Xtralis VESDA LCD Programmer Product Guide

Xtralis 

VESDA

® 

6

www.xtralis.com

Table 1 - LCD Programmer specifications

The LCD Programmer Keys

The LCD Programmer has two rows of keys. The keys are used to move the cursor and to use 
the various functions of the LCD Programmer.

The top row of keys have dual functions and are known as “Soft Keys”. When the commands 
NO, BACK, YES, CONT, EXIT, QUIT, or WAIT are

 

displayed on the LCD screen, the soft key 

directly below the command actions the respective command. 

The bottom row are the “Hard Keys”. Each hard key has a single function. The function of the 
LCD Programmer keys are mentioned in Table 3, 

“Description of LCD Programmer keys and 

functions” 

on page 8.

Figure 3 - LCD Programmer keys

4

User Access Levels and PIN

User Access Level

The three user access levels allow different people to access different sets of functions. The 
functions that can be edited with USR, ADM and DST access levels are listed in 

LCD 

Programmer Screen Description

 on page 13.

Table 2 - User access levels 

Connections:

Terminal Connector 
to Head Processor 
Card or to 
expansion 
connector on 
another Xtralis 
VESDA device.

15 pin D-type 
connector. 
VESDAnet cable 
required. Connects 
to Detector or 
Remote 
VESDAnet Socket.

RS485 VESDAnet 
field wiring to 
screw terminals 
blocks (0.2 - 2.5 
mm, 30 - 12 AWG

User 
Level

Access 
Level

Functional Authorization

USR

Low

This is the USER or the OPERATOR level. The 
user can view the event log, change the date 
and the time. They can also perform selected 
VESDA Zone control functions. 

ADM

High

At the ADMINISTRATOR level access is 
available to most functions. These include 
setting alarm thresholds, normalizing air flows, 
and defining the relay Configuration.

DST

Absolute

The DISTRIBUTOR level allows unlimited 
access to all the system commands and 
parameters.

Legend

B

Soft  Keys

C

Hard Keys

Содержание LCD Programmer Hand Held

Страница 1: ...Xtralis VESDA LCD Programmer Product Guide Document Number 10194_05 Part Number 30004 ...

Страница 2: ......

Страница 3: ... cause equipment damage Xtralis is not responsible and cannot be held accountable for any liability that may arise due to improper use of the equipment and or failure to take proper precautions Only persons trained through an Xtralis accredited training course can install test and maintain the system Liability You agree to install configure and use the products strictly in accordance with the User...

Страница 4: ...tion Convention Description Caution This icon is used to indicate that there is a danger to equipment The danger could be loss of data physical damage or permanent corruption of configuration details Warning This icon is used to indicate that there is a danger of electric shock This may lead to death or permanent injury Warning This icon is used to indicate that there is a danger of inhaling dange...

Страница 5: ...rent power circuit to the receiver or consult the dealer or an experienced radio television technician for help FDA This VESDA product incorporates a laser device and is classified as a Class 1 laser product that complies with FDA regulations 21 CFR 1040 10 The laser is housed in a sealed detector chamber and contains no serviceable parts The laser emits invisible light and can be hazardous if vie...

Страница 6: ...Xtralis VESDA LCD Programmer Product Guide Xtralis VESDA iv www xtralis com ...

Страница 7: ...ccess Level 6 Personal Identification Number PIN 7 Hour Glass Symbol 7 5 Installing and Connecting the LCD Programmer 7 Installing an LCD Programmer in a Detector 7 Installing an LCD Programmer in a Remote Unit 7 Connecting the Hand Held LCD Programmer 7 6 Operating the LCD Programmer 7 Standby Mode 7 Navigating the LCD Programmer 8 Logging On Off the System 8 Automatic Log Off 8 Intentional Log O...

Страница 8: ...Xtralis VESDA LCD Programmer Product Guide Xtralis VESDA 2 www xtralis com ...

Страница 9: ...ough VESDAnet The Xtralis VESDA VLC 500 RO System Relay Module and AOM cannot be programmed using the LCD Programmer The programmer enables management and interrogation of Xtralis VESDA devices connected to VESDAnet Features of LCD Programmer The LCD Programmer features User friendly menu systems Multiple language support Single point of access to the entire VESDAnet network Alarm and fault simula...

Страница 10: ... plate of a VLP or VLS detector Front Cover or in an Xtralis VESDA Remote Mounting System For further information see the Xtralis VESDA Remote Systems Product Guide Figure 2 The Hand held LCD Programmer A hand held version of the programmer offers the flexibility of connecting to VESDAnet at multiple points Legend A Display B Soft Keys C Hard Keys ...

