![Woodward SPM-D2-10 Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/woodward/spm-d2-10/spm-d2-10_manual_995878041.webp)
Manual 37615C
SPM-D2-10 - Synchronizing Unit
© Woodward
Page 41/68
Configure Basic Settings
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
WARNING
The following values must be entered correctly to ensure proper monitoring of the generator. Failure to
do so may lead to incorrect measuring of parameters resulting in damage to or destruction of the gen-
erator and/or personal injury or death!
Parameter 1750
Rated Frequency
fn = 00.0Hz
System rated frequency
48.0 to 62.0 Hz
The system rated frequency, which in most cases is 50 Hz or 60 Hz, is entered in this
screen.
Parameter 5500
Generator freq.
Setpoint= 00.0Hz
Generator frequency set point
48.0 to 62.0 Hz
The generator (variable system) frequency set point is entered in this screen. The fre-
quency controller will reference this value for no-load and isolated operations.
Parameter 1800
Gen. voltage
secondary 000V
Secondary generator voltage (measuring transducer)
50 to 440 V
The secondary voltage for the generator (variable system) potential transformers is
configured here in Volts. This entry is the reference voltage for displaying the system
or primary voltage. If potential transformers are not used, the system voltage must be
entered here. Example: if a generator rated for 400v is used without PTs, then 400v
must be entered for this parameter.
Parameter 1803
Mains voltage
secondary 000V
Secondary mains voltage (measuring transducer)
50 to 440 V
Secondary voltage for the mains (reference system) potential transformers is config-
ured here in Volts. This entry is the reference voltage for displaying the system or
primary voltage. If potential transformers are not used, the system voltage must be
entered here. Example: if a main rated for 400v is used without PTs, then 400v must
be entered for this parameter.
Parameter 1801
Gen. voltage
primary 00.000kV
Primary generator voltage (measuring transducer)
0.1 to 65.0 kV
The primary voltage for the generator (variable system) is configured here in kV.
This entry is the generator voltage to be displaying on the controller. If potential
transformers are not used, the generator voltage must be entered here. Example: if a
generator rated for 400v is used without PTs, then 00.400kV must be entered for this
parameter.
Parameter 1804
Mains voltage
primary 00.000kV
Primary mains voltage (measuring transducer)
0.1 to 65.0 kV
The primary voltage for the mains (reference voltage) is configured here in kV. This
entry is the generator (variable system) voltage to be displaying on the controller. If
potential transformers are not used, the generator voltage must be entered here. Ex-
ample: if a generator rated for 400v is used without PTs, then 00.400kV must be en-
tered for this parameter.
Parameter 1767
Rated voltage
......Vn = 000V
System rated voltage
70 to 420 V
The system rated voltage is entered in this screen. The controller references this val-
ue to determine the permissible voltage range for synchronization.
This setting affects the synchronization limits (refer to Table 5-3 on page 23).