Original Operating Instructions
BATx0280-ES-1-400-1 (Outdoor)
Troubleshooting
O_BATx0280-ES-1-400-1_(Outdoor)_V1.3_GB
Page
54
of
69
Table 5: Extract of BAT Error Codes (continued)
Code
Error Description
Corrective Action
157
OV-Protection_/_Filter_Fuses
Check OV-Protection
158
Insulation Error
Check Insulation
161
Inverter_HW_Error_L1
Check Powerstack
162
Inverter_HW_Error_L2
Check Powerstack
163
Inverter_HW_Error_L3
Check Powerstack
164
Port_Idc_error
Check Idc-Sensor connection
169
Precharge_DC-Link
Check Precharge circuit
Check DC-Source
171
Grid_rotation
Check gird rotation
172
Switch_on_condition failed
Check Grid voltage / frequency
174
Frequency_error
Check frequency
175
Island_Grid_detected
Check Grid voltage
6.1.1 BAT Error Codes 11-21
Corrective action:
1.
Clean
the cooling air inlet and cooling air outlet (Figure 4, Figure 5).
2.
Check
the insect meshes (cooling air inlet and outlet) for pollutions.
If insect meshes are polluted,
remove
insect meshes on back and top of
housing.
NOTICE: The covers are connected with the PE conductor to the cabinet.
3.
Clean
insect meshes.
4.
Fix
insect meshes.
6.1.2 BAT Error Codes 22-29
Corrective action:
1.
Check
if the ambient temperature is within the specified limits (Table 11).
6.1.3 BAT Error Codes 66-68, 71-73, 76-78, 116-118, 121-123, 126-128, 175
Corrective action:
1.
Ensure
that the motor protecting switch (-F31) in position
I
.
2.
Measure
the AC voltage.
3.
Check
if the values are within the specified limits.
The values can be seen in the
Interface Description.
6.1.4 BAT Error Codes 81, 82, 131, 132
Corrective action:
1.
Measure
the DC voltage. (Section 4.3)
2.
Check
if the values are within the specified limits.
The values can be seen in the
Interface Description.