Страница 11: ...USR Operator ADM Administrator DST Distributor Security Access 3 character User Level ID 4 digit individual Personal Identification Number PIN Default PIN is available with Xtralis VESDA Distributors Operating Temperature Ambient 0 o to 39 o C 32 o to 103 o F Humidity 10 99 RH non condensing Maximum Xtralis VESDA Devices Addressed 250 devices VESDA Devices Addressed VLP Detector and Display VLS De...

Страница 12: ...nt people to access different sets of functions The functions that can be edited with USR ADM and DST access levels are listed in LCD Programmer Screen Description on page 13 Table 2 User access levels Connections Terminal Connector to Head Processor Card or to expansion connector on another Xtralis VESDA device 15 pin D type connector VESDAnet cable required Connects to Detector or Remote VESDAne...

Страница 13: ... data is received by the LCD Programmer if there is a large amount of information transferred to the LCD programmer this may take several minutes 5 Installing and Connecting the LCD Programmer Installing an LCD Programmer in a Detector The LCD Programmer module is snapped into the front cover of the Detector For wiring details please refer to the product guide for that detector Installing an LCD P...

Страница 14: ... logs you off it will display a warning message and beep Press any key on the programmer to stop the detector from automatically logging you off Key Key Type Description Used For Soft Directional Key Soft Key Function Moves Cursor to the left or right of the screen Scrolls highlighted item left right Actions a soft key question Soft Directional Key Soft Key Functions Moves the cursor up or down on...

Страница 15: ... programmer menu 1 of 4 34 Latching 1 Main Menu 2 Logon 3 VLP Detector 4 Setup By Zone 6 VLP Detector 138 Setup By Type 5 Zone Number and Name 7 Status 8 Event Log 9 View Events 10 Select Events 11 Zone Control 12 Smoke Thresholds 13 Day Thresholds 14 Night Thresholds 15 Alarm Delays 16 Change Over Times 17 Weekend 18 Holidays 19 Smoke Change 20 AutoLearn 21 Zone Number 22 Zone Name Location 23 Ai...

Страница 16: ...Weekend 53 Holidays 58 Smoke Change 54 Scanner 55 Scanner Delays 56 Sector Factor 57 Valve Operations 59 AutoLearn 60 Zone Number 61 Zone Name Location 62 Air Flow 65 Normalize 66 Filter 63 Flow Thresholds 64 Flow Control 67 Reference Detector 68 Rebuild Zone List 69 Power Supply Number 73 Latching 70 Relays Disp Connected 71 Relay Setup 72 Relay Startup Mode 74 Relay 1 7 12 Assignment 75 Diagnost...

Страница 17: ... Filter 94 Flow Thresholds 97 Reference Detector 98 Rebuild Zone List 99 Power Supply Number 100 Button Lockout 101 Diagnostics 102 Relay Test 103 Factory Defaults 104 Communications 105 Miscellaneous 106 Ancillary 107 Display Rly 108 Status 109 Zone Control 110 Zone Number 111 Location 112 Power Supply Number 113 Button Lockout 114 Relays Disp Connected 115 Relay Setup 117 Latching 118 Beeper 120...

Страница 18: ...1 Miscellaneous 132 HLI 133 Status 134 Location 135 Power Supply Number 136 Factory Defaults 137 Communications 140 System All Device 141 Status 142 System Control 143 AutoLearn 144 Set Date Time 145 Weekend 146 Holidays 152 Filter 151 Air Flow 153 Reference Detector 147 Users 148 Change User Details 149 Add User 150 Delete User 154 Button Lockout 155 Communications 156 Smoke Change 157 Miscellane...

Страница 19: ...VESDA Zone numbers and names are allocated this screen lists all the VESDA Zone numbers and names on VESDAnet All devices without a VESDA Zone number are grouped in an unconfigured devices menu The Ancillary devices include programmers HLI and SRMs USR 5 Address Zone Number and Name Lists all devices in the particular VESDA Zone USR 6 Address with a VLP Detector Lists functions available for acces...

Страница 20: ...nder Zone Address control are the same as the functions performed by the buttons on the display module Mode This controls the mode of the Multi Segment LCD display on any display connected to that zone Use the and the keys to change the mode Sensitivity Displays the sensitivity level of Fire 1 Smoke Displays the current smoke level Address Number Displays the assigned Address number for the detect...

