2.1.4

V[4]: Voltage Protection Pre-Configured According to the HV
Requirements

V[4] . Mode

[Device planning]

V<

Voltage protection instance number 4: Pre-configured
as undervoltage protection for HV connections.

For the password-protection (of access level “S.3”), see
the “Security” chapter in the generic MRU4 User
Manual.

S.3

V[4] . Function

[Protection Para / Set 1…4 / V-Prot / V[4]]

• Set 1: active
• Set 2: active
• Set 3: active
• Set 4: active

Permanent activation or deactivation of module/stage:
This instance V[6] is pre-configured for HV
applications.

It is active by default. This means that if you need to
switch to LV protection, you have to make the following
settings:

• »V[1] . Function« = “active”,

and the same for »V[2]«, »V[3]«

• »V[4] . Function« = “inactive”,

and the same for »V[5]«, »V[6]«

For the password-protection (of access level “P.2”), see
the “Security” chapter in the generic MRU4 User
Manual.

P.2

V[4] . Measuring Mode

[Protection Para / Set 1…4 / V-Prot / V[4]]

• Set 1: Phase to Phase
• Set 2: Phase to Phase
• Set 3: Phase to Phase
• Set 4: Phase to Phase

Measuring/Supervision Mode: Determines if the phase-
to-phase or phase-to-earth voltages are to be
supervised.

For the password-protection (of access level “P.2”), see
the “Security” chapter in the generic MRU4 User
Manual.

P.2

12

MRU4

MRU4-3.6-EN-G99

2 G99-Specific Protection Settings

2.1.4 V[4]: Voltage Protection Pre-Configured According to the HV Requirements

Содержание HighPROTEC MRU4-2 G Series

Страница 1: ...Version 3 6 g Build 48004 Original document English Supplement MRU4 3 6 EN G99 2020 MRU4 2xxxxx G Voltage Protection G99 Type Tested Variant...

Страница 2: ...n Germany Telephone 49 0 21 52 145 1 Internet www woodward com Sales Telephone 49 0 21 52 145 331 Fax 49 0 21 52 145 354 Email SalesPGD_EMEA woodward com Service Telephone 49 0 21 52 145 614 Fax 49 0...

Страница 3: ...ding to the HV Requirements 12 2 1 5 V 5 Voltage Protection Pre Configured According to the HV Requirements 14 2 1 6 V 6 Voltage Protection Pre Configured According to the HV Requirements 16 2 2 G99 S...

Страница 4: ...oint below 110 kV 10 8 MW 50 MW Type D connection point 110 kV and or registered capacity 50 MW Depending on the type to be protected the EREC G99 1 6 makes the following requirements for the voltage...

Страница 5: ...es of the voltage protection module that are pre configured as follows V 1 is pre configured as an undervoltage protection according to the LV requirements V 2 is pre configured as overvoltage protect...

Страница 6: ...HV settings enabled This means that for an LV protection you have to make the following settings V 1 Function active and the same for V 2 V 3 V 4 Function inactive and the same for V 5 V 6 For the pa...

Страница 7: ...h phase to phase voltages VT con Phase to Phase then the setting of Measuring Mode is ignored and internally set to Phase to Phase instead so that Vn VT sec Set to the required threshold by default bu...

Страница 8: ...HV settings enabled This means that for an LV protection you have to make the following settings V 1 Function active and the same for V 2 V 3 V 4 Function inactive and the same for V 5 V 6 For the pa...

Страница 9: ...h phase to phase voltages VT con Phase to Phase then the setting of Measuring Mode is ignored and internally set to Phase to Phase instead so that Vn VT sec Set to the required threshold by default bu...

Страница 10: ...HV settings enabled This means that for an LV protection you have to make the following settings V 1 Function active and the same for V 2 V 3 V 4 Function inactive and the same for V 5 V 6 For the pas...

Страница 11: ...phase to phase voltages VT con Phase to Phase then the setting of Measuring Mode is ignored and internally set to Phase to Phase instead so that Vn VT sec Set to the required threshold by default but...

Страница 12: ...u need to switch to LV protection you have to make the following settings V 1 Function active and the same for V 2 V 3 V 4 Function inactive and the same for V 5 V 6 For the password protection of acc...

Страница 13: ...phase to phase voltages VT con Phase to Phase then the setting of Measuring Mode is ignored and internally set to Phase to Phase instead so that Vn VT sec Set to the required threshold by default but...

Страница 14: ...need to switch to LV protection you have to make the following settings V 1 Function active and the same for V 2 V 3 V 4 Function inactive and the same for V 5 V 6 For the password protection of acce...

Страница 15: ...phase to phase voltages VT con Phase to Phase then the setting of Measuring Mode is ignored and internally set to Phase to Phase instead so that Vn VT sec Set to the required threshold by default but...

Страница 16: ...e the following settings V 1 Function active and the same for V 2 V 3 V 4 Function inactive and the same for V 5 V 6 Furthermore this stage is optional for Type D applications and may be set to inacti...

Страница 17: ...phase to phase voltages VT con Phase to Phase then the setting of Measuring Mode is ignored and internally set to Phase to Phase instead so that Vn VT sec Set to the required threshold by default but...

Страница 18: ...planning f Frequency protection instance number 1 Configured as underfrequency protection This setting is fixed according to the G99 requirements and cannot be modified Fixed setting f 1 f Protection...

Страница 19: ...Set 1 47 00 Hz Set 2 47 00 Hz Set 3 47 00 Hz Set 4 47 00 Hz Pickup value for underfrequency This setting is fixed according to the G99 requirements and cannot be modified Fixed value f 2 t Protection...

Страница 20: ...et 1 52 00 Hz Set 2 52 00 Hz Set 3 52 00 Hz Set 4 52 00 Hz Pickup value for underfrequency This setting is fixed according to the G99 requirements and cannot be modified Fixed value f 3 t Protection P...

Страница 21: ...s enabled by default but can be disabled For the password protection of access level S 3 see the Security chapter in the generic MRU4 User Manual S 3 Intertripping Function Protection Para Set 1 4 Int...

Страница 22: ...cannot be modified Fixed setting df dt df dt Protection Para Set 1 4 Intercon Prot Mains Decouplg df dt Set 1 1 00 Hz s Set 2 1 00 Hz s Set 3 1 00 Hz s Set 4 1 00 Hz s Measured value calculated Rate...

Страница 23: ...Cmd3 V 3 TripCmd SG 1 Off Cmd4 V 4 TripCmd SG 1 Off Cmd5 V 5 TripCmd SG 1 Off Cmd6 V 6 TripCmd SG 1 Off Cmd7 f 1 TripCmd SG 1 Off Cmd8 f 2 TripCmd SG 1 Off Cmd9 f 3 TripCmd SG 1 Off Cmd10 df dt TripCm...

Страница 24: ...om Service Fax 49 0 21 52 145 354 Telephone 49 0 21 52 145 614 Email industrial support woodward com Woodward has company owned plants subsidiaries and branches as well as authorized distributors and...

Отзывы: