Input, Output and LED Settings
LED configuration
The LEDs can be configured within menu:
[Device Para/LEDs/Group X]
Attention must be paid that there are no overlapping functions due to double or
multiple LED assignment of colors and flashing codes.
If LEDs are parameterized
»Latched=active«,
they
will k
eep (return into) their
blink code/color even if there is a break within the power supply.
If LEDs are parameterized
»Latched=active«,
The LED blink code will also
retain, if the LED is reprogrammed in another way. This applies also if
»Latched
is set to ina
ctive«. Resetting a LED that has latched a signal will always require
an acknowledgement.
This chapter contains information on the LEDs that are placed on the left hand
of the display (group A).
If your device is also equipped with LEDs on the right hand of the display
(group B), the information in this chapter is valid analog. The only difference is
“group A” and “group B” within the menu paths.
Via push button »INFO« it is always possible to display the current alarms/alarm texts that are assigned to an LED.
Please refer to chapter
Navigation (description of the »INFO-key«).
Set the following parameters for each LED:
»Latching/self holding function«: If »Latching« is set to »active«, the state that is
set
by the alarms will be
stored. If latching
»Latching« is set to »inactive«, the LED always adopts the state of those alarms that were
assigned.
»Acknowledgment« (signal from the »assignment list«)
»LED active color«, LED lights up in this color in case that at least one of the allocated functions is valid (red,
red flashing, green, green flashing, off).
»LED inactive color«, LED lights up in this color in case that none of the allocated functions is valid (red, red
flashing, green, green flashing, off).
Apart from the
LED for System OK, each LED can be assigned up to five functions/alarms out of the
»assignment list«.
»Inverting« (of the signals), if necessary.
186
MCDLV4
DOK-HB-MCDLV4-2E
Содержание HighPROtec MCDLV4
Страница 1: ...Manual Line Differential Protection MCDLV4 Software Version 3 4 a DOK HB MCDLV4 2E Revision A English...
Страница 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Страница 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Страница 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Страница 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Страница 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Страница 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Страница 822: ...Protective Elements Name Description Profibus Scada Cmd 16 Scada Command 822 MCDLV4 DOK HB MCDLV4 2E...
Страница 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Страница 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Страница 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...
Страница 1070: ...Supervision 1070 MCDLV4 DOK HB MCDLV4 2E...