4. Using steps (XD series)
4-1. Prepartion
Open the function of data traffic for the Nano SIM card
Open the message function (optional)
XD series PLC hardware V3.4.5 and up
XD/EPPro programming software V3.5.1 and up
XINJEConfig tool version v1.6.375 and up
XD series PLC programming cable
PC (enable to visit internet, installed XD/EPPro software)
4-2. Module configuration
The module configuration needs XD/EPPro software and Config tool. Please make sure the PLC
hardware and software version meet the requirements in chapter 4-1.
4-2-1. Serial port setting
4-2-1-1. XD-4GBOX-ED configuration
XD series PLC serial port communication protocol includes Modbus RTU, XNET
(OMMS/TBN/PPFD), free format protocol. When connecting 4GBOX, make sure the parameters
are compatible with below table. The network number, station number is recommended to use
default parameters.
Communication protocol
XNET-PPFD
Serial port speed
1000000bps
Physical layer
TTL
Network ID
32768
Station number
1
When configuring the serial port parameters, please set the DIP switch as below and power on
again.
S1
S2
S3
S4
function
ON
-
-
OFF
Configuration mode
OFF
-
-
OFF
Running mode
Содержание 4GBOX