97-0019-01-01
59
Configuring the Freedom SW using the SCP
Charger Settings Menu
The
Charger Settings
menu provides options for
configuring the Freedom SW to operate from your battery
bank.
Figure 28
Charger Settings Menu Screen
FSW3012 00: Chg Settings
Batt Type
Custom Settings
Batt Capacity
Max Chg Rate
Charge Cycle
ReCharge Volts
Absorb Time
Auto Recharge
Default Batt Temp
[Flooded]
[440Ah]
[100%]
[3-Stage]
[12.5V]
[180min]
[Enabled]
[Warm]
[*Flooded] [Gel] [AGM] [Custom]
[*3-Stage] [2StgNoFloat]
[*Enabled] [Disabled]
[*Warm] [Hot] [Cold]
Table 10
Setting Defaults and Ranges
Model
Freedom SW 2012 / 3012
Freedom SW 2024 / 3024
Item
Default
Min
Max
Default
Min
Max
Batt Type
Flooded
Flooded, Gel,
AGM, Custom
Flooded
Flooded, Gel,
AGM, Custom
Batt Capacity
2000-watt models
250Ah
50Ah
2000Ah
250Ah
50Ah
2000Ah
Batt Capacity
3000-watt models
440Ah
440Ah
Max Chg Rate
100%
10%
100%
100%
10%
100%
Charge Cycle
3Stage
3Stage,
2StgNoFloat
3Stage
3Stage,
2StgNoFloat
ReCharge Volts
12.5V
11.0V
13.5V
25.0V
22.0V
27.0V
Absorb Time
180min
1min
480min
180min
1min
480min
Auto ReCharge
Enabled
Enabled,
Disabled
Enabled
Enabled,
Disabled
Default Batt
Temp
Warm
Hot, Warm, Cold
Warm
Hot, Warm, Cold
FSW Owners Guide.book Page 59 Tuesday, August 7, 2018 9:03 AM
Содержание Freedom SW 815-2012
Страница 2: ...FSW Owners Guide book Page ii Tuesday August 7 2018 9 03 AM ...
Страница 14: ...FSW Owners Guide book Page iv Tuesday August 7 2018 9 03 AM ...
Страница 30: ...FSW Owners Guide book Page 16 Tuesday August 7 2018 9 03 AM ...
Страница 116: ...FSW Owners Guide book Page 102 Tuesday August 7 2018 9 03 AM ...
Страница 121: ...FSW Owners Guide book Page i Tuesday August 7 2018 9 03 AM ...