Xtralis
VESDA
®
Xtralis VESDA LCD Programmer Product Guide
www.xtralis.com
5
Product Specifications
Supply Voltage
18 to 30 VDC
Screen Display
70 mm x 37 mm (2.75 in x 1.45 in)
Full graphic display
Large characters
8 lines, 21 characters per line
Adjustable backlit screen with contrast control
Inactivity Time Out
10 minutes (Defaults to VESDA Standby screen)
Beeps at 1 minute and then continuously for 15 seconds before
log off
Push Button Keys
2 rows x 4 keys, each key 19 mm x 12 mm (0.75 in x 0.50 in)
User Levels
User (up to 10 Users)
Administrator (3 Administrators)
Distributor (1 Distributor)
Default User Level
IDs
USR = Operator
ADM = Administrator
DST = Distributor
Security Access
3 character User Level ID
4 digit individual Personal Identification Number (PIN)
(Default PIN is available with Xtralis VESDA Distributors)
Operating
Temperature
Ambient: 0
o
to 39
o
C (32
o
to 103
o
F)
Humidity
10-99% RH, non-condensing
Maximum Xtralis
VESDA Devices
Addressed
250 devices
VESDA Devices
Addressed
VLP Detector and Display
VLS Detector and Display
VLC Detector (VN Model) and Display
HLI (High Level Interface)
Relay Modules
Remote Relays
Power Usage
Power at 24 VDC
Current at 24
VDC
Module
Min
0.6 W
20 mA
Max
2.3 W
80 mA
Hand-held
Min
1.3 W
50 mA
Max
3.0 W
110 mA
Remote
Min
1.3 W
50 mA
Max
3.0 W
110 mA
Dimensions
Module
Hand Held
Remote
mm
98 x 130 x 30
105 x 135 x 60
140 x 150 x 90
Inches
3.9 x 5.1 x 1.21
4.1 x 5.3 x 2.4
5.5 x 5.9 x 3.5