58
Freedom SW 230V Owner’s Guide
Configuring the Freedom SW using the SCP
Stacking Configuration Menu
The
Stacking
menu configures the Freedom SW 230V to operate
as a part of a multi-unit installation.
When installing a stacked system, every setting on the
Stacking
menu (except for
Dev Name
) must be configured for each Freedom SW
230V in the system. The settings should be configured in the following
order:
•
Dev Number
•
Stack Mode
Figure 33
Stacking Menu Screen
IMPORTANT:
Accessing this menu automatically places the Freedom SW
230V in standby mode. When entering the
Stacking
menu, the unit
identifies itself by flashing all front panel lights. After exiting the
Stacking
menu, the Freedom SW 230V returns to operating mode and the front panel
lights stop flashing.
NOTE:
The same
Battery
number must be used for all stacked Freedom
SW 230V units
.
g
Dev Name
Dev Number
Stack Mode
AC In
Battery
[00]
[01]
[Master]
[SHORE1]
[Batt1]
[*Master] [Slave] [L2Master]
[*SHORE1] [SHORE2
to
5] [GEN1
to
5] [None]
Table 17
Stacking Menu Description and Values
a
a. Applies to all Freedom SW 230V models.
Item
Description
Default
Range
Dev Name
Allows the customizing of the
default name for the inverter/
charger. This setting is
optional and does not affect
operation. See “Setting the
Device Name” on page 59.
FSW3524E
in the
case of Freedom
SW 3524-230.
Can be changed by
the user.
Dev Number
Allows setting of a unique unit
number in a multiple-unit
system. See “Setting the
Device Number” on page 60.
00
00
–
31
Stack Mode
Parallel Stacking
: For this to
operate, one Freedom SW
230V must be configured to
Master
and the other as
Slave
, otherwise a system-
wide fault is asserted.
Master
Master,Slave,
L2Master
b
b.
L2Master
is not supported in Freedom SW 230V models.
AC In
Identifies to the system the
kind of AC input the
inverters are accepting.
SHORE1
SHORE1
–
SHORE5
GEN1
–
GEN5
NONE
Battery
Points the system to which
battery bank is used.
Batt1
Batt1
–
Batt5
FSW 230V Owners Guide.book Page 58 Tuesday, August 7, 2018 9:38 AM
Содержание Freedom SW 230V 815-3524-02
Страница 2: ...FSW 230V Owners Guide book Page ii Tuesday August 7 2018 9 38 AM...
Страница 10: ...FSW 230V Owners Guide book Page viii Tuesday August 7 2018 9 38 AM...
Страница 14: ...FSW 230V Owners Guide book Page iv Tuesday August 7 2018 9 38 AM...
Страница 98: ...FSW 230V Owners Guide book Page 84 Tuesday August 7 2018 9 38 AM...
Страница 103: ...FSW 230V Owners Guide book Page i Tuesday August 7 2018 9 38 AM...