![xFusion Digital Technologies FusionServer G5500 V7 Скачать руководство пользователя страница 73](http://html2.mh-extra.com/html/xfusion-digital-technologies/fusionserver-g5500-v7/fusionserver-g5500-v7_technology-white-paper_5005726073.webp)
6.2 Environmental Specifications
Table 6-2
Environmental specifications
Category
Specifications
Temperature
● Operating temperature: 5°C to 35°C (41°F to 95 °F),
compliant with ASHRAE Classes A1 and A2
● Storage temperature (within three months): –30ºC to
+60ºC (–22ºF to +140ºF)
● Storage temperature (within six months): –15ºC to
+45ºC (5ºF to 113ºF)
● Storage temperature (within one year): –10°C to
+35°C (14°F to 95°F)
● Maximum rate of temperature change: 20ºC (36ºF)
per hour, and 5ºC (9ºF) per 15 minutes
NOTE
The highest operating temperature varies depending on the
server configuration. For details, see
.
Relative humidity (RH,
non-condensing)
● Operating humidity: 8% to 90%
● Storage humidity (within three months): 8% to 85%
● Storage humidity (within six months): 8% to 80%
● Storage humidity (within one year): 20% to 75%
● Maximum rate of humidity change: 20% per hour
Air volume
≥ 330 CFM
Altitude
≤ 3050 m (10,006.56 ft)
● When the server configuration complies with ASHRAE
Classes A1 and A2 and the altitude is above 900 m
(2952.76 ft), the highest operating temperature
decreases by 1°C (1.8°F) for every increase of 300 m
(984.24 ft).
● HDDs cannot be used at an altitude of over 3050 m
(10,006.56 ft).
Corrosive airborne
contaminant
Maximum growth rate of the corrosive product thickness:
● Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
● Silver corrosion rate test: 200 Å/month
FusionServer G5500 V7 Server