System Specifications
975-0799-01-01
93
System Specifications
Freedom XC PRO 2000
Freedom XC PRO 3000
Transfer relay rating (A
a
)
30A
50A
Transfer time (milliseconds
b
)
Shore to inverter:
Inverter to shore:
<20 milliseconds
<20 milliseconds with a 20-second
delay
<20 milliseconds
<20 milliseconds with a 20-second
delay
Transfer voltage (V)
Shore to inverter:
Inverter to shore:
<85 V and >140 V
<135 V and >90 V
<85 V and >140 V
<135 V and >90 V
Cooling
Fan, activated by any of the following:
High internal temperature
High AC output power
Fan, activated by any of the following:
High internal temperature
High AC output power
Table 19 System specifications
a
Circuit breakers shall not carry more than 80% of their UL rating continuously.
b
To change the AC Transfer time (mode), see
Содержание Freedom XC PRO Series
Страница 4: ...This page is intentionally left blank...
Страница 6: ...This page is intentionally left blank...
Страница 28: ...This page is intentionally left blank...
Страница 64: ...This page is intentionally left blank...
Страница 92: ...This page is intentionally left blank...