5.5.6
Airflow Options
The Airflow options provide the ability to set:
l
limits for what the detector considers to be normal airflow behavior for the sampling pipe network
l
which pipe inlets are being used
l
aspirator speed
These settings should be confirmed in the ASPIRE design of the sampling pipe network.
Note:
Refer to Section 5.6 for the default settings.
Figure 5-17: Airflow Options
The Airflow configuration options are as follows:
l
Air Flow:
The air flow conditions, as a percentage of the normalized air flow, that will cause a fault to be
reported. If the installation site flow conditions vary significantly, it is recommended that the Major High
and Major Low parameters are set closer to their limits.
l
Major High:
The level of air flow considered to be so far above normal as to require urgent attention.
l
Minor High:
The level of air flow considered to be above normal but not urgent.
l
Minor Low:
The level of air flow considered to be below normal but not urgent.
l
Major Low:
The level of air flow considered to be so far below normal as to require urgent attention.
l
Significant Flow Change:
The amount of airflow change at which an event is recorded in the event log.
l
Delay:
The length of time between the air flow fault threshold being reached and the fault relay operation.
l
Pipes in Use:
The pipes that are actually being used. Refer to Section 3.3 on page 17 for further
information.
l
Aspirator:
Select the required Aspirator Speed setting 1 through 5, as determined using ASPIRE.
5.5.7
Filter Option
The Filter option page allows you to define the time period after which a filter fault will be generated.
Содержание VESDA-E VEP-A10-P
Страница 1: ...VESDA E VEP A10 P Product Guide VEP A10 P 4 Pipes April 2016 Document 22071_11 Part Number 30311 ...
Страница 2: ......
Страница 10: ...VESDA E VEP A10 P Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 22: ...VESDA E VEP A10 P Product Guide 16 www xtralis com This page is intentionally left blank ...
Страница 54: ...VESDA E VEP A10 P Product Guide 48 www xtralis com This page is intentionally left blank ...
Страница 82: ...VESDA E VEP A10 P Product Guide 76 www xtralis com This page is intentionally left blank ...
Страница 100: ...VESDA E VEP A10 P Product Guide 94 www xtralis com 1 2 3 Figure 7 21 Undo Sampling Module screws ...
Страница 108: ...VESDA E VEP A10 P Product Guide 102 www xtralis com This page is intentionally left blank ...
Страница 114: ...VESDA E VEP A10 P Product Guide 108 www xtralis com Z zone 58 60 79 103 ...