6 Product Specifications
2023-02-14
65
6.2 Environmental Specifications
Table 6-2
Environmental specifications
Category
Specifications
Temperature
⚫
Operating temperature: 5°C to 35°C (41°F to 95 °F)
(ASHRAE Classes A1 to A4 compliant)
⚫
Storage temperature (within three months):
–30°C to
+60°C (
–22°F to +140°F)
⚫
Storage temperature (within six months):
–15°C to
+45°C (5°F to 113°F)
⚫
Storage temperature (within one year):
–10°C to
+35°C (14°F to 95°F)
⚫
Maximum rate of temperature change: 20ºC (36ºF) per
hour, and 5ºC (9ºF) per 15 minutes
NOTE
The highest operating temperature varies depending on the
server configuration. For details, see the A.3 Operating
Temperature Limitations.
Relative humidity
(non-condensing)
⚫
Operating humidity: 8% to 90%
⚫
Storage humidity (within three months): 8% to 85%
⚫
Storage humidity (within six months): 8% to 80%
⚫
Storage humidity (within one year): 20% to 75%
⚫
Maximum rate of humidity change: 20% per hour
Air volume
≥ 330 cubic feet per minute (CFM)
Operating altitude
≤ 3050 m (10006.56 ft)
⚫
When the server configuration complies with ASHRAE
Classes A1 and A2 and the altitude is above 900 m
(2952.76 ft), the highest operating temperature
decreases by 1°C (1.8°F) for every increase of 300 m
(984.24 ft).
⚫
When the server configuration complies with ASHRAE
Class A3 and the altitude is above 900 m (2952.76 ft),
the highest operating temperature decreases by 1°C
(1.8°F) for every increase of 175 m (574.14 ft).
⚫
When the server configuration complies with ASHRAE
Class A4 and the altitude is above 900 m (2952.76 ft),
the highest operating temperature decreases by 1°C
(1.8°F) for every increase of 125 m (410.1 ft).
⚫
HDDs cannot be used at an altitude of over 3050 m
(10006.56 ft).
Corrosive gaseous
contaminant
Maximum growth rate of the corrosion product thickness:
⚫
Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
⚫
Silver corrosion rate test: 200 Å/month