Adjusting Settings in Configuration Mode
975-0999-01-01
37
Invert Sub-settings
Setting Name
Setting
Number
Default
Value
Range of Values
Unit Step
Description
Low Battery Cutout
(LBCO)
I1
44
.
0
36
.
0
to
50
.
0
V
0.1
Controls when the inverter turns off due to a low
battery voltage condition. The inverter will turn
off only after this level has been reached for the
period of time set by the LBCO Delay. This
setting is not temperature compensated.
NOTE
: When battery voltage reaches below this
value, the battery must be recharged.
LBCO Hysteresis
I2
6
.
0
0
.
0
to
10
.
0
V
0.1
Determines the Low Battery Recovery Voltage
Level which is a summation of LBCO + LBCO
Hysteresis. The unit will resume operation if the
battery voltage exceeds the LBCO Recovery
Voltage Level.
LBCO Delay
I3
10
0
to
600
s
5
Controls how long the inverter is allowed to
operate at or below the LBCO level before
turning off due to a low battery voltage
condition. When the range is from 1 to 20, the
timer setting value can be adjusted by 1-second
increments, then by 5-second increments above
20 seconds.