Страница 21: ...levant week day will denote it as being weekend By default Saturday and Sunday are set as weekend days ADM 18 Holidays Insert the first and the last day of holidays to set the different smoke thresholds during this period ADM Scrn No Description Min Access Level Parameter Default Minimum Maximum Fire 2 Full Scale 2 000 obs m 0 020 obs m 20 000 obs m 0 625 obs ft 0 0062 obs ft 6 25 obs ft Fire 1 Fi...

Страница 22: ... detector ADM 23 Air Flow This screen lists the options available to monitor and manage air flows Flow Thresholds Flow Control Normalize ADM 24 Flow Thresholds Input the required High Urgent High Minor Low Minor and Low Urgent air flow thresholds Enter the time over which the air flow should be monitored above and below the threshold levels An appropriate urgent or minor air flow fault will be gen...

Страница 23: ... DST 28 Reference Detector If a reference detector is connected to VESDAnet enter the Reference Address Number Dilution Factor This is the factor by which the background levels have to reduce to reach the levels of the current VESDA Zone Delay This is the time taken for the current VESDA Zone to return to its ambient levels after background from the Reference Address is introduced ADM 29 Rebuild A...

Страница 24: ...to be reported even after the event is over Manual intervention is necessary to reset If the condition is unlatched the reporting of the condition automatically stops once the event is over To latch an alarm or a fault place a against the respective alarm level or fault The isolate function is fixed for unlatched and cannot be changed ADM Scrn No Description Min Access Level Parameter Default Rela...

Страница 25: ...o restore factory defaults highlight Restore and press Defaults OK Highlighting Start and pressing will acknowledge Factory Default settings and clear faults 12 30 31 33 34 35 38 57 68 and 72 DST ADM 39 Communications The Communications screen allows settings for Net Delay This function sets the maximum time for a message to travel around the network and return to the originating device If the mes...

Страница 26: ... Displays the current Status of the Address Smoke Level Displays the current smoke level in the VESDA Zone Alarms If the detector is in alarm mode the alarm stage is displayed Faults List of faults generated for each device assigned to the Address Isolated The isolated status is reported if the detector has been isolated Current Flow Reports the current percentage of air flow through each pipe SW ...

Страница 27: ...ace a and key to insert a x to deselect the option ADM DST 47 Address Control The four functions under Address Control are the same as the functions performed by the buttons on the Display Module Mode This controls the mode of the LCD Numerical display on the Display Use the and the keys to change the mode Sensitivity Displays the sensitivity level Smoke Displays the current smoke level Address Nu...

Страница 28: ...turday and Sunday are set as weekend days ADM 53 Holidays Insert the first and the last day of holidays to set the night fire thresholds during this period ADM 54 Scanner The Scanner Menu has 3 sub menus for Scanner Delays Thresholds Sector Factor Sectors 1 to 4 Valve Operations USR Scrn No Description Min Access Level Parameter Default Minimum Maximum Fire 2 2 000 obs m 0 020 obs m 20 000 obs m 0...

Страница 29: ...ws air sample from a previous pipe to clear out from the detector before it starts reading the air sample from the next pipe Thresholds The smoke threshold for the VLS Day Threshold The day smoke threshold for the VLS Night Threshold The night smoke threshold for the VLS ADM Scrn No Description Min Access Level Parameter Default Minimum Maximum Delay 3 seconds 0 seconds 10 seconds Sector Time 10 s...

Страница 30: ...ent log This is subject to the change occurring over the interval period that is input You can input the required obscuration and interval Change By Min Interval ADM DST Scrn No Description Min Access Level Parameter Default Minimum Maximum Factor 1 000 0 500 2 000 Parameter Default Minimum Maximum Fire 2 2 000 obs m 0 020 obs m 20 000 obs m 0 625 obs ft 0 0062 obs ft 6 25 obs ft Fire 1 0 200 obs ...

Страница 31: ...ld be monitored above and below the threshold levels An appropriate urgent or minor air flow fault will be generated once the air flow crosses the threshold and remains above or below the threshold for the period set as Delay ADM 64 Flow Control The Flow Control Screen permits changing the Aspirator speed for VLP and VLS Enter the Pipes in Use by placing a against the respective pipe Default 3000r...

Страница 32: ...ence detector These settings allow you to fine tune how much of the smoke detected by the reference detector is also likely to reach each detector Delay The amount of time it will take smoke to move from the reference detector to the other detectors ADM 68 Rebuild Address List Highlight Start and press to rebuild the Address List Use this option to rebuild the Address List after removing a display...

