Module for process control in CO
2
refrigeration plants with rack and gas cooler control
ANI-2F1-A_V2.0.0_PI_2022-01_EN
7
Subject to technical changes
ANI-2F1-A
Analogue inputs: Voltage Uin 1 - Uin 2
Analogue inputs: Current Iin 1 - Iin 5
Analogue inputs: Sensors S 1 - S 16
127
DI 17
230V~
HP rack fault
137
N
128
DI 18
230V~
GC fan fault
138
N
129
DI 19
230V~
UPS / gas warning 1
fault
139
N
130
DI 20
230V~
RCCB / gas warning
2 fault
140
N
Terminal
Analogue input
Potential
Assignment
41
Uin 1
GND
Not available
42
0-10V
43
Uin 2
GND
Not available
44
0-10V
Terminal
Analogue input
Potential
Assignment
151
Iin 1
4-20mA
MT 1 p0
152
23V=
153
Iin 2
4-20mA
p.mp
154
23V=
155
Iin 3
4-20mA
p.gc
156
23V=
157/158
Iin 4 Not used
159/160
Iin 5 Not used
Terminal
Sensor input
Sensor type
Assignment
161/162
S 1
TRK
Ts MT
163/164
S 2 Not used
165/166
S 3 Not used
167/168
S 4
TRK
T.out
169/170
S 5
DGF
T.gc 1
171/172; 173/174;
175/176; 177/178;
179/180; 181/182;
183/184; 185/186;
187/188; 189/190;
S 6 - S 15 Not used
191/192
S 16
TRK
Control cabinet sen
-
sor
193/194
Not used
Terminal
Digital input
Potential
Assignment