FusionServer 1288H V5 Server
Technical White Paper
6 Product Specifications
2023-02-28
62
Category
Specifications
⚫
Maximum change rate: 20%/h
Air volume
≥ 96 cubic feet per minute (CFM)
Operating altitude
≤3050m
⚫
When the server configuration complies with ASHRAE
Classes A1 and A2 and the altitude is above 900 m
(2952.76 ft), the highest operating temperature
decreases by 1°C (1.8°F) for every increase of 300 m
(984.25 ft).
⚫
When the configuration complies with ASHRAE Class
A3 standards and the altitude is above 900 m (2952.76
ft.), the highest operating temperature decreases by
1°C (1.8°F) for every increase of 175 m (574.14 ft.).
⚫
When the server configuration complies with ASHRAE
Class A4 and the altitude is above 900 m (2952.76 ft),
the highest operating temperature decreases by 1°C
(1.8°F) for every increase of 125 m (410.1 ft).
⚫
HDDs cannot be used at an altitude of over 3050 m
(10006.44 ft).
Corrosive gaseous
contaminant
Maximum corrosion product thickness growth rate:
⚫
Copper corrosion rate test: 300 Å/month (meeting
level G1 requirements of the ANSI/ISA-71.04-2013
standard on gaseous corrosion)
⚫
Silver corrosion rate test: 200 Å/month
Particle contaminant
⚫
The equipment room environment meets the
requirements of ISO 14664-1 Class 8.
⚫
There is no explosive, conductive, magnetic, or
corrosive dust in the equipment room.
NOTE
It is recommended that the particulate pollution in the equipment
room be monitored by a professional agency.
Acoustic noise
The declared A-weighted sound power levels (LWAd) and
declared average bystander position A-weighted sound
pressure levels (LpAm) listed are measured at 23°C
(73.4°F) in accordance with ISO 7779 (ECMA 74) and
reported in accordance with ISO 9296 (ECMA 109).
⚫
Idle:
−
LWAd: 5.92 Bels
−
LpAm: 42.3 dBA
⚫
Operating:
−
LWAd: 6.14 Bels
−
LpAm: 46.3 dBA
NOTE
The noise generated during operation varies depending on the
server configuration, load, and ambient temperature.