Страница 33: ...ult continues to be reported even after the event is over Manual intervention is necessary to reset If the condition is unlatched the reporting of the condition automatically stops once the event is over To latch an alarm or a fault place a against the respective alarm level or fault The isolate function is fixed for unlatched and cannot be changed ADM Scrn No Description Min Access Level Paramete...

Страница 34: ...condition Fault Test This causes a system fault for 30 seconds Flow Fault This causes a 30 second Air Flow fault Sector Test This allows all valves to be forced closed and open Scan Test This will perform a scan test Relay Test Refer to Screen 76 ADM 76 Relay Test This allows testing each relay by turning it ON and OFF ADM 77 Factory Defaults Factory Defaults To restore factory defaults highlight ...

Страница 35: ...For details on GPI functions please refer to the VLS Product Guide ADM DST 80 VLC Detector Lists functions available for accessing and managing the properties of the selected VLC detector Select the required option and press USR 81 Status Displays the current Status of the Address Smoke Level Displays the current smoke level in the VESDA Zone measured in obs m or ft Alarms If the detector is in an...

Страница 36: ...og of events highlight Start and press Note Use the key to place a and key to insert a X and deselect the option ADM DST 85 Address Control The four functions under Address Control are the same as the functions performed by the buttons on the Display Module Mode This controls the mode of the LCD Numerical display on the Display Use the and the keys to change the mode Sensitivity Displays the sensi...

Страница 37: ...ver the interval period that is input You can input the required obscuration and interval Change By Min Interval ADM DST Scrn No Description Min Access Level Parameter Default Minimum Maximum Fire 1 Fire 0 200 obs m 0 015 obs m 2 000 obs m 0 0625 obs ft 0 0046 obs ft 0 6250 obs ft Action Pre Alarm 0 140 obs m 0 010 obs m 1 995 obs m 0 044 obs ft 0 0031 obs ft 0 6234 obs ft Alert 0 080 obs m 0 005 ...

Страница 38: ... Input the required High Urgent High Minor Low Minor and Low Urgent air flow thresholds Enter the time over which the air flow should be monitored above and below the threshold levels An appropriate urgent or minor air flow fault will be generated once the air flow crosses the threshold and remains above or below the threshold for the period set as Delay ADM 95 Normalize The Normalize screen displ...

Страница 39: ...also likely to reach each detector Delay The amount of time it will take smoke to move from the reference detector to the other detectors ADM 98 Rebuild Address List Highlight start and press to rebuild the Address List Use this option to rebuild the Address List after removing a display module assigned to the detector ADM 99 Power Supply Number Input the number of the power supply that is assigne...

Страница 40: ...es that the device is set to meet UL specifications Latch Alarms This provides a YES NO option to latch unlatch all Alarms Latch Faults This provides a YES NO option to latch unlatch all Faults GP Input The GP Input permits setting the general purpose input functions For details on GPI functions please refer to the VLP Detector Guide ADM DST 106 Ancillary Devices Should be put under the same flow ...

Страница 41: ... Display Relay ADM 111 Location Allocate a VESDA Zone name and location and assign these to the respective Display Relay ADM 112 Power Supply Number Input the number of the power supply that is assigned to the detector If the VESDA Intelligent Power Supply is not being used enter 0 ADM 113 Button Lockout This screen provides the option to Lock or enable the buttons on a Display ADM 114 Relays Disp...

Страница 42: ...vel or fault The isolate function is fixed for unlatched and cannot be changed ADM 118 Beeper Placing a tick beside each of the fire and fault conditions will result in the beeper activating during this condition If the display is allocated to a VLS fire conditions for individual sectors can also be chosen for beep on or off To set a condition to beep place a against the respective condition ADM S...

Страница 43: ...en allows settings for Net Delay This function sets the maximum time for a message to travel around the network and return to the originating device If the message does not return within the prescribed time it is presumed lost and will be resent Pref Port This allows you to assign a preferred port for communication Health Check This function sets the frequency of health check messages sent around ...

Страница 44: ...ocate a VESDA Zone name and location and assign these to the LCD Programmer ADM 127 Power Supply Number Input the number of the power supply that is assigned to the detector If the VESDA Intelligent power supply is not being used enter 0 ADM 128 Address Control Lockout This screen allows you to lock or unlock the button functions on any Display in the VESDA Zone This stops someone logging on at an...

Страница 45: ... during production Sub Node Type Informs the type of HLI connected to VESDAnet USR 134 Location Allocate a VESDA Zone name and location and assign these to the LCD Programmer ADM 135 Power Supply Number Input the number of the power supply that is assigned to the detector If the VESDA Intelligent Power Supply is not being used enter 0 ADM 136 Factory Defaults Factory Defaults To restore factory de...

