
3-1
3. Getting Started
This section describes a simplified installation procedure for the RSM-8R hardware,
which will allow you to communicate with the unit in order to demonstrate basic features
and check for proper operation.
Note that this Quick Start procedure does not provide a detailed description of unit
configuration, or discuss advanced operating features in detail. For more information,
please refer to the remainder of this User’s Guide
3.1. Apply Power to the RSM-8R
Refer to the safety precautions listed at the beginning of this User's Guide, and then
connect the unit to an appropriate power source. Connect the power supply cable to
the unit’s power inlet, snap the Cable Keeper into place, and then connect the cable to
an appropriate power supply. Please refer to the table below for information concerning
power requirements and maximum load. Note that RSM-8R8 series units feature two
power inlets.
Model No.
Total
Outlets
Input
Voltage
Input Feed
Max. Load
RSM-8R4-1
4
100 to 120 VAC
15 Amp
12 Amps*
RSM-8R4-2
4
100 to 240 VAC
15 Amp
12 Amps*
RSM-8R4-1-DCM
4
100 to 120 VAC
15 Amp
12 Amps*
RSM-8R4-2-DCM
4
100 to 240 VAC
15 Amp
12 Amps*
RSM-8R8-1**
8
2 ea., 100 to 132 VAC**
20 Amp
16 Amps*
RSM-8R8-2***
8
2 ea., 200 to 240 VAC***
20 Amp
16 Amps*
*
In accordance with UL requirements for branch circuits, this value has been
de-rated to 80%.
** The input voltage for RSM-8R8-1 units must be between 100 and 132 VAC.
Other voltages will cause damage to the unit.
*** The input voltage for RSM-8R8-2 units must be between 200 and 240 VAC.
Other voltages will cause damage to the unit.
When power is applied to the RSM-8R, the ON LED on the instrument front panel should
light, and the RDY LED should begin to flash within 90 seconds. This indicates that the
unit is ready to receive commands.