Warnings and Cautions:

Installation Instructions

Secure Racking

If Secure Racked units are installed in a closed or multi-unit rack assembly, they may 
require further evaluation by Certification Agencies.  The following items must be 
considered.

1.  The ambient within the rack may be greater than room ambient.  Installation 

should be such that the amount of air flow required for safe operation is not 
compromised.  The maximum temperature for the equipment in this environment is 
45°C.  Consideration should be given to the maximum rated ambient.

2.  Installation should be such that a hazardous stability condition is not achieved due 

to uneven loading.

Input Supply

1.  Check nameplate ratings to assure there is no overloading of supply circuits that 

could have an effect on overcurrent protection and supply wiring.

2.  When installing 48 VDC rated equipment, it must be installed only per the following 

conditions:

A.  Connect the equipment to a 48 VDC supply source that is electrically isolated 

from the alternating current source.  The 48 VDC source is to be connected to 
a 48 VDC SELV source.

B.  Input wiring to terminal block must be routed and secured in such a manner 

that it is protected from damage and stress.  Do not route wiring past sharp 
edges or moving parts.

C.  A readily accessible disconnect device, with a 3 mm minimum contact gap, 

shall be incorporated in the fixed wiring.

Grounding

Reliable earthing of this equipment must be maintained.  Particular attention should 
be given to supply connections when connecting to power strips, rather than direct 
connections to the branch circuit.

No Serviceable Parts Inside; Authorized Service Personnel Only

Do not attempt to repair or service this device yourself.  Internal components must be 
serviced by authorized personnel only.

•  Shock Hazard - Do Not Enter

•  Lithium Battery 

CAUTION:  Danger of explosion if battery is incorrectly replaced.  Replace 
only with same or equivalent type recommended by the manufacturer.  
Discard used batteries according to the manufacturer's instructions.

Содержание RSM Series

Страница 1: ...M Series RemoteSiteManagers RSM xRy Series RemoteSiteManagerswithPowerControl Products Covered TSM Series RSM Series RSM xRy Series TSM 40 Models RSM 16 Models RSM 16R16 Models TSM 24 Models RSM 8 Models RSM 8R8 Models TSM 8 Models RSM 2R4 Models User s Guide ...

Страница 2: ...Connect the equipment to a 48 VDC supply source that is electrically isolated from the alternating current source The 48 VDC source is to be connected to a 48 VDC SELV source B Input wiring to terminal block must be routed and secured in such a manner that it is protected from damage and stress Do not route wiring past sharp edges or moving parts C A readily accessible disconnect device with a 3 m...

Страница 3: ...sconnect the power supply cable s from the power source s Two Power Supply Cables Note that some TSM RSM series units and RSM xRy series units feature two separate power inlets and a separate power supply cable for each power inlet In addition RSM 16R16 series units feature four separate power inlets and a separate power supply cable for each power inlet Make certain to disconnect all power supply...

Страница 4: ...ponsible for compliance could void the user s authority to operate the equipment EMC Safety and R TTE Directive Compliance The CE mark is affixed to this product to confirm compliance with the following European Community Directives Council Directive 89 336 EEC of 3 May 1989 on the approximation of the laws of Member States relating to electromagnetic compatibility and Council Directive 73 23 EEC ...

Страница 5: ...y Cable Keeper 4 1 4 1 3 DC Powered Units 4 2 4 2 Connecting the Network Cable 4 2 4 3 The Internal Modem Port 4 2 4 4 Connection to Switched Outlets 4 3 4 5 Connecting Devices to the TSM RSM Serial Ports 4 3 4 6 Emergency Shut Off Function 4 3 5 Basic Configuration 5 1 5 1 Communicating with the TSM RSM Unit 5 1 5 1 1 The Text Interface 5 1 5 1 2 The Web Browser Interface 5 3 5 1 3 Access Via PDA...

Страница 6: ... Security 5 55 5 9 3 1 Adding IP Addresses to the Allow and Deny Lists 5 56 5 9 3 2 Linux Operators and Wild Cards 5 57 5 9 3 3 IP Security Examples 5 57 5 9 4 Static Route 5 58 5 9 5 Domain Name Server 5 58 5 9 6 SNMP Access Parameters 5 59 5 9 7 SNMP Trap Parameters 5 61 5 9 8 LDAP Parameters 5 62 5 9 8 1 Adding LDAP Groups 5 64 5 9 8 2 Viewing LDAP Groups 5 65 5 9 8 3 Modifying LDAP Groups 5 65...

Страница 7: ...lug Status Screens 8 3 8 5 The Plug Group Status Screen 8 4 8 6 The Current Metering Status Screen RSM 8R8 CM Series Only 8 5 8 7 The Current History Screen RSM 8R8 CM Series Only 8 6 8 8 The Power Range Status Screen RSM 8R8 CM Series Only 8 7 8 9 The Power History Screen RSM 8R8 CM Series Only 8 8 8 10 The Port Diagnostics Screen 8 9 8 11 Alias Status Screen 8 9 8 12 The Alarm Status Screen 8 9 ...

Страница 8: ...12 1 13 Operation via SNMP 13 1 13 1 TSM RSM SNMP Agent 13 1 13 2 SNMPv3 Authentication and Encryption 13 1 13 3 Configuration via SNMP 13 2 13 3 1 Viewing Users 13 3 13 3 2 Adding Users 13 3 13 3 3 Modifying Users 13 3 13 3 4 Deleting Users 13 3 13 4 Plug Control via SNMP 13 4 13 4 1 Controlling Plugs 13 4 13 4 2 Controlling Plug Groups 13 5 13 5 Configuring Serial Ports 13 6 13 6 Viewing Unit St...