Страница 46: ...t Sector Display the First Alarm Sector in VLS Display Sensitivity Displays the sensitivity level Smoke Level Displays the current smoke level Address Number Displays the assigned VESDA Zone number for the detector Silence Silences beeping sound of the detector Scan Selecting this option in a VLS Display commences a Scan sequence of the assigned VLS Detector Reset Resets faults Isolate Starts and ...

Страница 47: ...and below the threshold levels An appropriate urgent or minor air flow fault will be generated once the air flow crosses the threshold and remains above or below the threshold for the period set as Delay ADM 152 Filter Set the service interval for changing the filter in this screen ADM 153 Reference Detector If a reference detector is connected to VESDAnet enter the Reference Address Number Diluti...

Страница 48: ...evices on the system are set to meet UL specifications Isolate Remind Provides an option to enable or disable the reminder beeper when the Isolate function is enabled Support Displays the contact phone number for support Device ID This provides an option to Name and Number Name Only or Number Only devices connected to VESDAnet Refresh Map Refreshes the VESDAnet map when a Detector Chassis is chang...

Страница 49: ...20 21 29 30 Alarms Status 13 Alert 31 Alert level 15 Ancillary Devices 34 AutoLearn 16 25 32 VLP Detector 40 Automatic Log Off 8 B Backward Action Key 8 Beeper 36 Button Lockout 33 35 System All Devices 41 C Cfg Code 20 29 Status HLI 39 Cfg Code Status 13 Change User Details Users System All Devices 41 Change Over Times 15 22 Clear Log 14 21 30 Communications 19 29 34 37 HLI 39 LCD Programmer 39 S...

Страница 50: ...ces 41 Fire 31 Fire 1 15 Fire 2 15 Flow Control 17 25 Flow Fault 28 33 Flow Thresholds 16 25 32 Forward Action Key 8 G GP Input 20 29 34 H Hard Keys 6 Health Check 19 34 37 Communications HLI 39 Communications LCD Programmer 39 Communications System All Devices 42 HLI Ancillary 39 Holidays 15 22 System All Devices 40 Hour Glass Symbol 7 Humidity 5 I Inactivity Time Out 5 Instant Fire Alarm 15 Inte...

Страница 51: ...ht Threshold 23 Night Thresholds 22 Smoke Thresholds VLP Detector 15 Normalize 17 25 32 O Open ended 19 37 Communications HLI 39 Communications LCD Programmer 39 Operating Temperature 5 Overlay Alert 31 P Page Down 8 Page Up 8 Personal Identification Number PIN 7 PIN 7 Power Consumption 5 Power Supply Number 17 26 33 35 HLI 39 LCD Programmer 38 Pre Alarm 31 Pref Port 19 34 37 Communications HLI 39...

Страница 52: ...m All Devices 42 Smoke Level 14 20 21 29 30 35 Smoke Level Status 13 Smoke Thresholds 14 21 30 31 Soft Keys 6 Software Version Installed 38 Standby Mode 7 Status 20 29 34 38 HLI 39 System All Devices 40 Status Faults 13 Status SW Version 13 Status VLP 13 Sub Node Type Status HLI 39 Supply Voltage 5 Support Miscellaneous LCD Programmer 39 SW Version 20 29 Status HLI 39 System Control System All Dev...

Страница 53: ...ce 14 Smoke 14 Smoke Level 14 Smoke Level Status 13 Smoke thresholds 14 Status alarm 13 Status Cfg Code 13 Status Current flow 13 Status Faults 13 Status Isolated 13 Status SW Version 13 SW Version status 13 User action 14 View events 13 VLP Settings 13 VLP Status 13 VLS Address 20 Address Control 21 Address Name Location 25 Address Number 25 Air Flow 25 Alarm Test 28 Alarms 20 21 AutoLearn 25 Cfg...

Страница 54: ...r 22 Sector Factor 24 Sector test 28 Sector time 23 Select Events 21 Silence 21 Smoke Change 24 Smoke level 20 21 Smoke Thresholds 21 Status 20 SW Version 20 Thresholds 23 UL Version 29 User Action 21 View Events 20 Weekend 22 Voltage 5 W Weekend 15 22 System All Devices 40 Z Zone AKA Address 29 Zone Number Zone Control VLS Detector 21 Zone with a VLS Detector Setup By Type 20 29 ...

Отзывы: