Settings
MIQ/CR3; DIQ/CR3
4 - 30
ba64107e08
05/2006
4.6.1
Recorder
Function
The measured values of the linked sensor at the current output are set
up as current intensity in the
Recorder
application. The output of
measured values is laid down in the
Recorder type
,
Start value
and
End
value
settings.
Settings
Setting
Selection/Values
Explanation
Recorder type
0 to 20 mA or
4 to 20 mA
Start value
within the
measuring range
(sensor-
dependent)
Minimum spacing:
5 % of the measuring
range
End value
Measured variable
Main variable
Adjoining variable
Main variable
designates
the actual measured
parameter of the sensor
(e.g. pH, oxygen, etc.).
Adjoining variable
designates an additional
measured parameter
(e.g. temperature).
Attenuation
0 ... 40 mA/s
Speed of change of the
output current (mA/s) in
the case of an erratic
change of the input
signal.
Behavior at error
Fixed current
value
In case of system errors
and sensor errors, and in
case of measured values
outside the range
between
Start value
and
End value
, the current
output supplies the
specified fixed current
value.
Possible values:
0 ... 21 mA.
Unchanged
The current at the output
remains unchanged.