Operation Manual 37107F
MFR 3 - Multi Function Relay
© Woodward
Page 97/165
Generator Overload Monitoring
NOTE
All percentage indications of the power are in relation to the generator rated power (Parameter 28).
Function:
"Positive real power not within the permissible range"
The real power of the generator is outside the configured overload limit values, and an alarm is issued.
Parameter
125
Gen.overload
monitoring ON
Generator overload
ON/OFF
ON
................ Generator overload monitoring is enabled. The subsequent screens of
this function are displayed.
OFF
.............. Generator overload monitoring is not performed. The subsequent
screens of this function are not displayed.
Parameter
126
Gen.overload MOP
resp.value 000%
Generator overload: limit MOP (Mains Operating in Parallel)
80 to 150 %
The value configured in this screen is a percentage of the configured generator
rated power. If this level is reached or exceeded for the configured delay time, the
unit issues an alarm and opens the GCB.
Tripping of class F2 alarm
without load shedding
Parameter
127
Gen.overload MOP
Delay 00s
Generator overload: delay MOP (Mains Operating in Parallel)
0 to 99 s
The generator overload MOP monitoring threshold limit must be exceeded, without
interruption, for the time period configured here before the configured relay will be
energized.
Parameter
128
Gen.overload IOP
resp.value 000%
Generator overload: limit IOP (Isolated Operating in Parallel)
80 to 150 %
The value configured in this screen is a percentage of the configured generator
rated power. If this level is reached or exceeded for the configured delay time, the
unit issues an alarm and opens the GCB.
Tripping of class F2 alarm
without load shedding
Parameter
129
Gen.overload IOP
Delay 00s
Generator overload: delay IOP (Isolated Operating in Parallel)
0 to 99 s
The generator overload IOP monitoring threshold limit must be exceeded, without
interruption, for the time period configured here before the configured relay will be
energized.