Страница 9: ...fications Apx 1 A 1 Standard TSM Series Units and Standard RSM Series Units Apx 1 A 2 RSM xRy Series Units Apx 2 B Serial Interface Description Apx 3 B 1 Serial Port RS232 Apx 3 B 2 TSM and RSM xRy Series RJ45 Serial Ports Apx 4 B 3 RSM Series DB9M Serial Ports Apx 5 C Connecting Devices to RJ45 Serial Ports Apx 6 C 1 Straight RJ 45 Cables and Rollover RJ 45 Cables Apx 6 C 2 Connecting DB 9M DTE D...

Страница 10: ...mbly TSM Series DC Units Only 4 2 4 2 Terminal Block Assembly RSM Series DC Units Only 4 2 5 1 Boot Priority Example 1 5 34 5 2 Boot Priority Example 2 5 35 14 1 Web Access Parameters Text Interface Only 14 1 B 1 TSM Series and RSM xRy Series RS232 Port Interface RJ45 Apx 3 B 2 RSM Series RS232 Port Interface DB9 Apx 3 C 1 Straight Cables Apx 6 C 2 Rollover Cables Apx 6 C 3 DX9F DTE RJ Snap Adapte...

Страница 11: ...strator defined serial ports and plugs The ViewOnly level allows you to check unit status but does not allow control of serial ports or switched outlets or access to configuration menus The TSM RSM includes full Radius LDAP and TACACS capability DHCP an IP Address filter and an invalid access lockout feature An Audit Log records all user access login and logout times and command actions and an Ala...

Страница 12: ...s Throughout this User s Guide all of these units are referred to as the TSM RSM In addition when power control features are discussed all RSM 16R16 models RSM 8R8 models and RSM 2R4 models are referred to as RSM xRy Series Units Typographic Conventions e g X Indicates a control character For example the text X Control X indicates the Ctrl key and the X key must be pressed simultaneously COURIER F...

Страница 13: ...is operational DCD Data Carrier Detect Lights when the DCD signal is present ACTIVITY LEDs A series of LEDs which will light when a CTS signal is detected and will flash during data transmission to indicate activity at the corresponding port TSM 8 series units include 8 Activity LEDs TSM 24 series units include 24 Activity LEDs TSM 40 series units include 40 Activity LEDs STATUS DEFAULT RESET ON R...

Страница 14: ...applications Power On Off Switch Master Power Switch Note The Power On Off Switch is not present on TSM series units that include the optional secondary power inlet I O Ethernet 10 100 PHONE ACT LINK 100 120V 50 60Hz 0 1 0 06A SETUP PORT SERIAL PORTS 1 2 3 4 5 Figure 2 2 TSM 8 Series Units Back Panel I O Ethernet 10 100 PHONE ACT LINK 100 120V 50 60Hz 0 1 0 06A 1 3 5 7 9 11 13 15 10 12 14 16 17 19...

Страница 15: ... 192 168 168 168 This allows you to connect to the unit without first assigning an IP address Note that the Network Port also includes two small LED indicators for Link and Data Activity For more information on Network Port configuration please refer to Section 5 9 Notes Some TSM series units include an optional secondary RJ45 Ethernet port This allows the TSM to be connected to both a primary net...

Страница 16: ...fault parameters as described in Section 2 11 Ã RDY Ready Flashes to indicate unit is operational Ä ACTIVITY LEDs A series of LEDs which will light when a CTS signal is detected and will flash during data transmission to indicate activity at the corresponding port RSM 8 series units include 8 Activity LEDs RSM 16 series units include 16 Activity LEDs CLEAR SET ON RDY ACTIVITY 1 2 3 4 5 6 7 8 www w...

Страница 17: ...o console ports on target devices Standard DB9 connectors configured as DTE ports The RS232 ports are similar to a serial port on a PC When connecting a modem use a standard serial cable When connecting a PC or other DTE device please refer to Section 4 5 and Appendix B and Appendix C RSM 8 series units include 8 Serial Ports RSM 16 series units include 16 Serial Ports à Power Inlet An IEC 320 C14...

Страница 18: ...ease refer to Section 4 5 and Appendix B and Appendix C Port Activity Indicators A series of LEDs which will light when a CTS signal is detected and flash during data transmission to indicate activity at the port RESET Button Restarts the RSM 16R16 as described in Section 2 11 DEFAULT Button Switches all plugs Off or sets plugs to default values as described in Section 2 11 ON Indicator Lights whe...

Страница 19: ...ower supply and secondary fallback power supply to Branch B Also includes cable keepers not shown Branch A Switched Outlets Eight switched AC outlets that are powered by the Branch A Power Inlets RSM 16R16 1 Eight 8 each NEMA 5 15R Outlets RSM 16R16 2 Eight 8 each IEC320 C13 Outlets Branch B Switched Outlets Eight switched AC outlets that are powered by the Branch B Power Inlets RSM 16R16 1 Eight ...

Страница 20: ... ETH0 the bottom Network Port is ETH1 When connecting only a single network cable to an RSM 8R8 series unit that includes the optional secondary Network Port make certain to connect to Port ETH0 Serial Ports For connection to console ports on target devices Standard RJ45 connectors configured as DCE ports For more information on connecting devices to the serial ports please refer to Section 4 5 an...

Отзывы: