Adjusting Feature Settings in Configuration Mode
44
Freedom XC 1800 (12VDC) Owner's Guide
Settings
Setting Name
Setting
Number
Default
Value
Range of Values
Description
Inverter Ignition
Control
01
ATO
OFF
LOT
ATO
See
Description of Ignition Control Features on page 32
.
LBCO Voltage
02
11
.
8
10
.
1
to
12
.
8
The voltage setting value can be adjusted by 0.1 increments.
The inverter is able to recover automatically at LBCO voltage
+ 2.0 V (default).
LBCO Shutdown
Delay Timer
03
300
0
to
300
When the range is from 1 to 20, the timer setting value can be
adjusted by 1-s increments. When the range is from 20 to 300,
the timer setting value can be adjusted by 10-s increments.
LBCO Recovery
Voltage
04
12
.
3
12
.
0
to
16
.
0
The range is from LBCO v 0.2 to 16, adjusted by 0.1
increments. Selecting a higher value than the battery’s actual
fully-charged voltage level will disable the auto-recovery
feature. You may manually reset the inverter/charger when
the low battery cut off event occurs.
Power Save Time
05
0FF
OFF
,
1
to
25
The range is from 1 to 25, adjusted by 1-h increments. The
next setting after 25 is OFF.
Power Save (Load
Sensing) Mode
06
dIs
ENA
(enable)
,
DIS
(disable)
When enabled, the inverter/charger’s “no load” loss can be
reduced further when total load is less than 25 W.