COMMISSIONING
6 720 804 532 (2012/09)
32
GAS PRESSURE WITHIN THE SYSTEM
Refer to the figures below for natural gas or L.P.G gas pressures.
The pressure at the boiler must not be less than the pressure read at the
meter minus:
• 1 mbar for Natural Gas
• 2.5 mbar for L.P.G.
The pressure drop from the meter to the gas valve must not be more
than:
• 2.5 mbar for Natural Gas
• 4 mbar for L.P.G.
If the pressure drops are greater than shown below, then this would
indicate a problem with the pipe work or connections within the system.
Fig. 66 Natural gas pressures
Fig. 67 L.P.G. pressures
5.5.2
CHECKING THE GAS RATE
▶ The gas rate should be measured at the gas meter after 10 minutes
operation at maximum.
See technical data section at the front of this manual.
▶ Where a gas meter is not available (e.g. L.P.G.) the CO/CO
2
must be
checked to the units shown in the setting of the air/gas ratio, refer to
section 6.6.
▶ If pressure and gas rate are satisfactory press the service button again
and the boiler will return to normal operation.
– If left in the service mode the control will return to normal operation
after 15 minutes.
▶ Close the gas isolation valve.
▶ Remove the manometer.
▶ Re-seal the screw in the gas inlet pressure test point.
▶ Open the gas isolation valve.
▶ Ensure that there are no gas leaks.
▶ Replace the outer case.
5.5.3
DOMESTIC HOT WATER:
Controlling the hot water temperature:
The hot water temperature can be set to between approximately 40°C
and 60°C using the DHW temperature control.
5.6
FINISHING COMMISSIONING
5.6.1
REPLACE OUTER CASING:
▶ Replace outer casing making sure that the securing points are
properly located.
▶ Replace top two screws (1).
▶ Tighten bottom two screws (2).
Fig. 68 Fitting case
Ensure inlet pressure is satisfactory with all other gas
appliances working.
≤
Equal to or less than.....
NOTICE:
Do not continue commissioning until the correct gas
pressure is achieved.
Meter
Boiler inlet
Gas Control
valve
19 - 23 mbar
18 - 22 mbar
16.5 - 20.5 mbar
1 mbar
drop
1.5 mbar
drop
Natural Gas
< 2.5mbar
difference
6720644744-44.2Wo
Gas Control
valve
L.P.G.
< 4.0mbar
difference
Regulator
Boiler inlet
32 - 45 mbar
29.5 - 42.5 mbar
28 - 41 mbar
2.5 mbar
drop
1.5 mbar
drop
6720644744-45.2Wo
NOTICE:
Domestic Hot Water
▶ The hot water temperature can only be controlled
when the “Optional diverter valve” kit is fitted.
1.
1.
2.
2.
6720643895-54.1W
o