Load Sense in Series Stacking
975-1057-01-01
60
3. From the RV-C system device controller, if available,
navigate to the device screen for the inverter you want to
configure as a secondary device.
4. Navigate to the Advanced Settings screen and select
Stacking.
5. Selecting Stack Mode, change it from
Master
to
Slave
, if
you are parallel-stacking the Freedom SW-RVCs or
Selecting Stack Mode, change it from
Master
to
L2Master
,
if you are series-stacking the Freedom SW-RVCs.
6. Save the configuration and exit to the Home screen of the
RV-C system device controller, if available.
NOTES
:
The only situation in which the secondary unit may shut down the
primary unit is when error conditions are detected such as high or
low battery voltage, overcurrent, or over-temperature conditions.
Both inverters will auto reset after a fault condition has been
cleared. The exception is that an overcurrent condition will
generate a shutdown for both inverters that will require a manual
restart of the system.
Load Sense in Series Stacking
When configured for 120/240-volt series stacking, each
inverter/charger operates independently in search mode and
attempts to detect loads connected to its terminals only.
Load Sense Operation in
Parallel Stacking
When two inverter/chargers are stacked for parallel operation,
load sense behavior on the secondary unit is modified and is
dependent on how much total load is on the system.