Manual 37615C
SPM-D2-10 - Synchronizing Unit
© Woodward
Page 53/68
Parameter 5505
Phase matching
Gain 00
Phase matching control = ON
Phase-angle-zero-control gain
1 to 36
This configuration screen only appears, if the phase matching control is configured
ON!
When phase matching control is enabled, this gain determines how much the output
signal is changed depending on phase difference. By increasing the gain, the re-
sponse is increased to permit larger corrections to the variable to be controlled result-
ing in longer ON time periods. The farther out of tolerance the process is the larger
the response action is to return the process to the tolerance band. If the gain is con-
figured too high, the result is excessive overshoot/undershoot of the desired value.
Prior to setting the value for this gain, the frequency controller must be enabled and
properly adjusted.
Parameter 5506
Phase matching
df start 0.00Hz
Phase matching control = ON
Differential frequency for starting phase-angle-zero-control
0.02 to 0.25 Hz
This configuration screen is displayed only if the phase matching control is enabled!
The control enables phase matching when the generator and busbar/mains frequency
differential falls below the value configured here.
Synchronization Time Monitoring
Parameter 3060
Sync.time contr.
Alarm ON
Synchronization time monitoring
ON/OFF
ON
................ The synchronization timer is enabled. When a synchronization opera-
tion is initiated, this timer starts to count down. If the timer expires
prior to the synchronization being completed and the breaker closing,
the warning message "Synchronization time" is displayed. In addition
to the warning message the “Ready for operation" relay is de-energized
and the synchronization operation is terminated. The alarm condition
may be reset by pressing and holding the "Clear" pushbutton for at
least 3 seconds or removing one of the required conditions for syn-
chronization (e.g. de-energize terminal 3 "Release CB"). The subse-
quent screens of this function are displayed.
OFF
.............. The synchronization time is not monitored and the control will contin-
ue to attempt to synchronize until the circuit breaker is successfully
closed or the synchronization it terminated. The subsequent screens of
this function are not displayed.
Parameter 3063
Sync.time contr.
Delay time 000s
Final value for synchronization time monitoring
10 to 999 s
If the synchronization time monitoring has been enabled, the control will attempt to
synchronize for up to the time period configured here.