SYNCONpanel - Transportable Remote Synchronizing Panel
Voltage Controller
In case of transfer operation mode, the unit controls frequency and voltage with droop behavior.
For the transfer operation mode, a droop characteristic for the voltage controller is required, otherwise the gen-
erator set would not be able to maintain a stable reactive power being in parallel with the mains.
Volt.controller
droop 02.0%
Frequency controller droop
0 to 20 %
The internally set value for voltage will be reduced by the configured value, when
the maximum reactive power of the generator is reached.
Example: In case of a 200 kW engine power, the reactive power will be 200 kvar as
base value.
Setpoint Voltage-Control
Droop (static curve)
80
84
88
92
96
100
104
0
10
20
30
40
50
60
70
80
90
100
110
P
reactive
in %
V
Nom
ina
l
in %
isochron
isotroop
2 %
Figure 6-2: Voltage controller droop characteristic
Power Factor Controller
In case of transfer and mains parallel operation mode, the power factor controller is required.
Pow.fact.contr.
ON
Power factor controller
ON / OFF
ON
................ In a mains parallel operation automatic control of the power factor is
carried out. If there are excessively low currents (secondary current
less than 5 % I
rated
) the power factor cannot be accurately measured.
In order to prevent power swings, the controller automatically locks
the power factor at a set value. The subsequent screens of this func-
tion are displayed.
OFF
.............. Power factor control is not performed, and the subsequent screens of
this function are not displayed.