3.5.1.1 Grounding
Required material:
•
1 x M10x20 mm hexagon screw
•
1 x
10.5 mm conical spring washer
Procedure:
1.
Route
the cable through the cable entry grommet.
2.
Connect
the PE conductor to the press-in nut (Figure 12).
3.
Tighten
the screw with a torque of
44 Nm
.
NOTICE: The cable lug must be suitable for a M10 screw.
4. Fix
the cable with a cable clamp.