![Xinje XG Series Скачать руководство пользователя страница 61](http://html2.mh-extra.com/html/xinje/xg-series/xg-series_user-manual_3414440061.webp)
53
Appendix 1-2
.
Special data register list
Battery (SD005~SD007)
ID
Function
Description
SD005
Battery register
It will display 100 when the battery voltage is 3.1V, if the battery
voltaeg is lower than 2.5V, it will display 0, it means please
change new battery at once, otherwise the data will lose when
PLC power off.
SD007
Power down hold data error type
Clock (SD010-SD019)
ID
Function
Description
SD010
Current scan cycle
100us
,
us is the unit
SD011
Min scan time
100us
,
us is the unit
SD012
Max scan time
100us
,
us is the unit
SD013
Second (clock)
0~59 (BCD code)
SD014
Minute (clock)
0~59 (BCD code)
SD015
Hour (clock)
0~23 (BCD code)
SD016
Day (clock)
0~31 (BCD code)
SD017
Month (clock)
0~12 (BCD code)
SD018
Year (clock)
2000~2099 (BCD code)
SD019
Week (clock)
0(Sunday)~6(Saturday) (BCD code)
Flag (SD020-SD031)
ID
Function
Note
SD020
Model type
SD021
model
(
low-8
)
series
(
high-8
)
SD022
Compatiable system version
(
low
)
system version
(
high
)
SD023
Compatiable model version
(
low
)
model version
(
high
)
SD024
Model info
SD025
Model info
SD026
Model info
SD027
Model info
SD028
Suitable software version
SD029
Suitable software version
SD030
Suitable software version
SD031
Suitable software version
Stepper ladder (SD040)
ID
Function
Description
SD40
Flag of the executing process S