Password Configuration
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
Once the code level is entered, access to the configuration menus will be allowed for two hours or until
another password is entered into the control. If a user needs to exit a code level then code level CL0
should be entered. This will block any configuration of the control. A user may return to CL0 by allow-
ing the entered password to expire after two hours or by changing any one digit on the random number
generated on the password screen and entering it into the unit.
Parameter 10413
Define level 1
code 0000
Code level 1 (Customer)
0000 to 9999
This parameter is only accessible with code level 2 rights. After the password has
been set for this parameter, only the personnel who are assigned this password will
have access rights to this code level. When the CL1 (Customer) password is entered,
only select parameters may be accessed. Refer to page 39 for more information to
password protection.
The default setting for this code level is
CL1 = 0 0 0 1
Parameter 10411
Define level 2
code 0000
Code level 2 (Commissioner)
0000 to 9999
This parameter is only accessible with code level 2 rights. After the password has
been set for this parameter, only the personnel who are assigned this password will
have access rights to this code level. When the CS2 (Commissioner) password is en-
tered, all parameters may be accessed. Refer to page 39 for more information to
password protection.
The default setting for this code level is
CL2 = 0 0 0 2