181
For L (live cable)
Turn the digital multimeter to 750V AC, use your one hand to hold the metal end, and then
the other hand insert the pen to the L port of the socket. See the following figure. If the
multimeter shows 120, then you can see current live cable connection is standard. If the
value is less than 60, then you can see current live cable connection is not proper or it is
not the live cable at all.
For N (Neutral cable)
Turn the digital multimeter to 750V AC, use your one hand to hold the metal end, and then
the other hand insert the pen to the N port of the socket. See the following figure. If the
multimeter shows 0, then you can see current N cable connection is standard. If the
value is more than 10, then you can see there is inductive current and the neutral cable
connection is not proper. If the value is 120, then you can know misconnected the
neutral cable to the live cable.
Содержание HVR-1608PK
Страница 1: ...HVR 1608PK HVR H408PKC Hybrid Standalone DVR User s Manual...
Страница 29: ...20 Please refer to the following figure for detailed information See Figure 2 5 General Series...
Страница 30: ...21 HVR H408PKC Series HVR 1608PK Series Figure 2 5...
Страница 41: ...32 General Series HVR H408PKC Series 3 7 2 Audio Output HVR 1608PK Series Figure 3 3...
Страница 43: ...34 HVR 1608PK Series Figure 3 4 3 8 Alarm Input and Output Connection General Series...
Страница 49: ...40 HVR H408PKC Series HVR 1608PK Series Figure 3 9...
Страница 65: ...Figure 4 24 56 Figure 4 21 Figure 4 22 Figure 4 23...
Страница 113: ...104 Figure 5 58...
Страница 115: ...106 direction arrows in DVR...
Страница 177: ...167 448K 196M 512K 225M 640K 281M 768K 337M 896K 393M 1024K 450M 1280K 562M 1536K 675M 1792K 787M 2048K 900M...
Страница 192: ...182...