 Relay...

Страница 116: ... Sector 4 Fire 2 Fire 1 Action Alert First Alarm Urgent Fault relay connection to fire panel tested using the Xtralis VSC Urgent Fault Test command Minor Fault relay connection to fire panel tested using the Xtralis VSC Minor Fault Test command Smoke Test done Transport time tested Scanning relay connection to Fire Panel verified Disable Standby Relay connection to Fire Panel Verified ...

Страница 117: ...ault Relay 3 Tested Default assignment Urgent Fault Relay 4 Tested Default assignment Alert Relay 5 Tested Default assignment Action Relay 6 Tested Default assignment Fire 1 Relay 7 Tested Default assignment Fire 2 Relay 8 Tested Default assignment Sector 1 Relay 9 Tested Default assignment Sector 2 Relay 10 Tested Default assignment Sector 3 Relay 11 Tested Default assignment Sector 4 Relay 12 Te...

Страница 118: ...ion to Fire Panel verified using the Xtralis VSC Fault Test command for the detector Disable Standby Relay connection to Fire Panel Verified Scanning relay connection to Fire Panel verified Client Representative Name Test witnessed by Date Hand Over Documents Copy of this form ASPIRE Installation Data Pack ASPIRE Bill of Materials Configuration printout from Xtralis VSC for each detector Configura...

Страница 119: ...mand on the File menu A 2 ASPIRE Data Print the ASPIRE Installation Data Pack IDP in order to record the ASPIRE modeling results for the system A 3 Smoke Test Table A 2 Smoke Test commissioning form Test Results Test Method Type of Smoke Test Date A 4 Air Sampling Test Results Table A 3 Air Sampling Test results commissioning form Pipe 1 Pipe 2 Pipe 3 Pipe 4 Transport Time from End Cap Hole Test 1...

Страница 120: ...VESDA E VES A10 P Product Guide 114 www xtralis com This page is intentionally left blank ...

Страница 121: ... for example alarms troubles user commands which is stored in the detector F Fault An urgent fault is a condition where the system requires urgent attention as it may be unable to detect an alarm condition A minor fault is a condition where the system requires attention or maintenance but is still able to detect an alarm condition Fire Alarm Control Panel FACP A central monitoring and control syst...

Страница 122: ...protected area Relay A device on a detector that has an electrical contact which can be configured to close when a condition occurs such as fire alarm or a fault in the detector This is the primary method used to signal alarms and faults S Sampling Network The pipe network constructed to allow the VESDA E detector to draw air for sampling Sensitivity Sensitivity refers to sensitivity to smoke A hi...

Страница 123: ...toLearn flow 56 cancel AutoLearn smoke 56 disable 55 enable 55 normalize air flow 55 rebuild zone list 57 reset 55 return to factory defaults 57 set system date and time 57 standby 55 start air flow fault test 57 start alarm test 57 start AutoLearn flow 56 start AutoLearn smoke 56 start lamp test 57 start major fault test 57 start minor fault test 57 start relay test 57 commissioning 77 109 115 sm...

Страница 124: ...36 40 42 68 115 power supply voltage 40 68 reset isolate 68 standby mode 68 unmonitored 3 36 40 41 68 115 use night time threshold 70 H HLI 10 53 115 I isolate 36 39 70 L LED 3 5 7 43 68 81 105 M maintenance 12 check pipe flow 81 check pipe network 81 clean sampling point 81 filter inspection 81 flush pipe network 81 pipe integrity smoke test 81 power supply 81 mounting 11 29 31 44 bracket 19 loca...

Страница 125: ...6 39 41 43 55 68 71 105 115 action 36 alert 36 fault 36 39 fire 36 39 isolate 36 options 71 remote display 10 58 105 reset 5 7 40 43 55 68 70 77 S sampling module 5 95 103 sensitivity 3 11 115 settings 73 default 73 significant smoke change 63 specifications 11 alarm range 11 dimensions 11 power 11 weight 11 standby 55 69 81 83 88 90 supply voltage 11 36 T temperature 11 42 thresholds 5 11 action ...

Страница 126: ...VESDA E VES A10 P Product Guide 120 www xtralis com Z zone 57 58 81 115 ...

Отзывы: